Safety of Electronic Equipment within the Field of Audio/Video, Information Technology and Communication Technology. Lenovo assumes you are qualified in the servicing of equipment and trained in recognizing hazards energy levels in products. Access to the equipment is by the use of a tool, lock and key, or other means of security, and is controlled by the authority responsible for the location.
Page 7
Click Power ➙ Power Cables to see all line cords. • Make sure that the insulation is not frayed or worn. 3. Check for any obvious non-Lenovo alterations. Use good judgment as to the safety of any non-Lenovo alterations.
Page 8
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
See this topic for information about ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet. Figure 1. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet Features and specifications See this topic for features and specifications of ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet. Features Optional •...
Page 10
Maximal loaded shipping weight 2086 4599 Rear Door Heat eXchanger V2 (empty) One unit of extension Maximal empty rack cabinet weight Rear Door Heat eXchanger V2 (filled) Maximal deployed weight 1829 4032 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
See this topic for components of ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet. Parts listing See this topic to learn about parts of ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet. Figure 2. Parts listing Table 3. Heavy Duty Full Depth 42U Rack Cabinet components...
DWC RM100 in-rack CDU is installed. Attention: There is some residual water remaining in the CDU secondary circuit after Lenovo manufacturing integration, test, and draining. Before filling the CDU secondary circuit and rack for the first time, be sure to flush/rinse the entire secondary loop with clean, bacteria free water (distilled or deionized preferred).
Page 13
Figure 4. In-rack coolant distribution layout - front view Table 4. In-rack coolant distribution layout - front view Neptune DWC RM100 in-rack CDU Chapter 2 Rack cabinet components...
See this topic to learn about optional components that are supported by ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet. DWC 38 Port Rack Manifold See this topic to learn about parts of ThinkSystem Neptune® DWC 38 Port Rack Manifold. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 15
Figure 6. DWC 38 Port Rack Manifold Table 6. DWC 38 Port Rack Manifold components Manifold supply side Manifold return side Figure 7. In-row hose kit components (1.3m) Table 7. In-row hose kit components (1.3m) In-row hose supply side In-row hose return side Chapter 2 Rack cabinet components...
Table 10. 48U in-rack connection set components In-rack connection set supply side In-rack connection set return side 42U Advanced Rack Extension Kit See this topic to learn about parts of ThinkSystem 42U Advanced Rack Extension Kit. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 17
Figure 11. 42U Advanced Rack Extension Kit Table 11. Rack extension kit components One left extension panel Four M4 x 6 mm flat head socket cap screws (for extension top cover) One right extension panel Twelve M6 x 12 mm flat head socket cap screws (for support brackets) One extension top cover Fourteen M6 x 16 mm hex head flange screws...
“Install 42U Advanced Rack Extension Kit” on page 64 “Install 42U Advanced Rack Extension Kit with RDHX” on page 42U Standard Rack Extension Kit See this topic to learn about parts of ThinkSystem 42U Standard Rack Extension Kit. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 19
Figure 13. 42U Standard Rack Extension Kit Table 13. Rack extension kit components One left extension panel Eight support bracket screws One right extension panel Four extension top cover screws Fourteen extension panel screws One extension top cover Two support brackets Specifications Table 14.
Figure 14. Openings on an extension panel For installation procedure, see “Install 42U Standard Rack Extension Kit” on page 116. Cable management brackets See this topic to learn about the cable management brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 21
21U front cable management bracket Figure 15. 21U front cable management bracket components 21U front cable management bracket Six screws Rear cable management bracket Figure 16. Rear cable management bracket components Four screws Rear cable management bracket For installation procedure, see “Install a cable management bracket”...
For a complete list of supported power distribution units, go to • Power distribution units: https://lenovopress.com/servers/options/pdu • Console switches: https://lenovopress.com/servers/options/kvm Rear Door Heat eXchanger V2 See this topic to learn about parts of ThinkSystem Rear Door Heat eXchanger V2. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 23
Figure 17. ThinkSystem Rear Door Heat eXchanger V2 components Table 15. Rear Door Heat eXchanger components Rear Door Heat eXchanger assembly Hinge kit Air-purging valve Lift handles Air-purging tool Lift handle Door latch Serial number Latch plate Lift handle Drain valve Lower air baffle Return manifold coupling Upper air baffle...
Page 24
100% indicates that the heat exchanger not only removed all of the heat generated by the devices but further cooled the air so that the average air temperature leaving the rack is actually lower than that entering the rack. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 18. Typical performance of the heat exchanger, 30 kW heat load As described in “Water specifications for the secondary cooling loop” on page 165, a given water temperature may be used only if the system that is supplying the water is able to measure the room dew point and automatically adjust the water temperature accordingly.
Page 26
Two latch plate screws One latch plate • Three top hinge screws • Four bottom hinge screws For installation procedure, see “Install 42U Advanced Rack Extension Kit with RDHX” on page ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
• Space requirement: You will need minimum of 2885 mm (113.6 inch) on the rear side of the pallet to unpack the rack cabinet. • Tool requirement: You will need one sharp tool. • Forklift requirements: Note: Only the front side of the pallet is available for the forklift. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 29
Figure 22. Forklift – must be longer than 350 mm. – must be shorter than 700 mm. – must be between 1450 to 1650 mm. – Loading capacity must be larger than 3000 kg. Step 1. Cut the four straps with a sharp tool. Figure 23.
Page 30
Remove the top bars and side boxes. Note: One of the side cartons contains the ramps and is quite heavy. Lifting it requires two people. Figure 25. Removing the top bars and side boxes ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 31
Step 4. Release and remove the side frames. Figure 26. Removing the side frames Slightly lift and slide the six horizontal bars left to disengage their right ends from the slots on the right frame. Remove the right frame along with the three horizontal bars. Remove the left frame along with the nine horizontal bars.
Page 32
• Remove the two bolts with wrench for 10, 14, 5, 18, 26. • Remove the four M6 screws with wrench for 8, 9, 2 • Remove the six M10 screws with wrench for 8, 9, 2. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 33
Note: Keep at least one bolt for later use. Figure 28. Removing the rear shipping bracket Step 7. Rise each of the four leveling pads with wrench for 10, 14, 5, 18, 26 in turns until they no longer bear the weight of the rack cabinet. Figure 29.
Page 34
Secure the two metal plates to the ramp with the eight screws that come in a small bag attached to the plates. Figure 30. Securing the two plates to the ramp ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 35
Step 9. Secure the ramp to the pallet with one of the bolts that have been removed previously with wrench for 10, 14, 5, 18, 26. Figure 31. Securing the ramp to the pallet Step 10. Place the ramp next to the cabinet front door, and slowly slide the rack cabinet down from the pallet to the designated location.
Extend each of the four leveling pads in turns until they firmly contact the floor and support the rack cabinet. Make sure the cabinet is balanced by gently pushing the cabinet. If it tilts, adjust the length of the leveling pads until the cabinet is well balanced. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 37
Figure 33. Lowering the leveling pads Step 2. Remove the outrigger stabilizing bars, and remove them. Figure 34. Removing the outrigger stabilizing bars Remove the eight screws that secure the two bars to the rack cabinet. Place the two stabilizing bars on the ground, and remove the bars. Step 3.
Page 38
Figure 35. Removing the outriggers Step 4. Remove the front and rear doors of every rack cabinet that is to be part of the suite. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 39
Figure 36. Removing a door Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Step 5. (Optional) Remove all the sides covers that will contact each other in the suite. Chapter 3 Rack cabinet setup...
Page 40
Install four cage nuts on upper and lower locations on the side of adjacent cabinets as preparation for baying kit installation. Use the cage nuts that come with the baying kit. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 41
Figure 38. Installing the cage nuts “Install nuts on the mounting flanges” on page 147 for details. Step 8. Align the four screw holes of two attachment brackets with the holes in the adjacent cabinets, and secure each bracket to the racks with four screws. Note: Do not fully tighten the screws on the first bracket until securing the second bracket.
