BACnet / Modbus DUCT SERIES
Installation & Operation Instructions
GENERAL INFORMATION
The BACnet MS/TP / Modbus RTU Duct Series sensor
is designed for use with electronic controllers in
commercial heating and cooling building manage-
ment systems. The ACI BACnet MS/TP /Modbus RTU
Duct Series sensor can be ordered to monitor
temperature, RH, or temp/RH in commercial HVAC
ductwork. It uses BACnet MS/TP or Modbus RTU for
physical connection to a BAS or controller, has dip
switches to set addresses and baud rate, parity and
stop bits (Modbus RTU only) and has on board
end-of-line termination. There is no analog output.
WIRING INSTRUCTIONS
The BACnet/Modbus Duct Series temperature
sensor has a depluggable terminal block located on
the front of the PCB. For ease of wiring, we
recommend removing the block, wiring, and
reattaching before mounting. 16 to 22 AWG two
conductor shielded cable is recommended for
powering the sensors.
ACI recommends using Belden 3105 or compatible
cable for RS-485 communication wiring. This wire has
120 ohm input impendence. The terminal blocks
allow for (1) or (2) wires to be connected in each
position for daisy chaining. Daisy chain the RS-485
wiring and do not use "Star" or "T" wiring. Avoid
running communication wires next to AC line voltage
wires. These can be sources of noise that can a ect
signal quality.
PRECAUTIONS
• Remove power before wiring. Never connect
or disconnect wiring with power applied.
• It is recommended you use an isolated
UL-listed class 2 transformer when powering
the unit with 24 VAC. Failure to wire the devices
with the correct polarity when sharing
transformers may result in damage to any
device powered by the shared transformer.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
FIGURE 1: ENCLOSURE
DIMENSIONS
PLASTIC BOX (-PB): TEMP. ONLY
3.60"
(91.44 mm)
2.25"
(57.15 mm)
4.79"
(121.55 mm)
EURO (-EH): RH and RH/TEMP.
4.30"
(109.22 mm)
2.12"
(53.72 mm)
Page 1
Phone: 1-888-967-5224
Website: workaci.com
1.51"
(38.25 mm)
3.01"
(76.51 mm)
2.35"
(59.80 mm)
3.80"
(96.56 mm)
1.90"
(48.28 mm)
10.05"
(255.32 mm)
Version: 2.0
I0000927

Advertisement

loading

Summary of Contents for aci BACnet Series

  • Page 1 3.60" (91.44 mm) ment systems. The ACI BACnet MS/TP /Modbus RTU Duct Series sensor can be ordered to monitor temperature, RH, or temp/RH in commercial HVAC ductwork. It uses BACnet MS/TP or Modbus RTU for...
  • Page 2: Mounting Instructions

    BLOCKS solenoids, or other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of the power supply.
  • Page 3 Now fasten and insert (2) screws #8 x ¾” TEK (provided and recommended) through the ACI’s Modbus RTU sensors are slave devices. Only mounting holes in the flange and tighten until one master is connected to the bus and several the unit is held firmly to the duct.
  • Page 4 LED INFORMATION TABLE 2: BAUD RATE SELECTION BAUD RATE SW 8 SW 9 SW 10 One LED indicates four statuses. Solid green Auto-Baud shows that power is good, but no data is 9600 transmitting. A solid Amber indicates that 19200 auto-baud is set and no data has been received to 38400 set a baud rate.
  • Page 5 DEVICE NAME TABLE 4: UNIT SETTING By default, the device name is based on the type of device UNITS VALUE and the address. The device name can be a character string °F up to (32) characters in length. This can be changed once the device is connected to the network.
  • Page 6 Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master device con guration. ACI’s Modbus RTU sensors utilize 8 data bits during communication exchange. Parity and stop bit selection is performed via the SW4 switch located on the board. Dipswtiches #1 and #2 are adjusted to select the parity and stop bits - see TABLE 6.
  • Page 7 INPUT REGISTER IR 2001 2000 Temperature Range Temperature range Minimum value (Tenths). Signed Integer. 2002 2001 Temperature Range Temperature range Maximum value (Tenths). Signed Integer. 2003 2002 RH Range Min Relative Humidity range Minimum value (Tenths) 2004 2003 RH Range Max Relative Humidity range Maximum value (Tenths) 9001 9000...
  • Page 8: Warranty

    Neoprene/EPDM/SBR Polymer / UL94-HBF; FMVSS-302; MIL-R-6130C WARRANTY The ACI BACnet and Modbus RTU Room Series temperature sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site: www.workaci.com.

This manual is also suitable for:

Modbus duct series