Carrier 40TSF0131UP Installation Manual
Carrier 40TSF0131UP Installation Manual

Carrier 40TSF0131UP Installation Manual

4-way cassette type
Hide thumbs Also See for 40TSF0131UP:

Advertisement

Available languages

Available languages

Quick Links

AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Indoor Unit
Model name:
4-way Cassette type
40TSF0131UP
40TSF0181UP
40TSF0241UP
40TSF0301UP
40TSF0361UP
40TSF0401UP
40TSF0481UP
40TBU0481UP
For commercial use
สํ า หรั บ ใช ง านเชิ ง พาณิ ช ย
1 115 350 111
English
Installation Manual
1
คู  ม ื อ การติ ด ตั ้ ง
ภาษาไทย
22

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 40TSF0131UP and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 40TSF0131UP

  • Page 1 1 115 350 111 AIR CONDITIONER (SPLIT TYPE) Installation Manual Indoor Unit For commercial use สํ า หรั บ ใช ง านเชิ ง พาณิ ช ย Model name: 4-way Cassette type 40TSF0131UP 40TSF0181UP 40TSF0241UP 40TSF0301UP 40TSF0361UP 40TSF0401UP 40TSF0481UP 40TBU0481UP English Installation Manual คู...
  • Page 2: Table Of Contents

    Drain piping work ............. 8 work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus Refrigerant piping and evacuating .
  • Page 3: Warning Indications On The Air Conditioner Unit

    Warning indications on the air conditioner unit Defi nition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special Warning indication Description work detailed in the following table.
  • Page 4: Precautions For Safety

    – 3 – Precautions for safety Installation • When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be used. The manufacturer shall not assume any liability for the damage caused by not observing the description of this •...
  • Page 5: New Refrigerant Air Conditioner Installation

    Accessory parts Test run • Before operating the air conditioner after having completed the work, check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON Part name Q’ty Shape...
  • Page 6: Selection Of Installation Place

    – 5 – Selection of installation place Installation space (Unit: mm) Secure the specified space in the figure for installation and servicing. WARNING Model A mm Install the air conditioner at enough strong place to withstand the weight of the unit. 0131UP, 0181UP, 0241UP, 0301UP Type 271 or more If the strength is not enough, the unit may fall down resulting in injury.
  • Page 7: Ceiling Height

    Installation Ceiling height REQUIREMENT Possible installed ceiling height 0131UP, 0181UP, 0241UP, 0301UP UP to 3.8 m Strictly comply with the following rules to prevent damage of the indoor units and human injury. Do not put a heavy article on the indoor unit. (Even units are packaged) 0361UP, 0401UP, 0481UP UP to 4.6 m Carry in the indoor unit as it is packaged if possible.
  • Page 8 – 7 – Opening a ceiling and When hanging a ceiling, open the ceiling along the Existing concrete slab outside dimensions of the installation pattern. installation of hanging bolts Use a hole-in anchors, hole-in plugs, or a hole-in bolts. Indoor unit Consider the piping / wiring after the unit is hung when determining the location of the indoor unit installation and orientation.
  • Page 9: Drain Piping Work

    Drain piping work Wireless remote controller REQUIREMENT Before installation of the indoor unit, be sure to The standard distance for signal reception is For length of the traversing drain pipe, restrict to remove the cushion for transportation between the CAUTION 20 m or less.
  • Page 10 – 9 – Connecting drain pipe Check the draining Perform heat insulating After the electric work has finished, pour water during COOL mode operation. If the electric work has not yet finished, pull out Connect a hard socket (Locally procured) to the hard In the test run, check that water drain is properly As shown in the figure, cover the flexible hose and the float switch connector (CN34: Red) from the...
  • Page 11: Refrigerant Piping And Evacuating

    Refrigerant piping and evacuating Tightening connection Air purge CAUTION Refrigerant piping Permissible piping length Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit. Do not apply excessive torque. Otherwise, the nut and height difference For details, follow to the Installation Manual attached may crack depending on the conditions.
  • Page 12: Electrical Connection