Page 42
Then, proceed with the actual extension kit installation procedure. See “Install 42U Standard Rack Extension Kit” on page 116. Figure 40. Removing screws to prepare for extension installation ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Otherwise, reinstall all the doors that have been removed. Figure 41. Installing a door Align the door with the hinges, and hold the door in place. Push the hinge pins down to the closed position so that the door is secured. Install the front stabilizer and recirculation prevention plate See this topic to learn how to enhance rack cabinet balance with the front stabilizer.
Page 44
Step 3. Secure the stabilizer to the floor with two screws. Figure 43. Securing the stabilizer to the floor Front Rear Figure 44. Rack cabinet with stabilizer installed ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Install DWC 38 Port Rack Manifold (in-rack system) Use this information to install the manifold in an in-rack direct water cooling system. CAUTION: The coolant might cause irritation to the skin and eyes. Avoid direct contact with the coolant. S002 CAUTION: The power-control button on the device and the power switch on the power supply do not turn off the electrical current supplied to the device.
Page 46
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 48
Make sure that the in-rack CDU and other devices are not powered on, and that all external cables are disconnected. Step 2. Install the server into the rack. Step 3. Install the manifold. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 49
Figure 45. Installing the manifold Hold the manifold with both hands, and mount it onto the rack cabinet. Align the spools with holes, and clutch the cabinet. Step 4. Repeat the last step to install the other manifold. Step 5. Install ball valves to CDU.
Page 50
Close the clamp. Lift the screw upright. Tighten the screw and make sure that it is secured. Step 6. Install the connection set to manifolds. Figure 47. Installing the connection set ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 51
17 mm wrench Connect the connection set to both manifolds. Wrap the interface around with the clamp. Close the clamp. Lift the screw upright. Tighten the screw and make sure that it is secured. Step 7. Install the connection set to ball valves. Figure 48.
Page 52
• For more operation and maintenance guidelines, see Lenovo Neptune DWC RM100 in-rack Coolant Distribution Unit (CDU) Operation & Maintenance Guide. • For service support, associated warranty and maintenance sizing, contact Lenovo Professional Services team at cdusupport@lenovo.com. Step 9. Install the quick connect plug to the manifolds.
Page 53
Remove the rubber quick connect plug covers from the ports on the manifold. Connect the plug to the manifold port. Step 10. Install the bleeder kit to the manifold supply side. Figure 52. Installing the bleeder kit to the supply side Remove the rubber quick connect plug covers from the ports on the manifold.
Page 54
Step 12. Slowly open the bleeder valve to conduct the air out of the hose. Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. Figure 54. Opening the bleeder valve on the supply side ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 55
Step 13. Install the bleeder kit to the manifold return side. Figure 55. Installing the bleeder kit on the return side Remove the rubber quick connect plug covers from the ports on the manifold. Plug the bleeder kit to the manifold. Step 14.
Page 56
Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 57. Opening the bleeder valve on the supply side Step 16. Once completed, pay close attention to the front display of CDU and maintain the system pressure at one bar. For more information about coolant temperature and system pressure requirements, see the water requirement section for your server.
Page 58
CAUTION: Sharp edges, corners, or joints nearby. S038 CAUTION: Eye protection should be worn for this procedure. S040 CAUTION: Protective gloves should be worn for this procedure. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 60
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 61
Attention: • Ensure proper handling procedures are followed when working with any chemically treated coolant used in the rack cooling system. Ensure that material safety data sheets (MSDS) and safety information are provided by the coolant chemical treatment supplier and that proper personal protective equipment (PPE) is available as recommended by the coolant chemical treatment supplier.
Page 62
Repeat the last step to install the other manifold. Step 4. Install the quick connect plug to the manifolds. Note: Depending on the model, your server might look different from the illustrations in this topic. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 63
Figure 59. Installing the quick connect plug Remove the rubber quick connect plug covers from the ports on the manifold. Connect the plug to the manifold port. Step 5. Install the hose kit to the manifold. Chapter 3 Rack cabinet setup...
Page 64
Wrap the interface around with the clamp. Close the clamp. Lift the screw upright. Tighten the screw and make sure that it is secured. Step 6. Install the bleeder kit to the manifold supply side. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 65
Figure 61. Installing the bleeder kit to the supply side Remove the rubber quick connect plug covers from the ports on the manifold. Plug the bleeder kit to the manifold. Step 7. To push the air out of the manifold supply side, connect facility supply to manifold return. Chapter 3 Rack cabinet setup...
Page 66
Slowly open the bleeder valve to conduct the air out of the hose. Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 67
Figure 63. Opening the bleeder valve on the supply side Step 9. Install the bleeder kit to the manifold return side. Chapter 3 Rack cabinet setup...
Page 68
Remove the rubber quick connect plug covers from the ports on the manifold. Plug the bleeder kit to the manifold. Step 10. To push the air out of the manifold return side, connect facility supply to manifold supply. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 69
Figure 65. Facility supply to manifold supply Press the button on the ball valve switch. Rotate both switches open and stop at around 1/4 of 90 degrees. Attention: • Open the ball valves on manifold supply side and facility supply side, while keep manifold return side closed.
Page 70
Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 71
Figure 67. Opening the bleeder valve on the supply side Step 13. Once completed, connect the supply and return of manifold and facility correspondingly. Fully open all connections on both supply and return sides. Figure 68. Opening ball valves Note: Manifold supply connects to facility Manifold return connects to...
– One Nut-driver with holding hex bit 10 mm to tighten the M6 screws ( in the next bullet point) – One 2.5 mm Hex bit socket to tighten the M4 screws ( in the next bullet point) ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 73
– One 3 mm Hex bit socket to tighten the M5 screws (PDU/manifold brackets, opening covers on the extension panels) – One 4 mm Hex bit socket to tighten the M6 screws ( in the next bullet point) • The extension kit comes with a miscellaneous bag, which contains the following components: Figure 70.
Page 74
Figure 71. Hex Allen wrenches Description Hex Allen wrench, 4 mm Hex Allen wrench, 3 mm Hex Allen wrench, 2.5 mm Procedure Step 1. Remove the door. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 75
Figure 72. Removing a door Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Step 2. Remove the two hinges and the two doorstops. Chapter 3 Rack cabinet setup...
Page 76
Remove the door latch. Figure 74. Removing the door latch Step 4. Install fourteen M6 cage nuts to the rack frame with cage nut insertion tool or a flat-blade screwdriver. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 77
Figure 75. Cage nut installation location With cage nut insertion tool Insert one edge of the cage nut into the target mounting flange hole, and hook the other edge with the insertion tool through the flange hole. Rotate and pull the tool to force the other nut edge into the flange hole, and thus secure the nut.
Page 78
Note: If baying kit has been installed previously, make sure to remove the two screws from top and bottom of the cabinet first. Then, secure the screws through the panel and the baying kit. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 79
Figure 78. Installing the extension panels Step 6. Align the extension top cover with the screw holes on the extension panels, and secure it with six screws. Chapter 3 Rack cabinet setup...
Page 80
Figure 79. Installing the extension top cover Step 7. Depending on the requirements, remove the filler(s) from the extension panels to route cables. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 81
Figure 80. Removing the fillers Loosen the screws that secure the filler to the extension panel. Remove the filler. Step 8. If there is a plan to install 0U PDU to the extension panel, complete the following steps. Depending on the requirements, select the corresponding installation procedures. •...
Page 82
– If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 83
Figure 82. Replacing the screws Remove the M6 hex head flange screw. Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with four screws. Chapter 3 Rack cabinet setup...
Page 84
2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. Choose the left or right slot for PDU installation based on the requirements. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 85
Figure 84. Installing the PDU Note: PDU can be rotated 180 degrees for installation with the input cable at the bottom. • L-shaped bracket (up to two PDUs, or one PDU and one manifold) Notes: – Below illustration shows the locations for installing the brackets. Chapter 3 Rack cabinet setup...
