Hinen H8000H-EU User Manual

Three-phase hybrid inverter
Hide thumbs Also See for H8000H-EU:

Advertisement

Quick Links

Dongguan Hinen New Energy Technology Co., Ltd
Adres: No.24 Dongkang Road, Dalingshan Town,
Dongguan City, Guangdong, China
Tel.: +86 (769) 89920666 ext 8318
Email: service@hinen.com
Strona internetowa: https://www.hinen.com
Hinen Australia Pty. Ltd.
Adres: Suite 503,Level 5, Tenancy 3,107 Mount Street, North Sydney
Email: service@hinen.com.au
Tel.: +61 2 7258 1272
Strona internetowa: https://au.hinen.com
Europe HL Hinen B.V.
Adres: John M. Keynesplein 1, 1066EP Amsterdam
Email: service@hinen.com
Tel.: +86 (769) 89920666 ext 8318
Strona internetowa: https://eu.hinen.com
Hinen Energy Eastern Europe
Adres: Wąska 95, 05-806 Sokołów Poland
Email: biuro@hinen.com
Tel.: +48 606 807 712
Strona internetowa: https://eu.hinen.com
Hinen South Africa (Pty) Ltd
Adres:Ground floor, Block B, 100 West Street,
Sandton.Johannesburg 2196, South Africa
Email: SAfrica@hinen.com
Tel.: +27 10 449 2306
Strona internetowa: https://za.hinen.com
Hinen Technology East Africa LIMITED
Adres: No. 6, Kirichwa Lane Court, next to
GreenhouseMall, Ngong Road, Nairobi, Kenya
Email: EAfrica@hinen.com
Tel.: +254789688999
Strona internetowa: https://za.hinen.com
Hinen West Africa LIMITED
Adres:30A Opebi Rd, IKEJA, Ikeja 101233, Lagos, Nigeria
Email: WAfrica@hinen.com
Tel.: +86 (769) 89920666 ext 8318
Strona internetowa: https://za.hinen.com
THREE-PHASE
HYBRID INVERTER
H����H-EU / H�����H-EU / H�����H-EU
User Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the H8000H-EU and is the answer not in the manual?

Questions and answers

Summary of Contents for Hinen H8000H-EU

  • Page 1 Dongguan Hinen New Energy Technology Co., Ltd THREE-PHASE Adres: No.24 Dongkang Road, Dalingshan Town, Dongguan City, Guangdong, China Tel.: +86 (769) 89920666 ext 8318 Email: service@hinen.com HYBRID INVERTER Strona internetowa: https://www.hinen.com Hinen Australia Pty. Ltd. Adres: Suite 503,Level 5, Tenancy 3,107 Mount Street, North Sydney H����H-EU / H�����H-EU / H�����H-EU...
  • Page 2 · Incompatible batteries, loads, or other devices are connected to the inverter system. The manual cannot include complete information about the photovoltaic (PV) system. The reader can get additional information about other devices at https://www.hinen.com or on the webpage of the respective component manufacturer.
  • Page 3: Safety Warning

    Symbol Definition and Explanation Safety warning Warning! Any installation and operation must be carried out by a qualified electrician in accordance with local grid or company standards, wiring rules or requirements (such as AS ���� and AS/NZS ���� in Australia). Failure to follow the warning signs in this manual could result in personal injury.
  • Page 4: Table Of Contents

    �. � Connect WIFI Module �� Contents �. � .� Logger Installation �� �. � .� Logger Status �� �. Introduction �.�.� Abnormal State Troubleshooting �� �.� Introduction to Operating Modes � �. � The Connection Mode of COM �� �.�...
  • Page 5: Introduction

    �. Introduction �.�.�.� Anti-Backflow Setting �� The inverter is a hybrid or bidirectional solar inverter, suitable for solar systems involving PV, batteries, loads, �.�.�.� PU Settings �� and grid systems for energy management. The energy generated by the photovoltaic system can be used to �.�.�.�...
  • Page 6: Introduction To Operating Modes