    – 11 – Electrical connection Heat insulation process Apply heat insulation for the pipes separately at liquid side and gas side. WARNING To use the attached heat insulation pipe, apply the heat insulation to the pipe connecting section of the Use the specified wires for wiring connect the terminals.
  • Page 13: Wire Connection

    Wire connection System interconnection terminal block Side D (Space: 8.5 mm) 1 2 3 REQUIREMENT Side C (Space: 4 mm) Be sure to connect the wires matching the terminal numbers. Incorrect connection causes an error. Be sure to pass the wires through the bushing of wiring connection port of the indoor unit. Keep a margin (Approx.
  • Page 14: Applicable Controls

    – 13 – Applicable controls Wired remote Controller Wiring (When a wired remote controller is installed) A wired remote controller is required for applicable controls. Purchase a wired remote controller (sold separately). For details of wiring / installation of the remote controller, refer to the installation manual enclosed to in the remote controller.
  • Page 15: Filter Sign Setting

    Installing indoor unit on high Filter sign setting Procedure Push button to check the setting. Each time you push button, indoor unit ceiling The display state changes from flashing to numbers in the control group change cyclically. Select According to the installation condition, the lighting time lighting, and the setting is fixed.
  • Page 16: Louver Lock (No Swing)

    – 15 – Louver lock (No swing) Cancelling louver lock About “Dual swing” Indoor unit data “Dual” means that louvers 01 and 03 are directed CODE No. Data name and swing in one direction and louvers 02 and 04 are Set the wind direction to “0000”...
  • Page 17: Group Control

    Group control To recognize the position of the Procedure After confirmation, push button to return the mode corresponding indoor unit though the One wired remote controller can control maximum 8 to the usual mode. indoor unit No. is known indoor units as a group. When pushing button, the display disappears and Check the position during operation stop.
  • Page 18: Test Run

    – 17 – Test run Signal receiving unit Procedure Using button, select the operation mode, When TEMPORARY button is pushed for [COOL]. Before test run Procedure Do not run the air conditioner in a mode other than 10 seconds or more, “Pi!” sound is heard Cooling test run [COOL].
  • Page 19: Maintenance

    Maintenance Close the air intake grille. Mount the discharge louver. Close the air intake grille, slide the knob First push in one side of the louver, and The fan is running for self cleaning maintenance Cleaning air filters outward, and fix the air intake grille securely. then insert the other side sagging the centre after running the cooling or dry mode.
  • Page 20: Troubleshooting

    – 19 – Troubleshooting NOTE Annual maintenance Confirmation and check Confirmation of error log For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner. When an error occurred in the air conditioner, the When an error occurred on the air conditioner, When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
  • Page 21 Check codes and parts to be checked Wired Wireless remote controller remote Sensor block display of controller receiving unit display Wired Judging Main defective parts Parts to be checked / error description conditioner Wireless remote controller remote device Operation Timer Ready Sensor block display of status...
  • Page 22 – 21 – Wired Wireless remote controller remote Sensor block display of controller receiving unit display Judging Main defective parts Parts to be checked / error description conditioner device Operation Timer Ready status Indication Flashing There may be gas leakage from the pipe or connecting Gas leakage detected Outdoor Entire stop...
  • Page 23 คํ า แนะนํ า เบื ้ อ งต น โปรดอ า นคํ า แนะนํ า ต า งๆ ที ่ ม ี ข  อ มู ล สํ า คั ญ ซึ ่ ง ตรงตาม “Machinery Directive” (Directive 2006/42/EC) อย า งละเอี ย ดถี ่ ถ  ว น และโปรดปฏิ...
  • Page 24 – 23 – คํ า อธิ บ ายอุ ป กรณ ป  อ งกั น สั ญ ลั ก ษณ ค ํ า เตื อ นของตั ว เครื ่ อ งปรั บ อากาศ สวมถุ ง มื อ ป อ งกั น และชุ ด ที ่ ป ลอดภั ย สํ า หรั บ การทํ า งาน เม อเคล อนย า ย ติ ด ตั ้ ง บํ า รุ ง รั ก ษา ซ อ มแซม หรื อ ถอดชิ ้ น ส ว น เคร...
  • Page 25: ข อ ควรระวั ง เพื ่ อ ความปลอดภั ย