Page 86
– If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 87
Figure 86. Replacing the screw Remove the M6 hex head flange screw. Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with three screws. Choose the installation location for the bracket based on the orientation of the PDU. Chapter 3 Rack cabinet setup...
Page 88
Figure 87. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 89
Figure 88. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet 2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. Chapter 3 Rack cabinet setup...
Page 90
Figure 89. Installing the PDU with the PDU facing the front of the rack cabinet ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 91
Figure 90. Installing the PDU with PDU facing the rear of the rack cabinet Step 9. Depending on the requirements, select one of the following methods to ensure there is sufficient space for routing cables. • Slide the brush panel Chapter 3 Rack cabinet setup...
Page 92
Slide the baffle and brush panel toward the center of the top cover. Tighten the two screws to secure the baffle. • Remove the brush panel Figure 92. Removing the brush panel ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 93
Loosen the two screws to remove the brush panel from the top cover. • Remove the brush panel and baffle Figure 93. Removing the brush panel and baffle Loosen the two screws to remove the brush panel and baffle from the top cover. Step 10.
Page 94
Step 11. If the rack needs to be shipped, install the three support brackets. Note: Depending on the requirement, remove the support brackets upon arrival at the site. Figure 95. Installing the support brackets ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Step 12. Install the door back to the rack. Figure 96. Installing the door Align the door with the hinges, and hold the door in place. Push the hinge pins down to the closed position so that the door is secured. Install 42U Advanced Rack Extension Kit with RDHX See this topic to learn how to install 42U Advanced Rack Extension Kit and RDHX.
Page 96
– One 4 mm Hex bit socket to tighten the M6 screws ( in the next bullet point) • The extension kit comes with a miscellaneous bag, which contains the following components: ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 97
Figure 98. Parts Description Quantity Description Quantity M6 x 16 mm hex head flange Left extension panel screw Latch plate Top hinge for RDHX 1, 2, 3 Support bracket Cable strap module M6 x 16 mm flat head Grounding plate socket cap screw M4 x 6 mm flat head socket Bottom hinge for...
Page 98
Figure 99. Hex Allen wrenches Description Hex Allen wrench, 4 mm Hex Allen wrench, 3 mm Hex Allen wrench, 2.5 mm Procedure Step 1. Remove the door. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 99
Figure 100. Removing a door Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Step 2. Remove the two hinges and the two doorstops. Chapter 3 Rack cabinet setup...
Page 100
Remove the door latch. Figure 102. Removing the door latch Step 4. Install fourteen M6 cage nuts to the rack frame with cage nut insertion tool or a flat-blade screwdriver. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 101
Figure 103. Cage nut installation location With cage nut insertion tool Insert one edge of the cage nut into the target mounting flange hole, and hook the other edge with the insertion tool through the flange hole. Rotate and pull the tool to force the other nut edge into the flange hole, and thus secure the nut.
Page 102
• If baying kit has been installed previously, make sure to remove the two screws from top and bottom of the cabinet first. Then, secure the screws through the panel and the baying kit. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 103
Figure 107. Installing the extension panels Step 7. Align the extension top cover with the screw holes on the extension panels, and secure it with six screws. Chapter 3 Rack cabinet setup...
Page 104
Figure 108. Installing the extension top cover Step 8. Depending on the requirements, remove the filler(s) from the extension panels to route cables. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 105
Figure 109. Removing the fillers Loosen the screws that secure the filler to the extension panel. Remove the filler. Step 9. If there is a plan to install 0U PDU to the extension panel, complete the following steps. Depending on the requirements, select the corresponding installation procedures. •...
Page 106
– If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 107
Figure 111. Replacing the screws Remove the M6 hex head flange screw. Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with four screws. Chapter 3 Rack cabinet setup...
Page 108
2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. Choose the left or right slot for PDU installation based on the requirements. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 109
Figure 113. Installing the PDU Note: PDU can be rotated 180 degrees for installation with the input cable at the bottom. • L-shaped bracket (up to two PDUs, or one PDU and one manifold) Notes: – Below illustration shows the locations for installing the brackets. Chapter 3 Rack cabinet setup...
Page 110
– If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 111
Figure 115. Replacing the screw Remove the M6 hex head flange screw. Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with three screws. Choose the installation location for the bracket based on the orientation of the PDU. Chapter 3 Rack cabinet setup...
Page 112
Figure 116. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 113
Figure 117. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet 2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. Chapter 3 Rack cabinet setup...
Page 114
Figure 118. Installing the PDU with the PDU facing the front of the rack cabinet ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 115
Figure 119. Installing the PDU with PDU facing the rear of the rack cabinet Step 10. Depending on the requirements, select one of the following methods to ensure there is sufficient space for routing cables. • Slide the brush panel Chapter 3 Rack cabinet setup...
Page 116
Slide the baffle and brush panel toward the center of the top cover. Tighten the two screws to secure the baffle. • Remove the brush panel Figure 121. Removing the brush panel ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 117
Loosen the two screws to remove the brush panel from the top cover. • Remove the brush panel and baffle Figure 122. Removing the brush panel and baffle Loosen the two screws to remove the brush panel and baffle from the top cover. Step 11.
Page 118
Figure 123. Installing the latch plate Step 12. Remove the two doorstops from the right extension panel. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 119
Figure 124. Removing the doorstops Step 13. Secure the bottom hinge to the right extension panel with four screws. Figure 125. Securing the bottom hinge Step 14. If the rack needs to be shipped, install the three support brackets and skip steps 15 to 20. Note: The support brackets must be removed upon arrival at the site to install the RDHX.
Page 120
Step 15. Face the bottom side of the carton, remove the carton top, and slit the two carton corners on your right-hand side with a knife. Then, fold the right carton panel down to the ground, and rotate the threes carton inserts down. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 121
Bottom Figure 127. Unpacking the heat exchanger Step 16. With three people, rotate the heat exchanger to vertical on the three carton inserts. Then, remove the inner and outer hose access panels while one person hold the heat exchanger. Chapter 3 Rack cabinet setup...
Page 122
Figure 129. Lifting the heat exchanger with three people Handles that the first person hold on to Spots that the third person hold on to Handles that the second person hold on to ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 123
Step 18. Carry the heat exchanger with three people to the cabinet frame. Align the bottom corner with the bottom hinge pin; then, lower the heat exchanger to fit the pin in. Figure 130. Installing the heat exchanger to the rack cabinet Step 19.
Step 4 on page 119. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 125
Figure 132. Removing screws to prepare for extension installation Procedure Step 1. Remove the door. Chapter 3 Rack cabinet setup...
Page 126
Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Step 2. Remove the two hinges and the two doorstops. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 127
Figure 134. Removing the door hinges and doorstops Step 3. Remove the door latch. Figure 135. Removing the door latch Step 4. Secure an extension panel to the side of the rack with seven screws, and repeat the step on the other extension panel.
Page 128
Figure 136. Installing an extension panel ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 129
Figure 137. Installing an extension panel (with baying kit) Note: If baying kit has been installed previously, make sure to remove the two screws from top and bottom of the cabinet first. Then, secure the screws through the panel and the baying kit. Step 5.
Page 130
Figure 138. Installing the extension top cover Step 6. Secure each of the two support brackets to the extension panels with four screws. If the extension panel screws have not been fully tightened, tighten them now. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 131
Figure 139. Installing the support brackets Step 7. Install the two hinges, two doorstops, and the door latch to the rack. Chapter 3 Rack cabinet setup...
Page 132
Figure 140. Install the hinges, doorstops, and door latch Step 8. Install the door back to the rack. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 141. Installing the door Align the door with the hinges, and hold the door in place. Push the hinge pins down to the closed position so that the door is secured. Install 42U Standard Rack Extension Kit with RDHX See this topic to learn how to install 42U Standard Rack Extension Kit and RDHX.
