SBZ22x Mechatronic flow meter 1 Preliminary note You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at documentation.ifm.com. 1.1 Symbols used Requirement Instructions Reaction, result [...] Designation of keys, buttons or indications...
Mechatronic flow meter SBZ22x 2 Safety instructions • The unit described is a subcomponent for integration into a system. – The system architect is responsible for the safety of the system. – The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system.
SBZ22x Mechatronic flow meter 3 Intended use The unit monitors liquid media. The unit detects the process categories volume flow (volumetric flow quantity/time) and medium temperature. ATTENTION Frost formation of the medium. w The sensor may be damaged. u Ensure that the medium in the sensor does not freeze during operation and transport. Application: •...
Mechatronic flow meter SBZ22x 4 Function • The unit detects the flow rate according to the principle of differential pressure by means of a permanent magnet and a measuring cell. • As additional process value the unit detects the medium temperature. •...
SBZ22x Mechatronic flow meter Process value Time Upper limit value Lower limit value Hysteresis Window area Fno: Window function NO (normally open) Fnc: Window function NC (normally closed) Fig. 2: Window function When set to the window function the upper limit value [FH] and the lower limit value [FL] are defined.
Mechatronic flow meter SBZ22x 4.4.2 Temperature monitoring [mA] FOU=On 21,5 FOU=OFF [°C] [°F] Fig. 4: Characteristics of the analogue output according to the standard IEC 6094752, temperature Analogue signal MAW: Initial value of the measuring range Temperature MEW: Final value of the measuring range Measuring range Above the display range Display range...
SBZ22x Mechatronic flow meter 4.5.1 Volumetric flow monitoring [% FrP1] FOU = ON 130 = FrP1 FOU = OFF 0 FEP1 MEW 120 130 [% MEW] Fig. 5: Output characteristic frequency output, flow rate Frequency signal MAW: Initial value of the measuring range Flow MEW: Final value of the measuring range...
IO-Link is a communication system for connecting intelligent sensors and actuators to automation systems. IO-Link is standardised in the IEC 61131-9 standard. General information on IO-Link at io-link.ifm Input Output Device Description (IODD) with all parameters, process data and detailed descriptions of the device at documentation.ifm.com...
SBZ22x Mechatronic flow meter 5 Mounting CAUTION During installation or in case of a fault (e.g. housing damage) media under high pressure or hot media can leak from the system. w Risk of injury caused by pressure or burns. u Ensure that the system is free of pressure during installation. u Ensure that no media can leak at the mounting location during installation.
Install sensor horizontally. u Adhere to the inclination angle to the horizontal axis: ± 90° Fig. 10: Alignment in case of medium containing dirt In clean medium, installation in vertical pipes is also possible. Information about available filters at www.ifm.com.
SBZ22x Mechatronic flow meter 6 Electrical connection [Für die Übersetzung exportiert] The unit must be connected by a qualified electrician. Observe the national and international regulations for the installation of electrical equipment. Voltage supply according to SELV, PELV. u Disconnect power. u Connect the unit as follows: OUT2 OUT1/ IO-Link...
Mechatronic flow meter SBZ22x 7 Operating and display elements Switching status LED for OUT1 Switching status LED for OUT2 Process value in the indicated unit of measurement * 4-digit alphanumeric display Keys for changing views and parameter setting Fig. 13: Operating and display elements * l/min, m /h, gpm, gph, °C, °F...
SBZ22x Mechatronic flow meter 8 Menu 8.1 Menu overview Use the operating keys to navigate from the process value display to the main menu and from there to the submenus. Process value display Main menu Extended functions [EF] Basic settings [CFG] Memory [MEM] Display settings [DIS] Fig. 14: Menu overview 8.2 Main menu and submenus...
