7.0 A3 OPERATION
Vacuum Equipment and preparation
1. 3 metre safety exclusion zone barriers.
2. Dry powder fire extinguisher.
3. A3 Certified leak detector. (Gas Mate or Profind + )
4. CareAir EX N rated fan with 5 metre power lead.
5. A personal A3 Gas monitor.
6. JAVAC Or JAVAC EDGE A2L (A3) Rated Vacuum pump.
Before the Vacuum pump is operated use an A3/ATEX Rated JAVAC Leak detector
(Gas Mate or Profind + ) around the pipework and system to be evacuated to test for any
Hydrocarbon refrigerants present.
Using barriers create a 3m exclusion zone.
A Personal A3 Gas monitor should be warn at all times.
If Hydrocarbons are detected do not operate the vacuum pump.
If the area is completely clear of Hydrocarbons or any flammable gasses please proceed with
the following Evacuation process.
It is essential that Oxygen free nitrogen is purged through the Pipework and exhausted
to outdoor area before the vacuum pump is connected clearing the pipework of any potential
Flammable gasses.
It is essential that throughout the full evacuation process the CareAir EX N Fan is within the
3m Exclusion Zone and turned on to circulate fresh air and disperse any potential flammable
gases in the atmosphere.
Connect the Vacuum pump to the System via a 1/4 or 3/8th Suitable Vacuum hose and step
outside of the 3m exclusion Zone.
Locate the vacuum pump inside the 3 metre safety zone.
Switch the vacuum pump ON at the pump.
After evacuation and prior to re-charging the system with HFO, electrically isolate the
vacuum pump
Remove the pump from the 3 metre safety zone.
* The JAVAC Range of A2L (A3) Vacuum pumps must only be used by
F-Gas qualified Engineers.