Page 134
• A utility knife or a pair of scissors is required to unpack the extension kit. • The extension kit comes with a miscellaneous bag, which contains the following components: ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 135
Figure 143. Parts Description Description Quantity Quantity M6 cage nut Bottom support panel M6 screw M4 screw Top support panel M6 flat hex screw Right extension panel Bottom hinge for RDHX Left extension panel Top hinge for RDHX Support bracket Figure 144.
Page 136
Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Step 2. Remove the two hinges and the two doorstops. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 137
Figure 146. Removing the door hinges and extension bottom covers Step 3. Remove the door latch. Figure 147. Removing the door latch Step 4. Install fourteen M6 cage nuts to the rack frame with cage nut insertion tool or a flat-blade screwdriver.
Page 138
Rotate and pull the tool to force the other nut edge into the flange hole, and thus secure the nut. Figure 149. Installing cage nuts with cage nut insertion tool ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 139
With flat blade screwdriver Figure 150. Installing cage nuts with flat blade screwdriver Insert one edge of the cage nut into the target mounting flange hole. Press and compress the other nut edge with a flat-blade screwdriver, and rotate the screwdriver towards the flange hole until the nut edge goes in the hole.
Page 140
Figure 151. Installing an extension panel Step 6. Loosely tighten the four screws to secure the extension top cover to the panels loosely. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 141
Figure 152. Installing the extension top cover Note: After this step, the extension top cover should be active and could be slightly moved around. Step 7. If there is a plan to install RDHX, install the bottom hinge now. Otherwise, tighten all the screws installed in previous steps, and go on with installing the door (see “Install a door”...
Page 142
Step 10. Face the bottom side of the carton, remove the carton top, and slit the two carton corners on your right-hand side with a knife. Then, fold the right carton panel down to the ground, and rotate the threes carton inserts down. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 143
Bottom Figure 155. Unpacking the heat exchanger Step 11. With three people, rotate the heat exchanger to vertical on the three carton inserts. Then, remove the inner and outer hose access panels while one person hold the heat exchanger. Chapter 3 Rack cabinet setup...
Page 144
Figure 157. Lifting the heat exchanger with three people Handles that the first person hold on to Spots that the third person hold on to Handles that the second person hold on to ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 145
Step 13. Carry the heat exchanger with three people to the cabinet frame. Align the bottom corner with the bottom hinge pin on the rack cabinet; then, lower the heat exchanger to fit the pin in. Figure 158. Installing the heat exchanger to the rack cabinet Step 14.
Figure 159. Installing the top hinge Install insulation foams on-site See this topic to learn how to install insulation foams on-site. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Insulation foam dimensions: • Gap sealing foam: 1,500 x 30 x 1.5 † • Rear foam: 550 x 330 x 38 mm • Rear foam: 485 x 30 x 25.4 mm • Ground foams: 600 x 300 x 68 • Rear extension foam: 535 x 182 x 136 ‡...
) to the rear side of the rack cabinet as illustrated. Figure 161. Installing the rear foam Step 2. Peel off the liner, and attach the foam ( ) to the rear side of the rack cabinet as illustrated. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 162. Installing the rear foam Ground foams Step 1. Insert the foam ( ) into the rear bottom of the rack cabinet. Step 2. Insert the foam ( ) into the rear bottom of the rack cabinet until it connects to the other one. Figure 163.
Step 2. Center align the three foams with the extension, and attach them. Step 3. Repeat to attach the foams to the other three extensions. Figure 165. Installing extension foam ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Extension sealing foam Step 1. Unlock and open the door. Step 2. Remove the door. Figure 166. Removing a door Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged.
Page 152
Center align the foam with the folded edge of the right side of the rack, and attach it. Cut off the foam with a sharp tool where the guide pins are installed. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 153
Figure 168. Installing the extension sealing foam to the right side of the rack Step 5. Install the foam to the extension top cover and bottom cover. Align the foam with the folded edge of the extension top cover, and attach it. Cut off the excess foam with a sharp tool.
Page 154
Figure 169. Installing the extension sealing foam to the extension top cover and bottom cover Step 6. Install the door. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 170. Installing a door Align the door with the hinges, and hold the door in place. Push the hinge pins down to the closed position so that the door is secured. Install nuts on the mounting flanges See this topic to learn how to adjust mounting flange holes with various types of nuts. Install clip nuts Procedure Step 1.
Release the screwdriver to secure the nut in the mounting flange hole. Install cage nuts with insertion tool Procedure Step 1. Locate the flange hole to install the nut in. Step 2. Install the cage nut. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 173. Installing a cage nut Insert one edge of the cage nut into the target mounting flange hole, and hook the other edge with the insertion tool through the flange hole. Rotate and pull the tool to force the other nut edge into the flange hole, and thus secure the nut.
Page 158
Align the bottom of the side cover with the slot on the rack cabinet; then, connect the grounding jumper wire to the posts on the rack frame and the side cover. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 159
Figure 176. Installing the grounding jumper wire Step 4. Secure the side cover to the rack cabinet. Chapter 3 Rack cabinet setup...
“Replace a regular door with Rear Door Heat eXchanger V2” on page 155. Important: Make sure to plan the cooling system with consideration of “Water specifications for the secondary cooling loop” on page 165. S010 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 161
CAUTION: Do not place any object weighing more than 82 kg (180 lb) on top of rack-mounted devices. S019 CAUTION: The power-control button on the device does not turn off the electrical current supplied to the device. The device also might have more than one connection to dc power. To remove all electrical current from the device, ensure that all connections to dc power are disconnected at the dc power input terminals.
The other specially trained persons must guide the rack down the ramp by holding onto the rack frame. Slowly roll the rack down the ramp until the casters are on the floor. Move the rack to the final location. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 179. Moving the rack cabinet from the pallet After this task is completed Proceed to “Fill the heat exchanger with water” on page 175. Replace a regular door with Rear Door Heat eXchanger V2 See this topic to learn how to replace a regular rear door with ThinkSystem Rear Door Heat eXchanger V2. Procedure Step 1.
Page 164
Figure 180. Lowering the leveling pads Step 2. Remove the rear door from the rack cabinet. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 165
Figure 181. Removing a door Step 3. Remove the two door hinges and the two doorstops. Chapter 3 Rack cabinet setup...
Page 166
Figure 183. Removing the door latch Step 5. Align the holes in the latch plate with those in the two clip nuts; then, secure the latch plate in place with two M6 screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 167
Figure 184. Installing the latch plate Step 6. Install the upper air baffle. Figure 185. Installing the upper air baffle Remove the two screws that secure the rear cable access cover, and remove the cover. Align the upper air baffle with the slot, and secure it with three screws. Chapter 3 Rack cabinet setup...
Page 168
Align the lower air baffle to the bottom cable slot, and secure it with four screws as illustrated. Figure 187. Installing the lower air baffle Step 9. Secure the bottom hinge assembly to the rack cabinet with eight screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 169
Figure 188. Installing the bottom hinge assembly Step 10. Face the bottom side of the carton, remove the carton top, and slit the two carton corners on your right-hand side with a knife. Then, fold the right carton panel down to the ground, and rotate the threes carton inserts down.
Page 170
Step 11. With three people, rotate the heat exchanger to vertical on the three carton inserts. Then, remove the inner and outer hose access panels while one person hold the heat exchanger. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 171
Figure 190. Removing the hose access panels Step 12. Hold the heat exchanger with three people on the handles/spots as illustrated. Then, carefully lift the heat exchanger and turn it upright. Figure 191. Lifting the heat exchanger with three people Handles that the first person hold on to Spots that the third person hold on to Handles that the second person hold on to...
