aci XT 0-5V 0002 Installation And Operation Instruction Manual

Advertisement

Quick Links

READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!
APPLICATION
The XT 0-5V 0002 provides temperature space monitoring with a backlit LCD. The unit will
display a Temperature based on a voltage input. A setup menu provides easy output and display
configuration changes.
INSTALLATION
Precautions
• R
EMOVE POWER BEFORE WIRING
WITH POWER APPLIED
.
BOARD
• A
N ISOLATION TRANSFORMER IS RECOMMENDED WHEN POWERING THE
DEVICE WITH
• D
O NOT RUN THE
POWERED WIRING
• F
AILURE TO WIRE DEVICES WITH THE CORRECT POLARITY WHEN USING A
SHARED TRANSFORMER MAY RESULT IN DAMAGE TO ANY DEVICE POWERED
BY THE SHARED TRANSFORMER
AUTOMATION COMPONENTS, INC
2305 Pleasant View Road
Middleton, Wisconsin 53562 (888) 967-5224
www.workaci.com
Installation and Operation Instructions
. N
. D
O NOT ALLOW LIVE WIRES TO TOUCH THE CIRCUIT
24VAC.
XT 0-5V 0002
WIRING IN ANY CONDUIT WITH LINE
.
.
Page 1 of 7
EVER CONNECT OR DISCONNECT WIRING
XT 0-5V 0002
Version : 3.0
I0000740

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XT 0-5V 0002 and is the answer not in the manual?

Questions and answers

Summary of Contents for aci XT 0-5V 0002

  • Page 1 XT 0-5V 0002 READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION! APPLICATION The XT 0-5V 0002 provides temperature space monitoring with a backlit LCD. The unit will display a Temperature based on a voltage input. A setup menu provides easy output and display configuration changes.
  • Page 2 A 16 to 22 AWG shielded cable is recommended for all sensor installations. Be sure to connect the cable shield to the ground at the controller only. Seven wires are needed for the XT 0-5V 0002. All outputs and inputs are common ground referenced.
  • Page 3: Normal Mode

    OPERATION Keypad The keypad comes in a 3 button version. Normal Mode The LCD can display temperature, and occupied status. The display configuration can be setup when ordered or changed through the setup menu. The backlight will turn on when the any key is pressed and will turn off 10 seconds after the last key press.
  • Page 4 Voltage Step Degrees F 0.000 0.073 60.5 0.146 0.220 61.5 0.293 0.366 62.5 0.439 0.512 63.5 0.585 0.659 64.5 0.732 0.805 65.5 0.878 0.951 66.5 1.024 1.098 67.5 1.171 1.244 68.5 1.317 1.390 69.5 1.463 1.537 70.5 1.610 1.683 71.5 1.756 1.829 72.5...
  • Page 5: Setpoint Mode

    Setpoint Mode Press to get into setpoint mode and change the setpoint. If temperature is displayed in the large numbers, the temperature setpoint will adjust when pressed. If no keys are pressed for 10 seconds the unit will automatically return to normal operation.
  • Page 6: Setup Menu

    Setup Menu Additional Options Menu Temperature Menu RH Menu Display Menu Fan Menu System Menu Sensor Setup Sensor Sensor Setup Setup Setup Setup Setup Sensor Sensor Sensor Display Display Display Display Display Display Temperature Options Systems Options Additional Options SELECT RH Options Fan Options Display Options...
  • Page 7: Specifications

    RoHS, REACH Warranty Statement The A/TUC2 Series and the A/TUCH2 Series are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’s SENSORS AND TRANSMITTERS CATALOG or can be found on ACI’s web site, which is: www.workaci.com...

Table of Contents