    �.� Introduction to Operating Modes Light Board Display : Light Board Display : Mode � Mode � According to different system configurations and layouts, the inverter can usually be set to the following When the grid is powered off, operating modes. The grid and photovoltaic system automatically...
  • Page 7: Specifications Parameters

    �.� Specifications Parameters Rated AC input current ��.�A ��.�A ��.�A ~�(�.�leading - �.�lagging) H����H-EU H�����H-EU H�����H-EU Power factor Model <�% THDI @Full load PV Input Specification ��A �����W �����W �����W AC inrush current Max. PV input power Max. output ����V ��A Max.
  • Page 8: Installation Descriptions

    � . Installation Descriptions Ⅱ(DC)/Ⅲ(AC) surge protection General Information �.� Examples of Incorrect Installation Transformerless Topology Ensure the installation follows these guidelines to avoid incorrect setups: · The off-grid port cannot be connected in parallel. If necessary, please contact after-sales support. ���*���*���mm Dimensions(W/H/D) ·...
  • Page 9: System Wiring Diagram

    �.� System Wiring Diagram Schematic representation of the grid system with no special requirements for electrical connections. The energy storage inverter wiring system Note: The off-grid ground wire and ground bar must be properly connected for proper operation. Otherwise, the off-grid function may malfunction during a grid failure. �...
  • Page 10 System Wiring Diagram The energy storage inverter wiring system According to Australian safety regulations, the neutral wires of the grid-connected side and the off-grid s Note: ide must be connected together. Otherwise, the off-grid function will not operate normally. Example of connecting N wires with PE wires in the distribution box Applicable in countries such as Australia, New Zealand, South Africa, etc.
  • Page 11: Packing List

    Model � � � � � Schematic representation of grid systems with no special requirements for electrical connections ��A, ≥���V ��A/���V ��A/���V, �L/N/PE ���mA RCD (Type A), H����H-EU main breaker Note: the off-grid ground wire and ground bar must be properly connected to work properly. DC breaker AC breaker ���mA RCD (Type A)
  • Page 12: Installation

    �.� Installation �.�.� Installation Tools Meter Recommended installation tools include but are not limited to the following tools. If necessary, additional RJ�� Waterproof PV Disassembly Communication Plug x� auxiliary tools can be used on site. Tool x� Cable x� Optional accessories adapted for the B����M-HA battery series Allen Wrench Protection Goggle Anti-noise Earplugs...
  • Page 13: Mounting The Inverter

    Rule �. Leave enough space around the inverter according to the below figure for natural heat dissipation. Rule �. The inverter with IP �� can be installed both indoors and outdoors. ���mm It is recommended to prevent the inverter from being exposed to direct sunlight, snow, Warning!...
  • Page 14: Electrical Connections

    �.�.� PV Wiring Connection � Use the standard screws to secure both sides of the wall-mounted bracket. Before connecting PV panels/strings to the inverter, ensure all the following requirements are met: � N · m �. The total short-circuit current of a PV string must not exceed the inverter's max DC current. �.
  • Page 15: Connect The Battery Cable

    �.�.� Connect the Battery Cable � Be aware of electrical shock hazards or chemical hazards. If the battery does not have a built-in DC circuit breaker, please ensure that an external DC circuit breaker (≥��A) is connected. Note: You will hear a "click"...
  • Page 16: Battery Protection

    � � Notice: If the battery port is not used, install a dust cap to prevent rain and dust from entering the inverter. · Thread the cable through the cable gland and insert the crimp contact into the insulator. A clicking sound indicates that it has snapped into place.
  • Page 17: On-Grid & Off-Grid Connection

    �.�.� On-grid & Off-grid Connection �.�.�.� Off-grid Connection When the inverter is connected to the grid, add an external AC circuit breaker to isolate the grid from The inverter supports both on-grid and off-grid functions. It will transmit power through the on-grid port the inverter if necessary.
  • Page 18: On-Grid Connection