Page 172
Figure 192. Installing the heat exchanger to the rack cabinet Step 14. Hold the heat exchanger in place with two people. Insert the top hinge pin to the heat exchanger; then, secure the hinge with three screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 193. Installing the top hinge After this task is completed Proceed to “Fill the heat exchanger with water” on page 175. Water specifications for the secondary cooling loop It is of crucial importance that water supplied to the heat exchanger meet the requirements listed in this topic.
Page 174
The water pressure in the secondary loop must be less than 690 kPa (100 psi). Normal operating pressure at the heat exchanger must be 414 kPa (60 psi) or less. • Flow rate ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 175
The flow rate of the water in the system must be in the range of 23 - 57 liters (6 - 15 gallons) per minute. Pressure drop versus flow rate for heat exchangers (including quick-connect couplings) is defined as approximately 103 kPa (15 psi) at 57 liters (15 gallons) per minute. •...
Page 176
0, flow impedance quick connects. Alternatively, these quick connects can be eliminated and replaced with a hose barb connection. Following are some examples of the most common solutions. • Primary and secondary cooling loops ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 177
Figure 194. Primary and secondary cooling loops This figure shows a typical cooling solution and identifies the components of the primary cooling loop and the secondary cooling loop. • Coolant distribution unit with a fabricated facilities solution Chapter 3 Rack cabinet setup...
Page 178
This figure shows an example of a facilities fabricated solution. The actual number of heat exchangers that are connected to a secondary loop depends on the capacity of the coolant distribution unit that is running the secondary loop. • Coolant distribution unit with off-the-shelf supplier solutions ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 179
Figure 196. Coolant distribution unit that uses off-the-shelf supplier solutions Notes: Supplier-built coolant distribution unit (CDU) suggested features: – Temperature and flow metering (monitoring) – Leak detection or water level sensing and shutdown – Local and remote monitoring and control –...
Page 180
• Use a 50.8 mm (2 in.) or larger supply pipe to provide the correct flow to three 19 mm (0.75 in.) supply hoses, with a 100 kW coolant distribution unit (CDU). ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 181
• Use a 63.5 mm (2.50 in.) or larger supply pipe to provide the correct flow to four 19 mm (0.75 in.) supply hoses, with a 120 kW CDU. • Use an 88.9 mm (3.50 in.) or larger supply pipe to provide the correct flow to nine 19 mm (0.75 in.) supply hoses, with a 300 kW CDU.
Page 182
• If a low impedance quick-connect coupling is used at the opposite (manifold) end of the hose, use positive locking mechanisms to prevent loss of water when the hoses are disconnected. The connections must minimize water spill and air inclusion into the system when they are disconnected. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Fill the heat exchanger with water See this topic to learn how to fill ThinkSystem Rear Door Heat eXchanger V2 with water. About this task S038 CAUTION: Eye protection should be worn for this procedure. Attention: Wear safety goggles or other eye protection whenever you fill, drain, or purge air or nitrogen from the heat exchanger.
Page 184
Align the supply hose coupling with the supply manifold, push it in and pull the collar backward until it locks in place with an audible click. Then, repeat the same procedure on the return hose and manifold. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 185
Figure 203. Supply and return hoses and manifold couplings • Connect the supply hose assembly ( ) to the supply manifold-coupling ( • Connect the return hose assembly ( ) to the return manifold-coupling ( Step 5. Turn on the flow of water to the heat exchanger, and let it run for several minutes. Step 6.
Page 186
Attention: If water drips from the air-purging valve after you remove the air-purging tool, reattach the tool and disconnect it again to seal the valve. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 187
Figure 205. Removing the air-purging tool Step 8. Install the valve cap back to the air-purging valve. Figure 206. Installing the valve cap Chapter 3 Rack cabinet setup...
Figure 208. Installing the outer hose access panel Install a 0/1U device into the rack See this topic to learn how to install a 0/1U device into the rack side. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 189
About this task S001 DANGER Electrical current from power, telephone, and communication cables is hazardous. To avoid a shock hazard: • Connect all power cords to a properly wired and grounded electrical outlet/source. • Connect any equipment that will be attached to this product to properly wired outlets/sources. •...
“Install a 1U PDU or console switch to the rack side” on page 183 • “Install a 1U device into the side pocket” on page 184 Install a 0U device Procedure ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Step 1. Insert the two PDU pegs into the keyhole slots in the side of the rack cabinet, and push down the PDU to secure it to the rack. Figure 209. Installing a 0U PDU Note: 0U PDU can be installed with sockets facing either rear or center of the rack cabinet. Install a 1U PDU or console switch to the rack side Procedure Step 1.
Refer to the document that comes with the device, and install the mounting brackets if necessary. Step 2. Remove the side cover next to the side pocket (see “Remove a side cover” on page 197 Step 3. Install the device. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 193
Figure 211. Installing a 1U PDU or console switch Install four M6 clip nuts on the rack flanges as shown in the illustration. Slide the device all the way into the side pocket. Secure the device with four M6 screws. Step 4.
Page 194
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 196
Cable access openings on the top of the rack cabinet Front cable access cover Rear cable access cover Figure 214. Cable access openings on the top of the cabinet Front cable access cover ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 197
Slide the cover as far forward as possible to close off the open area, thus prevent hot exhaust air from recirculating back through the rack. Rear cable access cover Slide the cover all the way open or closed, or in any intermediate position. Leaving the cover open provides extra exhaust area for components near the top and bottom of the rack;...
Page 198
Cable strap module Figure 216. Cable strap module Two lines of built-in cable straps along the front door frame are available for cable management. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 199
Cable access openings on extension panel There are five openings on each extension panel: • U0.5 to U1.5 • U7 to U11 • U14 to U29 • U31 to U35 • U40 to U42 Figure 217. Cable access openings on extension panel — 42U Advanced Rack Extension Kit Chapter 4 Managing cables and hoses...
• Install filler panels over all unoccupied bays. • Route signal cables at the rear of the rack so that they enter or exit the cabinet through the top and bottom air baffles. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 219. Managing cables with the upper air baffle Figure 220. Managing cables with the lower air baffle • Bundle signal cables together in a rectangle so that the air-baffle sliders are closed as far as possible. Do not bundle signal cables together in a circular formation. Raised-floor environment The following illustrations show routing and securing the hoses in a raised-floor environment for individual racks and adjacent racks.
Page 202
200 mm (8 in.) to pass through the floor. If adjacent racks share a hole in the floor, increase the size of the hole according to the number of hoses, 50 mm (2 in.) in length for every rack. For ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
example, the hole for one rack is 100 x 200 mm (4 x 8 in.), the hole for two racks is 150 x 200 mm (6 x 8 in.), and so on. Smaller hole sizes might also work, depending on the hose routing underneath the raised floor.
Page 204
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 206
Align the bottom of the side cover with the slot on the rack cabinet. Rotate the top of the cover towards the rack. Step 2. Secure the side cover to the rack cabinet. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 226. Securing the side cover Note: This procedure is best executed by two people. Press and hold the latch of one side, and firmly press the upper corner in. Repeat the previous step on the other side. Lock the side cover with the key. Installing, removing, and converting the door See this topic to learn how to remove, install and convert the door Remove and install a door...
Page 208
Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Install a door Procedure Step 1. Install the door. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 228. Installing a door Align the door with the hinges, and hold the door in place. Push the hinge pins down to the closed position so that the door is secured. Reverse a door See this topic to learn how to reverse a door. Procedure Step 1.
Page 210
Hold the door in place, and lift both hinge pins until they lock in the open position so that the door is disengaged. Remove the door from the rack cabinet frame. Step 2. Remove the two hinges and the two doorstops. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 211
Figure 230. Removing the hinges and the doorstops Step 3. Reverse the door latch. Chapter 5 Hardware removal, installation and reversion...