Page 17
Mechatronic flow meter SBZ22x Main menu: Process value display FSP1 FEP1 FrP1 [CFG] [MEM] [DIS] Parameter Explanation Switch point for switching output OUTx with hysteresis function Reset point for switching output OUTx with hysteresis function Upper limit for switching signal OUTx with window function Lower limit for switching signal OUTx with window function FSP1 Frequency start point for OUT1 = Lower measured value from which a frequency signal is provid-...
Page 18
SBZ22x Mechatronic flow meter Configuration [CFG] menu: Hno│Hnc│Fno│Fnc│FRQ Main menu Hno│Hnc│Fno│Fnc│ I [EF] uni.F Lmin│m3h│GPm│GPH uni.T °C│°F PnP│nPn ---- ---- FOU1 On│OFF│OU FOU2 On│OFF│OU SEL1 FLOW│TEMP SEL2 FLOW│TEMP [CFG] Parameter Explanation Output function for hardware output OUTx uni.F Standard unit of measurement for flow uni.T Standard unit of measurement for temperature Output polarity for the switching outputs...
Page 19
Mechatronic flow meter SBZ22x Memory [MEM] and display [DIS] menus: Main menu [EF] Lo.T ---- Hi.T ---- [MEM] coLr rED│GrEn│r1ou│G1ou│r2ou│G2ou d1│d2│d3│rd1│rd2│rd3│OFF SELd FLOW│TEMP [DIS] Parameter Explanation Lo.T Minimum measured temperature value Hi.T Maximum temperature value measured colr Colour configuration of the display Update rate and orientation of the display SELd Standard process value of the display...
SBZ22x Mechatronic flow meter 9 Set-up After power on and expiry of the power-on delay time, the unit is in the normal operating mode. It carries out its measurement and evaluation functions and generates output signals according to the set parameters. During the power-on delay time the outputs are switched as programmed: •...
Mechatronic flow meter SBZ22x 10 Parameter setting Parameter setting can be carried out via the IO-Link interface or via the operating elements on the unit. Parameters can be set before installation or during operation. If you change parameters during operation, this will influence the function of the plant. u Ensure that there will be no malfunctions in your plant.
SBZ22x Mechatronic flow meter 10.2 Parameter setting via the unit keys CAUTION If the medium temperature is above 50 °C (122 °F), parts of the housing can increase in temperature to over 65 °C (149 °F). w Risk of burns u Do not touch the device with your hands. u Use another object (e.g.
Mechatronic flow meter SBZ22x 10.2.3 Setting the output functions The parameters for flow monitoring and temperature monitoring are set in the same way. The prerequisite is that the process value for OUTx has first been defined via [SELx]. 10.2.3.1 Limit monitoring OUTx / hysteresis function u Select the CFG menu.
SBZ22x Mechatronic flow meter • FLOW: The display shows the current process value for flow rate. • TEMP: The display shows the current process value for temperature. u Select [diS] and set the update rate and orientation of the display: •...
Mechatronic flow meter SBZ22x – OFF: The frequency signal goes to 0 Hz. – OU: The frequency signal still corresponds to the measured value. 10.2.4.7 Lock / unlock The unit can be locked electronically to prevent unintentional settings. Factory setting: not locked. Locking: u Make sure that the unit is in the normal operating mode.
SBZ22x Mechatronic flow meter 11 Operation 11.1 Process value display It is possible to switch between different process value indications during operation: u Press [▲] or [▼]. w The display changes between the standard indication with set standard unit of measurement and other views.
If several diagnostic events occur simultaneously, only the diagnostic message of the event with the highest priority is displayed. If the measured temperature value fails, the process value for flow rate is still available. Additional diagnostic functions are available via IO-Link Ò IO-Link interface description at documentation.ifm.com. 12.1 Error messages Display Problem/remedy Unit faulty / malfunction u Replace the unit.
SBZ22x Mechatronic flow meter 13 Maintenance, repair and disposal The operation of the unit is maintenance-free. Only the manufacturer is allowed to repair the unit. u After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations.
Need help?
Do you have a question about the SBZ22 Series and is the answer not in the manual?