    � Align the square opening on the AC load connector with the foot buckle on the inverter off-grid port Notice: and insert. If the off-grid port is not used, please install a dust plug for the AC load connector to prevent rain and The foot buckle entering the grid terminal and exposing the upper opening followed by a "click"...
  • Page 19 � Insert the cable conductor core into the terminal and crimp. Ensure that the cable sheath is not Notice: locked into the connector. · All electrical connections must be in accordance with local and national standards. · Only with the permission of the local utility grid company, the inverter can be connected to the utility Thread an appropriate length of AC cable through the waterproof terminal.
  • Page 20: Connect The Smart Meter

    Declarations for The Back-up Function �.�.� Connecting the Smart Meter The backup output of the hybrid inverters has overload capability. The inverter also has self-protection derating at high ambient temperatures. Ensure the AC cable is fully isolated from the AC power source before connecting the smart meter. �.
  • Page 21 Smart meter wiring with CT Item User interface Description Item User interface Description combined power A phase voltage=���.�V � �� factor PFt=�.��� Voltage signal (only for meters connected � � � �� �� �� �� �� �� �� B phase A phase power via current transformer): �...
  • Page 22 When using a smart meter, please follow the steps below to set the parameters. Smart meter wiring Instrument Voltage signal (only for meters connected power on via current transformer): � click � click � click � click � click � �...
  • Page 23: Connection Ground Fault Alarm

    Note: When the smart meter is used with this product, the current ratio is set to ��, and the voltage ratio Item Color CAN(BMS) � � � � is set to �.�. � WAKE_UP � � � � range and white �...
  • Page 24: Connect Wifi Module

    �.�.� Logger Status �.� Connect WIFI Module Check the indicator lights The WIFI communication function is only applicable to the WIFI module, please refer to the following figure to install the WiFi module Light Meaning Status description (All indicator lights are single green lights.) �.
  • Page 25: The Connection Mode Of Com

    Fault Description Cause Solution PIN� RS���-A �. The connection between the logger and the inverter is �. Check whether the connection with the inverter is good. Communicate with loose or abnormal. External communication port Remove the logger and reinstall it. state state inverter is abnormally.
  • Page 26: Commissioning

    �. Commissioning DRM ("AU"/"NZ") ·When the inverter is applied in Australia, the DRMS terminal needs to be connected. �.� Inspection before Commissioning The following table lists the DRMs supported by the inverter. �.�.� Connection Check Mode Requirement PV Side �. Before checking, ensure that the DC switch and the breaker of the combiner box on the AC side are discon- DRM�...
  • Page 27: Battery Side

    Photovoltaic Module Access Requirements �.�.� Electrical Inspection Observe the lable of the three-phase inverter. When wiring, electrical inspection should be carried out to �. Modules with consistent photovoltaic characteristics should be used for connection under the same ensure that the AC and DC parameters are within the range of the label to avoid damage to the inverter due to MPPT.
  • Page 28: Powering On The System

    Checking Method for String Grounding ·In the picture on the right, the multimeter shows that the current battery voltage is ���V. The red test lead is connected to the positive pole, and the black test lead is connected to the negative pole, indicating correct polarity.
  • Page 29: Shutting Down The System

    If not, repeat step �. (When the running indicator is on and the power switch is not released immediately, the battery may fail to power on.) With the WIFI module installed, view corresponding information through Hinen APP or Hinen WEB. �.� Shutting Down the System �...
  • Page 30: Downloading And Login

    · The mobile phone supports WLAN or Bluetooth. XXXXXXXXX Method �: Search Hinen Solar in Google Play (Android) or App Store (iOS) to download and install the app. Method �: Scan the QR code below to download and install the app.
  • Page 31: Quick Installation

    After login, click "Quick Installation" on the home page. Follow the instructions to reset the logger and tap " Next " to connect the logger. Scan the following QR code to download and install the Solarman App according to the prompt information. https://www.hinen.com/pages/smart-energy-management-system �� ��...
  • Page 32: System Setup