Page 212
Remove the two screws that secure the latch to the rack. Rotate the latch 180 degree, and secure it to the opposite side on the rack cabinet with two screws. Step 4. Reverse the hinge orientation ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 213
Figure 232. Reversing the hinge orientation Pull the retainer spring out to release the hinge pin from the hinge. Pull and remove the pin from the hinge. Rotate the hinge 180 degree. Insert the pin from the top of the hinge. Step 5.
Page 214
Figure 233. Installing hinges and doorstops Step 7. Reverse the door handle. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 215
Figure 234. Reversing the door handle Rotate the door 180 degree. Remove the screw that secures the handle to the door. Rotate the door handle 180 degree, and secure it to the door with a screw. Step 8. Install the door. Chapter 5 Hardware removal, installation and reversion...
The illustrations below present the rear views of a rack cabinet; three sets of manifolds and three sets of connection hoses. There are two labels attached to the front of the manifolds, and one label on one end of each hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 236. Manifolds in a Figure 237. Manifolds in a 42U in-row system 42U in-rack system Figure 238. Manifolds in a Figure 239. Manifolds in a 48U in-row system 48U in-rack system Figure 241. 42U in-rack connection set Figure 243. 48U in-rack connection set Figure 240.
Page 218
S011 CAUTION: Sharp edges, corners, or joints nearby. S038 CAUTION: Eye protection should be worn for this procedure. S040 CAUTION: Protective gloves should be worn for this procedure. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 219
Chapter 5 Hardware removal, installation and reversion...
Page 220
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 221
Attention: • Ensure proper handling procedures are followed when working with any chemically treated coolant used in the rack cooling system. Ensure that material safety data sheets (MSDS) and safety information are provided by the coolant chemical treatment supplier and that proper personal protective equipment (PPE) is available as recommended by the coolant chemical treatment supplier.
Page 222
Pull the hose off. Re-install the rubber quick connect plug covers to the ports on the manifold. Step 4. Repeat Step 3 step 3 on page 214 to the other manifold. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 223
Step 5. Disengage the connection set from ball valves. Figure 246. Removing the connection set Rotate the ball valve to the left. Pull the connection set off from ball valve. Step 6. Remove the manifold with the connection set attached. Figure 247.
Page 224
Plug the bleeder kit to the manifold. Step 9. Slowly open the bleeder valve to allow a steady stream of coolant to drain. Close the bleeder valve once coolant stops flowing. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 225
Figure 249. Opening the bleeder valve Step 10. Install the bleeder kit to the manifold return side. Note: This step drains the coolant with the help of a pressure difference inside and outside the return manifold. Chapter 5 Hardware removal, installation and reversion...
Page 226
Step 11. Slowly open the bleeder valve to allow a steady stream of coolant to drain. Close the bleeder valve once coolant stops flowing. Figure 251. Opening the bleeder valve ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Step 12. Separate the manifold from the connection set in a dry and clean work area, and keep a bucket and absorbent cloths around to collect any coolant that may drain out. Figure 252. Separating the manifold from the connection set 17 mm wrench Loosen the screw that locks the ferrule.
Page 228
CAUTION: Sharp edges, corners, or joints nearby. S038 CAUTION: Eye protection should be worn for this procedure. S040 CAUTION: Protective gloves should be worn for this procedure. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 229
Chapter 5 Hardware removal, installation and reversion...
Page 230
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 231
Attention: • Ensure proper handling procedures are followed when working with any chemically treated coolant used in the rack cooling system. Ensure that material safety data sheets (MSDS) and safety information are provided by the coolant chemical treatment supplier and that proper personal protective equipment (PPE) is available as recommended by the coolant chemical treatment supplier.
Page 232
Hold the manifold with both hands, and mount it onto the rack cabinet. Align the spools with holes, and clutch the cabinet. Step 4. Repeat the last step to install the other manifold. Step 5. Install ball valves to CDU. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 233
Figure 254. Installing ball valves Connect the ball valves to Supply and Return ports. Wrap the interface around with the clamp. Close the clamp. Lift the screw upright. Tighten the screw and make sure that it is secured. Step 6. Install the connection set to manifolds.
Page 234
Prepare the in-rack CDU. Connect the feed hose to inlet port on the front. Figure 257. The front of CDU Connect hoses to the drain port and bleeder port on the rear. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 235
• For more operation and maintenance guidelines, see Lenovo Neptune DWC RM100 in-rack Coolant Distribution Unit (CDU) Operation & Maintenance Guide. • For service support, associated warranty and maintenance sizing, contact Lenovo Professional Services team at cdusupport@lenovo.com. Step 9. Install the quick connect plug to the manifolds.
Page 236
Remove the rubber quick connect plug covers from the ports on the manifold. Plug the bleeder kit to the manifold. Step 11. To push the air out of the manifolds, open ball valve switches to let coolant fill the system. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 237
Figure 261. Opening ball valves Press the button on the ball valve switch. Rotate the switch to fully open the valves as illustrated above. Attention: • Pay close attention to the front display of CDU and maintain the system pressure at one bar. •...
Page 238
Step 14. Slowly open the bleeder valve to conduct the air out of the hose. Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 239
Figure 264. Opening the bleeder valve on the return side Step 15. (For precaution) To make sure that the air inside is as little as possible, re-install the bleeder kit back to manifold supply side and do it one more time. Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose.
The device also might have more than one power cord. To remove all electrical current from the device, ensure that all power cords are disconnected from the power source. S011 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 241
CAUTION: Sharp edges, corners, or joints nearby. S038 CAUTION: Eye protection should be worn for this procedure. S040 CAUTION: Protective gloves should be worn for this procedure. Chapter 5 Hardware removal, installation and reversion...
Page 242
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 243
Chapter 5 Hardware removal, installation and reversion...
Page 244
Protective gloves and eyewear may be recommended as a precaution. • This task requires two or more people. Procedure Step 1. Close both ball valves. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 245
Figure 266. Closing ball valves Note: Manifold supply connects to facility Manifold return connects to facility return supply Press the button on the ball valve switch. Rotate the switches to close the valves as illustrated above. Step 2. Remove the quick connect plugs to separate the hoses from the manifold. Note: Depending on the model, your server might look different from the illustrations in this topic.
Page 246
Re-install the rubber quick connect plug covers to the ports on the manifold. Step 3. Repeat Step 2 step 2 on page 237 to the other manifold. Step 4. Remove the manifold with the hose kit attached. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 247
Figure 268. Removing the manifold Hold the manifold with both hands, and lift it upward to relocate the spools from the small openings to large ones on the rack cabinet. Remove the manifold with the hose kit attached. Step 5. Repeat Step 4 step 4 on page 238 to the other manifold.
Page 248
Plug the bleeder kit to the manifold. Step 7. Slowly open the bleeder valve to allow a steady stream of coolant to drain. Close the bleeder valve once coolant stops flowing. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 249
Figure 270. Opening the bleeder valve Step 8. Install the bleeder kit to the manifold return side. Note: This step drains the coolant with the help of a pressure difference inside and outside the return manifold. Chapter 5 Hardware removal, installation and reversion...
Page 250
Plug the bleeder kit to the manifold. Step 9. Slowly open the bleeder valve to allow a steady stream of coolant to drain. Close the bleeder valve once coolant stops flowing. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 251
Figure 272. Opening the bleeder valve Step 10. Separate the manifold from the hose kit in a dry and clean work area, and keep a bucket and absorbent cloths around to collect any coolant that may drain out. Figure 273. Separating the manifold from the hose kit 17 mm wrench Loosen the screw that locks the ferrule.
S011 CAUTION: Sharp edges, corners, or joints nearby. S038 CAUTION: Eye protection should be worn for this procedure. S040 CAUTION: Protective gloves should be worn for this procedure. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 253
Chapter 5 Hardware removal, installation and reversion...
Page 254
ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 255
Attention: • Ensure proper handling procedures are followed when working with any chemically treated coolant used in the rack cooling system. Ensure that material safety data sheets (MSDS) and safety information are provided by the coolant chemical treatment supplier and that proper personal protective equipment (PPE) is available as recommended by the coolant chemical treatment supplier.