    ข อ ควรระวั ง เพื ่ อ ความปลอดภั ย การติ ด ตั ้ ง หากต อ งการติ ด ตั ้ ง ตั ว เครื ่ อ งภายในเป น แบบแขวน ควรใช โ บลต (M10 หรื อ W3/8) และน็ อ ต (M10 หรื อ W3/8) ในการติ ด ตั ้ ง ผู...
  • Page 26 – 25 – ชิ ้ น ส ว นอุ ป กรณ เ สริ ม การทดสอบการทํ า งาน ก อ นเป ด ใช ง านเครื ่ อ งปรั บ อากาศภายหลั ง การติ ด ตั ้ ง ควรตรวจสอบให แ น ใ จว า ฝาครอบกล อ งควบคุ ม ไฟของตั ว เครื ่ อ งภายใน ชื...
  • Page 27 การเลื อ กสถานที ่ ต ิ ด ตั ้ ง พื ้ น ที ่ ต ิ ด ตั ้ ง (หน ว ย : มม.) เตรี ย มพื ้ น ที ่ ส ํ า หรั บ การติ ด ตั ้ ง และการซ อ มบํ า รุ ง ตามที ่ ก ํ า หนดไว ใ นภาพ คํ...
  • Page 28 – 27 – ความสู ง ของเพดาน การติ ด ตั ้ ง ข อ กํ า หนด ความสู ง ของเพดานที ่ เ หมาะกั บ การติ ด ตั ้ ง 0131UP, 0181UP, 0241UP, 0301UP สู ง สุ ด 3.8 ม. โปรดปฏิ บ ั ต ิ ต ามกฎต อ ไปนี ้ อ ย า งเคร ง ครั ด เพื ่ อ ป อ งกั น ความเสี ย หายที ่ จ ะเกิ ด กั บ ตั ว เครื ่ อ งภายในและเพื ่ อ ป อ งกั น ผู  ใ ช จ ากการ ได...
  • Page 29 การเป ด ช อ งเพดานและการติ ด ตั ้ ง ขณะแขวนตั ว เครื ่ อ งบนเพดาน ให เ ป ด ฝ า เพดานตามขนาด แผ น คอนกรี ต ที ่ ม ี อ ยู  เ ดิ ม รอบนอกของแผ น ช ว ยการติ ด ตั ้ ง สลั...
  • Page 30 – 29 – งานติ ด ตั ้ ง ท อ ระบาย ข อ กํ า หนด รี โ มทคอนโทรลไร ส าย ก อ นติ ด ตั ้ ง ตั ว เครื ่ อ งภายใน ควรตรวจสอบให แ น ใ จว า ได ระยะห...
  • Page 31 การต อ ท อ ระบายนํ ้ า การตรวจสอบการระบายนํ ้ า หลั ง จากทํ า งานที ่ เ กี ่ ย วกั บ ไฟฟ า เสร็ จ แล ว ให เ ทนํ ้ า ระหว า งที ่ การใช ฉ นวนกั น ความร อ น เครื...
  • Page 32 – 31 – ท อ ส ง สารทํ า ความเย็ น และการไล อ ากาศ การขั น แน น การไล อ ากาศออก ข อ ควรระวั ง ท อ ส ง สารทํ า ความเย็ น ความยาวของท อ ที ่ ไ ด ร ั บ อนุ ญ าตและ ใช...
  • Page 33: การต อ สายไฟ