    �.�.� System Setup Methods of connecting the logger are as follows. On completion of connecting the logger, you can enter home page of " Quick Installation " . Tap " System Setting " and fill in the relevant information to complete the system setup. Method 2:...
  • Page 33 When to Choose AC Couple: · The system already has a third-party PV inverter installed, and you need to connect it to Hinen ' s inverter. Regional Standards: There are four main regions including A, B, C and NZ, which stands for New Zealand region.
  • Page 34: Adding Installation Information

    �.�.� Adding Installation Information Grid Name: Select the correct grid operator. You can choose None, South Australia Power Network, Jemena, City Power, Powercor Australia, or United Energy Services. National Meter Identifier: Please fill in the national meter identifier. Tap " Installation Info " to enter the " Installation Info " page. Please enter correct retailer name, actual end-user name and email address, plant address, actual end-user phone number, and photos.
  • Page 35: Configuring Network

    �.�.� Configuring Network �.�.� Version Update Tap " Networking " and fill in the WiFi name and password. Once successfully networked, tap " Finish " . Tap " Version update Info " to check if the current version is the latest. If not, tap " Update " . �.�.�...
  • Page 36: Controlling The Inverter Remotely

    �.� Controlling the Inverter Remotely �.�.� Overview of Device Tap " Overview " to control the operation of the inverter and check the real-time running status of the Tap " Device " to check all the devices you have installed, including online devices, off-line devices, added inverter, including the data of battery, PV, grid, and load.
  • Page 37: Viewing Alarm Information

    �.�.� Viewing Alarm Information Tap " Alerts " to check the alarm code and error code. Tap " Date " to check the graph of the day. You can check the graph data by filteringmonth, year, and total. Tap the icon to check the graph data on landscape.
  • Page 38: Viewing Other Information

    �.�.� Viewing other information �.�.� Work Mode Setup Tap " Others " to check the user information, basic information, battery information, off-grid information, Tap the icon to enter " Control Inverter " page to configure the work mode and cut-off SOC. Please refer and more.
  • Page 39 ・Users can set 3 time periods via the Hinen force charging/discharging power, and cut-off SOC as needed. Tap the App to enable forced charging or discharg- ing.
  • Page 40: Advanced Settings

    �.� Advanced Settings Remote control: Tap " Device " and select the device you want to check to enter device details page. Then tap the icon to enter " Control Inverter " page, and tap the icon to enter the password to enter " Advanced Setting "...
  • Page 41: Basic Settings

    �.�.� Basic Settings · CT/Meter Mode: You can select " CT " , " Meter " , or " without CT " based on the site installation. On " Basic " page, you can configure the active power percent, PV output power percent, AC charging current, installing mode, charging power percent, discharging power percent, and enable or disable fast charge and discharge or bypass mode according to the actual situation.
  • Page 42 · Installing Mode: You can select AC Couple, DC Couple, or hybrid mode depending on the actual · Fast Charge and Discharge: If fast charge and discharge is enabled, the fast charge/discharge time and situation. For specific configuration, please refer to step � in Chapter �. power can be configured.
  • Page 43: Battery Setup

    Please refer to the battery protocol code in the following table and select the correct one. Battery Protocol Code Three-phase Inverter Single-phase Inverter GOODWE high pressure PYLON low pressure SHOTO_HV HINEN low pressure PYLON high pressure GROWATT low pressure HINEN high pressure Growcol_LV 4-20 Battery 4~20...
  • Page 44: Off-Grid Setup

    If you select lead acid battery, the following parameters can be configured. Off-grid mode: The off-grid mode is enabled by default. When blackout occurs or the inverter cannot be connected to the grid, the EPS port will power the load immediately. CC Charging Current: refers to the maximum charging current.
  • Page 45: Safety Setup

    �.�.� Safety Setup The local safety command includes " Regional standards " , " Wide range of users " , and " Grid company safety regulations " . The default setting is " Regional standards " . " Wide range of users " applies to African areas. Please configure in compliance with local laws and regulations.
  • Page 46: Protection Parameter Setup