Page 256
Repeat the last step to install the other manifold. Step 4. Install the quick connect plug to the manifolds. Note: Depending on the model, your server might look different from the illustrations in this topic. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 257
Figure 275. Installing the quick connect plug Remove the rubber quick connect plug covers from the ports on the manifold. Connect the plug to the manifold port. Step 5. Install the hose kit to the manifold. Chapter 5 Hardware removal, installation and reversion...
Page 258
Wrap the interface around with the clamp. Close the clamp. Lift the screw upright. Tighten the screw and make sure that it is secured. Step 6. Install the bleeder kit to the manifold supply side. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 259
Figure 277. Installing the bleeder kit to the supply side Remove the rubber quick connect plug covers from the ports on the manifold. Plug the bleeder kit to the manifold. Step 7. To push the air out of the manifold supply side, connect facility supply to manifold return. Chapter 5 Hardware removal, installation and reversion...
Page 260
Slowly open the bleeder valve to conduct the air out of the hose. Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 261
Figure 279. Opening the bleeder valve on the supply side Step 9. Install the bleeder kit to the manifold return side. Chapter 5 Hardware removal, installation and reversion...
Page 262
Remove the rubber quick connect plug covers from the ports on the manifold. Plug the bleeder kit to the manifold. Step 10. To push the air out of the manifold return side, connect facility supply to manifold supply. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 263
Figure 281. Facility supply to manifold supply Press the button on the ball valve switch. Rotate both switches open and stop at around 1/4 of 90 degrees. Attention: • Open the ball valves on manifold supply side and facility supply side, while keep manifold return side closed.
Page 264
Close the bleeder valve once a steady stream of water flows into the bucket or there are only minimal bubbles in the bleeder hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 265
Figure 283. Opening the bleeder valve on the supply side Step 13. Once completed, connect the supply and return of manifold and facility correspondingly. Fully open all connections on both supply and return sides. Figure 284. Opening ball valves Note: Manifold supply connects to facility Manifold return connects to...
Attention: Wear safety goggles or other eye protection whenever you fill, drain, or purge air or nitrogen from the heat exchanger. Procedure Step 1. Lift and remove the inner hose access panel from the heat exchanger. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 267
Figure 285. Removing the inner hose access panel Step 2. Remove the screw that secures the panel if applicable, then lift and remove the panel from the heat exchanger. Figure 286. Removing the outer hose access pane Step 3. Disconnect the return and supply hose from the manifolds, and remove them from the heat exchanger.
Page 268
) from the supply manifold-coupling ( • Remove the return hose assembly ( ) from the return manifold-coupling ( Step 4. Remove the caps from the air-purging and drain valve. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 269
Figure 288. Removing valve caps Step 5. Remove the extension hose from the air-purging tool. Figure 289. Removing the extension hose Step 6. Insert one end of the air-purging tool extension hose into the center of air-purging valve stem at the top of the heat exchanger to allow air to enter the manifolds.
Page 270
2-liter (or larger) container to catch the water. Figure 291. Draining water Step 8. When the water is drained completely, remove the air-purging-tool extension hose from the valve. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 271
Figure 292. Removing the air-purging tool extension hose Step 9. Remove the air-purging tool from the drain valve. Figure 293. Removing the air-purging tool Step 10. Install the two caps back to the air-purging and drain valve. Chapter 5 Hardware removal, installation and reversion...
See this topic to learn how to remove ThinkSystem Rear Door Heat eXchanger V2. About this task S036 18 - 32 kg (39 - 70 lb) 32 - 55 kg (70 - 121 lb) CAUTION: Use safe practices when lifting. S010 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 273
CAUTION: Do not place any object weighing more than 82 kg (180 lb) on top of rack-mounted devices. S019 CAUTION: The power-control button on the device does not turn off the electrical current supplied to the device. The device also might have more than one connection to dc power. To remove all electrical current from the device, ensure that all connections to dc power are disconnected at the dc power input terminals.
Page 274
• Without rack extension kit installed Figure 295. Removing the top hinge Unfasten the three screws to remove the top hinge. • With 42U Advanced Rack Extension Kit installed ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 275
Figure 296. Removing the top hinge Unfasten the seven screws to remove the top hinge. • With 42U Standard Rack Extension Kit installed Figure 297. Removing the top hinge Chapter 5 Hardware removal, installation and reversion...
Page 276
Handles that the second person hold on to Step 4. Lift the heat exchanger with three people as described in the previous step, and remove it from the rack cabinet. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 299. Removing the heat exchanger from the rack cabinet Install Rear Door Heat eXchanger V2 See this topic to learn how to install ThinkSystem Rear Door Heat eXchanger V2. About this task S036 18 - 32 kg (39 - 70 lb) 32 - 55 kg (70 - 121 lb) CAUTION: Use safe practices when lifting.
Page 278
R004 CAUTION: See the instructions in the rack documentation before you install devices, remove devices, or relocate the rack. S038 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 279
CAUTION: Eye protection should be worn for this procedure. Procedure Step 1. (With 42U Advanced Rack Extension Kit installed only) Make sure the three support brackets are removed from the extension panels. Figure 300. Removing the support brackets Step 2. Face the bottom side of the carton, remove the carton top, and slit the two carton corners on your right-hand side with a knife.
Page 280
With three people, rotate the heat exchanger to vertical on the three carton inserts. Then, remove the inner and outer hose access panels while one person hold the heat exchanger. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 281
Figure 302. Removing the hose access panels Step 4. Hold the heat exchanger with three people on the handles/spots as illustrated. Then, carefully lift the heat exchanger and turn it upright. Figure 303. Lifting the heat exchanger with three people Handles that the first person hold on to Spots that the third person hold on to Handles that the second person hold on to...
Page 282
Step 6. Hold the heat exchanger in place with two people, and install the top hingeDepending on the configuration, select the corresponding installation procedures: • Without rack extension kit installed ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 283
Figure 305. Installing the top hinge Insert the top hinge pin to the heat exchanger; then, secure the hinge with three screws. • With 42U Advanced Rack Extension Kit installed Chapter 5 Hardware removal, installation and reversion...
Page 284
Insert the top hinge pin to the heat exchanger; then, secure the hinge with seven screws. • With 42U Standard Rack Extension Kit installed Figure 307. Installing the top hinge ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Insert the top hinge pin to the heat exchanger; then, secure the hinge with three screws. After this task is completed Proceed to “Fill the heat exchanger with water” on page 277. Fill the heat exchanger with water See this topic to learn how to fill ThinkSystem Rear Door Heat eXchanger V2 with water. About this task S038 CAUTION:...
Page 286
Figure 309. Removing the outer hose access panel Step 3. Purge the nitrogen that has been filled in the hose from the hose. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 287
Figure 310. Purging nitrogen Loosen and remove the cap from the air-purging valve. Press in on the valve stem of the air-purging valve to purge the nitrogen from the heat exchanger. Continue holding in the valve stem until the pressure is released. Step 4.
Page 288
Attention: If water drips from the air-purging valve after you remove the air-purging tool, reattach the tool and disconnect it again to seal the valve. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 289
Figure 313. Removing the air-purging tool Step 8. Install the valve cap back to the air-purging valve. Figure 314. Installing the valve cap Chapter 5 Hardware removal, installation and reversion...
M4 screw. Figure 316. Installing the outer hose access panel Replace the door latch See this topic to learn how to replace the door latch of Rear Door Heat eXchanger. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Procedure Step 1. Remove the screw that secure the latch to the heat exchanger; then, secure the replacement unit with the same screw. Figure 317. Replacing the door latch Installing and removing rack extension kit The rack cabinet supports up to two units of rack extension kit. See this topic to learn how to remove and install the rack extension kit.