    การต อ สายไฟ ขั ้ น ตอนการใช ฉ นวนกั น ความร อ น ใช ท  อ ฉนวนกั น ความร อ นแยกกั น ระหว า งด า นของเหลวและ คํ า เตื อ น ด า นก า ซ ควรใช ท  อ ฉนวนกั น ความร อ นที ่ ใ ห ม า โดยหุ  ม ฉนวนกั น ใช...
  • Page 34 – 33 – การต อ สายไฟ บล็ อ คขั ้ ว ต อ ที ่ เ ชื ่ อ มระบบ เข า ด ว ยกั น ด า น D (เว น ที ่ ว  า ง 8.5 มม.) 1 2 3 ข...
  • Page 35 การควบคุ ม การใช ง าน การเดิ น สายไฟรี โ มทคอนโทรลแบบใช ส าย (เมื ่ อ มี ก ารติ ด ตั ้ ง รี โ มทคอนโทรล แบบใช ส าย) ควรใช ร ี โ มทคอนโทรลแบบใช ส ายเพื ่ อ การควบคุ ม ที ่ เ หมาะสม รี...
  • Page 36 – 35 – ขั ้ น ตอนที ่ การติ ด ตั ้ ง ตั ว เครื ่ อ งภายในบนเพดาน การตั ้ ง ค า สั ญ ญาณเตื อ นทํ า ความ กดปุ  ม เพื ่ อ ทํ า การตั ้ ง ค า ให เ สร็ จ สมบู ร ณ สภาพ ทุ...
  • Page 37 เกี ่ ย วกั บ “การส า ยสองทิ ศ ทาง” การล็ อ กบานเกล็ ด (ไม ส  า ย) การยกเลิ ก การล็ อ กบานเกล็ ด ข อ มู ล ตั ว เครื ่ อ งภายใน “สองทิ ศ ทาง” หมายความว า บานเกล็ ด 01 และ 03 จะป ด CODE No.
  • Page 38 – 37 – การควบคุ ม เป น กลุ  ม หากต อ งการจดจํ า ตํ า แหน ง ของตั ว เครื ่ อ งภายใน ขั ้ น ตอนที ่ หลั ง ยื น ยั น แล ว ให ก ดปุ  ม เพื...
  • Page 39 การทดสอบการทํ า งาน ตั ว รั บ สั ญ ญาณ ขั ้ น ตอนที ่ กดปุ  ม แล ว เลื อ กโหมดการทํ า งาน [COOL] ก อ นทํ า การทดสอบการทํ า งาน ขั ้ น ตอนที ่ เมื ่ อ กดปุ  ม TEMPORARY ค า งไว 10 วิ น าที ขึ ้ น ไป อย...
  • Page 40: การบํ า รุ ง รั ก ษา

    – 39 – การบํ า รุ ง รั ก ษา ป ด ตะแกรงช อ งลมเข า ยึ ด บานเกล็ ด ช อ งลมออก ป ด ตะแกรงช อ งลมเข า เลื ่ อ นปุ  ม ออกด า นนอก แล ว ยึ ด เริ...
  • Page 41 การแก ไ ขป ญ หา ข อ สั ง เกต การบํ า รุ ง รั ก ษาประจํ า ป การยื น ยั น และตรวจสอบ การยื น ยั น รายงานข อ ผิ ด พลาด เพื ่ อ ป อ งกั น ความสู ญ เสี ย จากสภาพแวดล อ ม ขอแนะนํ า ให ท  า นทํ า ความสะอาด และบํ า รุ ง รั ก ษาตั ว เครื ่ อ งภายในและตั ว เครื ่ อ ง ภายนอกของเครื...
  • Page 42 – 41 – รหั ส การตรวจสอบและชิ ้ น ส ว นที ่ ต  อ งตรวจสอบ หน า จอ รี โ มทคอนโทรลไร ส าย ของรี โ มท หน า จอบล็ อ คเซ็ น เซอร สถานะ คอนโทรล ของตั ว รั บ สั ญ ญาณ หน...
  • Page 43 หน า จอ รี โ มทคอนโทรลไร ส าย หน า จอ รี โ มทคอนโทรลไร ส าย ของรี โ มท หน า จอบล็ อ คเซ็ น เซอร ของรี โ มท หน า จอบล็ อ คเซ็ น เซอร สถานะ สถานะ คอนโทรล ของตั ว รั บ สั ญ ญาณ คอนโทรล...
  • Page 44 1 115 350 111...