    �.�.�.� Protection Parameter Setup �.�.�.� On-grid Limits Setup Tap " Protection Parameter Settings " on " Safety " page to enter parameter setting. The safety regulations The inverter will detect the voltage and frequency of the grid before connecting to the grid. When the grid vary in different countries, so please set the voltage and frequency protection parameters in compliance voltage and frequency are within the normal range, the inverter can be connected to the grid.
  • Page 47 �� seconds. Hinen inverters are equipped with a hardware anti-backflow function. If enabled, the inverter will disconnect from the grid within � seconds if the output power exceeds the hardware limit.
  • Page 48 �.�.�.� PU Settings The PU settings have been pre-configured according to the safety standards of different countries. Please do not modify them without proper authorization. Active power control with an active power standard curve P=F(v) is shown in the figure below. VL Stop =0.9 V VL Start...
  • Page 49 �.�.�.� PF Settings Mode Comment The power factor is applicable in certain countries. Please follow the local grid requirements. Free Run PF Mode The PF is fixed at +1.000. Fixed PF Set Mode Power factor Q(P) Mode QP_p1 Rate User Set Line PF Mode ConstQ Lead PF Mode Q_Percentage ConstQ Lag PF Mode...
  • Page 50 Q(p) Mode: The power factor of the inverter varies with the change in the inverter ' s output power. �.�.�.� Other Settings Enter the "Other Settings" page to enable or disable the following functions based on actual conditions. Reactive power control, reactive power standard curve cos φ = f(P) φ...
  • Page 51 �.� Repair and Replacement �.� Personal Information Tap " Profile " to check personal information and submit feedback. Tap " Settings " to delete account, select language, view the App version and log out. Tap " Repair or Replace " to enter the corresponding page. Please select " Inverter Repair " or " Inverter Replacement "...
  • Page 52 �.� Error Codes Tap the avatar to configure your personal information or change the password. �.�.� Fault Reference Code Main Error Code Inverter State Fault Description Suggestion �. After shutdown, check the temperature. When it returns to normal, restart the inverter.
  • Page 53 �.�.� Warning reference code Main Error Code Inverter State Fault Description Suggestion �. After shutdown, check whether the grid Main Warning Code Inverter State Warning Description Suggestion phase is abnormal and restart the inverter. Error ��� Error/Off Phase difference too large �.
  • Page 54 Main Warning Code Inverter State Warning Description Suggestion Main Warning Code Inverter State Warning Description Suggestion �. After shutdown, check whether the tempera- Lead-acid battery �. Check the PV input terminals and switches. ture sampling module is connected properly. Warning ���� Warning/On Warning ����...
  • Page 55: Operational Problems

    Check before start-up and AC power-on Q & A Battery Settings, BMS Communication and Security Country: About the APP Operation and Monitoring After connecting the data logger, please check the parameters in the APP to make sure the selected battery type is the same as the one you installed, and the safety country is selected correctly.
  • Page 56: Other Problems

    About Smart Meter Functions About battery operation �. How to enable the output anti-reverse current function? �. Why does the battery not discharge when the grid is not available, but it can discharge normally For the inverter system, this function can be realized in the following ways: when the grid is available? (�) Make sure the smart meter connection and communication are good.
  • Page 57 �. Others �.� Fault Details When a fault occurs, the following error information can be viewed through the APP. Error message Reason Explanation Solution �. Use a multimeter to check whether there is voltage on the AC side, and ensure that the power grid is available. Grid power is unavailable The inverter does not detect Utility loss...
  • Page 58 Environmental Class Definition �.� Hazard Avoidance Quick Checklist � . Do not install the inverter near flammable, explosive or strong electromagnetic equipment. Environmental Relative humidity External temperature Apply to conditions �. T he inverter is heavy, be careful when taking it out of the bag. �.B e fore connecting the battery to the inverter, ensure that the battery circuit breaker is disconnected, and the Outdoor -��~��...
  • Page 59 �.�.� Daily Maintenance �.Before performing maintenance, use a multimeter and other instruments to measure the voltage between the metal parts that need to be touched or may be touched and the grounding copper bar to avoid electric shock. �.During maintenance, pay attention to the warning labels on the inverter to prevent personal injury caused by high voltage.