M-wrg-s series;5016 series;5014 series.
home ventilation with heat recovery
.
for surface-mount and flush-mount installation
of m-wrg ventilation units (32 pages)
Page 1
Modbus RTU Master Part no. 5256-01 Week 45/2022 EN Meltem Wärmerückgewinnung GmbH & Co. KG V E N T I L AT I O N T H E R I G H T WAY Am Hartholz 4 · D-82239 Alling...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Contents Introduction ........................5 Notes on these operating and installation instructions ........... 5 Description ........................
Page 3
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Rules for correct usage ....................18 General .........................
Page 4
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Cleaning and maintenance ..................31 Troubleshooting ......................32 Connecting the ventilation unit to the Modbus RTU ..........
Notes on these operating and installation instructions These original operating and installation instructions contain important information that should be followed when setting up and using the M-WRG-S M (-F, -FC) ventilation unit. ► Read all the instructions carefully before starting up the ventilation unit to avoid possible risks and mistakes.
KNX or Loxone. The M-WRG-S M-F ventilation unit has various ventilation levels/programs, including a humidity control. The M-WRG-S M-FC unit has an automatic mode (humidity and CO control) in addition to the ventilation levels. The CO value is the most important measure- ment for assessing the air quality.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y EU declaration of conformity The M-WRG-S... ventilation units manufactured by Meltem Wärmerückgewinnung GmbH &...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Technical data 1.7.1 Electrical connection Operating voltage...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 1.7.5 Unit properties Type of system...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 1.7.7 Air filters Designation Filter class Standard filter (for outdoor air and extract air)
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Safety instructions These instructions contain notes that you must follow for your own personal safety and to avoid injury and damage to property.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 2.2.3 Installation in wet areas The following rules from DIN VDE 0100-701/702 (IEC 60364-7-701) apply to installation of M-WRG ventilation units in wet areas: —...
— The ventilation unit’s functions may be impaired or the unit may be damaged in rooms with a lot of dust (e.g. model-making) or corrosive gas emissions (e.g. blueprint shop, cleaning). — For any use contrary to the intended use, Meltem Wärmerückgewinnung GmbH & Co. KG shall accept no liability for any damage that may occur and offers no warranty that the ventilation unit will work perfectly and correctly.
— The ventilation unit was not installed as described in the installation manual. — The ventilation unit was flush-mounted without using a flush-mount installation kit. — Genuine parts/genuine air filters were not replaced with genuine parts. — Unapproved changes were made to the installation kit or ventilation unit. — Repairs were not carried out by Meltem or by an authorised specialist company. — The ventilation unit was operated without air filters and outer wall terminals. — The warranty does not cover wearing parts such as air filters. Liability The manufacturer’s liability shall not apply in the following cases:...
V E N T I L A T I O N & H E A T R E C O V E R Y Dimensions Fig. 4: Dimensions of the ventilation unit M-WRG-S M (-F, -FC) in millimetres Meltem Wärmerückgewinnung GmbH & Co. KG V E N T I L AT I O N T H E R I G H T WAY Am Hartholz 4 ·...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Structure and function Overview of the modules 5.1.1...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Description of the functions 5.2.1 How the M-WRG ventilation unit works Fig.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 5.2.2 How the cross-flow plate heat exchanger works The warm extract air (item 5 in Fig. 9) drawn in from the interior is routed through the chambers of the cross-flow plate heat exchanger (item 1 in Fig. 9) and heats them.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Operation at cold times of year ►...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Air filters — Never run the ventilation unit without air filters. — Always use genuine Meltem filters. These are precisely matched to your M-WRG ventilation units, ensure minimal pressure losses and will ensure a long service life from your ventilation units.
Central and local operation of the ventilation unit Operation via the Modbus RTU master The M-WRG-S M ventilation unit is controlled centrally via Modbus (Modbus RTU master using the Modbus RTU protocol). The way it is operated via a Modbus RTU master will vary according to the system in use, and the master is to be supplied by the customer.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Starting up Checking the ventilation unit before switching on for the first time ► Check the ventilation unit for damage.
Modbus RTU master. This solution allows you to control the M-WRG units individually, room-by-room, floor-by-floor or all together. They can also be demand-controlled via humidity or CO sensors. Units with the appropriate sensors are needed to record the measured values (type: M-WRG-S M-F or M-WRG-S M-FC). Local operation The step switch (item 2 in Fig. 10 on page 21) is used to set four different ventilation levels/programs; the maximum ventilation level is activated using a switching sequence and is time-limited.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Ventilation levels/programs There are different ventilation programs/levels available for selection, depending on the type of ventilation unit. These can be activated using the step switch on the ventilation unit (see section 7.2 on page 21) or via the Modbus configuration (see section 16.7 on...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y range from 15 - 60 m /h fully automatically.
This option changes the level assignment on the control units for the ventilation unit: switch position I, II, III: 20, 40, 60 m NOTICE — This option can only be selected in conjunction with M-WRG-S M-F and M-WRG-S M-FC units with humidity and/or CO control.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Filter maintenance The ventilation unit has a runtime-controlled filter monitoring function with audible indi- cator. It monitors the time since the last air filter change. If the last air filter change was more than one year ago, the filter change indicator is activated and a pending air filter change is signalled.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 12.3 Changing the air filters NOTICE ► Always switch the ventilation unit off at the mains switch (item 1 in Fig. 10 on page 21) for the filter change. On ventilation units with the M-WRG-O/NOF option, power to the unit must be switched off using the building’s miniature circuit breaker.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y ► Clean the filter ring and filter cover with a damp cloth if they are dirty (see chapter 13 on page 31). ► Dispose of the used air filters in the non-recyclable waste or as required by your coun- try’s disposal regulations.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 12.3.4 Attaching the unit cover to the ventilation unit and switching on the ventilation unit ►...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Cleaning and maintenance WARNING ► Switch off the power to the ventilation unit before cleaning.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Troubleshooting Error Cause Remedy Ventilation unit is not...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Connecting the ventilation unit to the Modbus RTU This section describes how to connect the ventilation units electrically to the Modbus and the settings and registers for the Modbus protocol.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 15.1.2 Bus cable The bus cable is connected at the connection on the Modbus master and on the 10-pole terminal block (see item 1 in Fig. 18 on page 33) on the board of the first ventila-...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 15.3 Accessing the Modbus board in the ventilation unit 15.3.1 Switching off power to the ventilation unit...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 15.3.3 Removing the network connection cover ►...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 15.4.2 Example of floor-by-floor wiring 230 V AC 230 V AC...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 15.5 Electrical installation NOTICE — The ventilation unit may be damaged if the bus cable is connected incorrectly. This will also invalidate the warranty.
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y Modbus configuration 16.1 Default settings — Start bits: 8 —...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 16.5 Registers Register Read/ Function/name Data type...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 16.6 Sensors in the different ventilation unit types Ventilation unit type Sensor type...
Operating and installation instructions M-WRG-S M (-F, -FC) ventilation unit V E N T I L A T I O N & H E A T R E C O V E R Y 16.7.2 Unbalanced NOTICE — Registers 41120, 41121, 41122 and 41132 must be written in succession.
For integration into other bus systems, the system concerned must have a Modbus RTU interface. The customer will need to clarify with the system manufacturer whether Modbus ventilation units from Meltem will work in their system. Meltem Wärmerückgewinnung GmbH & Co. KG V E N T I L AT I O N T H E R I G H T WAY Am Hartholz 4 ·...