Page 292
– One 4 mm Hex bit socket to tighten the M6 screws ( in the next bullet point) • The extension kit comes with a miscellaneous bag, which contains the following components: ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 293
Figure 319. Parts Description Quantity Description Quantity Left extension panel M6 cage nut M6 x 16 mm hex head flange Support bracket screw M6 x 12 mm flat head Cable strap module socket cap screw Doorstop Grounding plate M6 x 16 mm flat head socket Door latch cap screw M4 x 6 mm flat head socket...
Page 294
Step 1. Install fourteen M6 cage nuts to the rack frame with cage nut insertion tool or a flat-blade screwdriver. Figure 321. Cage nut installation location With cage nut insertion tool ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 295
Insert one edge of the cage nut into the target mounting flange hole, and hook the other edge with the insertion tool through the flange hole. Rotate and pull the tool to force the other nut edge into the flange hole, and thus secure the nut. Figure 322.
Page 296
Figure 324. Installing the extension panels Step 3. Align the extension top cover with the screw holes on the extension panels, and secure it with six screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 297
Figure 325. Installing the extension top cover Step 4. Depending on the requirements, remove the filler(s) from the extension panels to route cables. Chapter 5 Hardware removal, installation and reversion...
Page 298
Depending on the requirements, select the corresponding installation procedures. • Bracket with two keyhole slots (up to two PDUs, or one PDU and one manifold) Notes: – Below illustration shows the locations for installing the brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 299
Figure 327. Locations for installing the brackets with two keyhole slots – If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. Chapter 5 Hardware removal, installation and reversion...
Page 300
Figure 328. Replacing the screws Remove the M6 hex head flange screw. Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with four screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 301
Figure 329. Installing the bracket with two keyhole slots 2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. Choose the left or right slot for PDU installation based on the requirements.
Page 302
Note: PDU can be rotated 180 degrees for installation with the input cable at the bottom. • L-shaped bracket (up to two PDUs, or one PDU and one manifold) Notes: – Below illustration shows the locations for installing the brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 303
Figure 331. Locations for installing the L-shaped brackets – If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. Chapter 5 Hardware removal, installation and reversion...
Page 304
Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with three screws. Choose the installation location for the bracket based on the orientation of the PDU. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 305
Figure 333. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet Chapter 5 Hardware removal, installation and reversion...
Page 306
Figure 334. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet 2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 307
Figure 335. Installing the PDU with the PDU facing the front of the rack cabinet Chapter 5 Hardware removal, installation and reversion...
Page 308
Figure 336. Installing the PDU with PDU facing the rear of the rack cabinet Step 6. Depending on the requirements, select one of the following methods to ensure there is sufficient space for routing cables. • Slide the brush panel ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 309
Figure 337. Sliding the brush panel Loosen the two screws that secure the baffle to the top cover. Slide the baffle and brush panel toward the center of the top cover. Tighten the two screws to secure the baffle. • Remove the brush panel Figure 338.
Page 310
Loosen the two screws to remove the brush panel and baffle from the top cover. Step 7. Install the two door hinges and the door latch to the extension panels. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 311
Figure 340. Installing the door hinges and door latch Step 8. If the rack needs to be shipped, install the three support brackets. Note: Depending on the requirement, remove the support brackets upon arrival at the site. Figure 341. Installing the support brackets Chapter 5 Hardware removal, installation and reversion...
If any devices are installed to the extension panels, remove them (see “Remove a 0U PDU” on page 349). Step 3. Unfasten the six screws, and remove the extension top cover. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 313
Figure 343. Removing the extension top cover Step 4. Unfasten the fourteen screws, and remove the two extension panels. Chapter 5 Hardware removal, installation and reversion...
Step 2 on page 310. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 315
Figure 345. Removing screws to prepare for extension installation • Required tools – One tool with plastic blade/scissors to open the packaging – One rubber hammer to align the extension panels with the side of the rack – One Screwdriver with No. 3 Phillips bit to tighten the M6 screws ( in the next bullet point) –...
Page 316
Cable straps are removable, remove the straps from the extension panels if needed. – Cable straps can be lengthened by connecting two or more straps together. – Use cable straps to secure PDUs and manifolds prior to shipping. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 317
– Connect one end of the grounding wire to the grounding plate on the extension panel and the other end to the nearest grounding plate on the rack. Figure 347. Hex Allen wrenches Description Hex Allen wrench, 4 mm Hex Allen wrench, 3 mm Hex Allen wrench, 2.5 mm Procedure Step 1.
Page 318
Release the screwdriver to secure the nut in the mounting flange hole. Step 2. Install the bottom hinge. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 319
Figure 351. Securing the bottom hinge Note: Do not fully tighten the four screws in this step. Align the hinge with the rack. Secure the hinge to the rack with four screws. Step 3. Secure the two extension panels to the rack with fourteen screws. Notes: •...
Page 320
Figure 352. Installing the extension panels Step 4. Align the extension top cover with the screw holes on the extension panels, and secure it with six screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 321
Figure 353. Installing the extension top cover Step 5. Depending on the requirements, remove the filler(s) from the extension panels to route cables. Chapter 5 Hardware removal, installation and reversion...
Page 322
Depending on the requirements, select the corresponding installation procedures. • Bracket with two keyhole slots (up to two PDUs, or one PDU and one manifold) Notes: – Below illustration shows the locations for installing the brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 323
Figure 355. Locations for installing the brackets with two keyhole slots – If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. Chapter 5 Hardware removal, installation and reversion...
Page 324
Figure 356. Replacing the screws Remove the M6 hex head flange screw. Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with four screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 325
Figure 357. Installing the bracket with two keyhole slots 2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. Choose the left or right slot for PDU installation based on the requirements.
Page 326
Note: PDU can be rotated 180 degrees for installation with the input cable at the bottom. • L-shaped bracket (up to two PDUs, or one PDU and one manifold) Notes: – Below illustration shows the locations for installing the brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 327
Figure 359. Locations for installing the L-shaped brackets – If one or two brackets are installed in the locations indicated in the illustration below, the M6 hex head flange screw must be replaced with an M6 round head flange screw. Chapter 5 Hardware removal, installation and reversion...
Page 328
Install the M6 round head flange screw. 1. Align the bracket with the extension panel, and secure it with three screws. Choose the installation location for the bracket based on the orientation of the PDU. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 329
Figure 361. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet Chapter 5 Hardware removal, installation and reversion...
Page 330
Figure 362. Installing the L-shaped bracket with the PDU facing the front of the rack cabinet 2. Insert the two PDU pegs into the keyhole slots on the brackets, and push down the PDU to secure it to the brackets. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 331
Figure 363. Installing the PDU with the PDU facing the front of the rack cabinet Chapter 5 Hardware removal, installation and reversion...
Page 332
Figure 364. Installing the PDU with PDU facing the rear of the rack cabinet Step 7. Depending on the requirements, select one of the following methods to ensure there is sufficient space for routing cables. • Slide the brush panel ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 333
Figure 365. Sliding the brush panel Loosen the two screws that secure the baffle to the top cover. Slide the baffle and brush panel toward the center of the top cover. Tighten the two screws to secure the baffle. • Remove the brush panel Figure 366.
Page 334
Loosen the two screws to remove the brush panel and baffle from the top cover. Step 8. Tighten the two screws to secure the latch plate to the left extension panel. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 335
Figure 368. Installing the latch plate Step 9. Remove the two doorstops from the right extension panel. Chapter 5 Hardware removal, installation and reversion...
Page 336
Step 11. If the rack needs to be shipped, install the three support brackets and skip steps 12 to 17. Note: The support brackets must be removed upon arrival at the site to install the RDHX. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 337
Figure 371. Installing the support brackets Step 12. Face the bottom side of the carton, remove the carton top, and slit the two carton corners on your right-hand side with a knife. Then, fold the right carton panel down to the ground, and rotate the threes carton inserts down.
Page 338
Step 13. With three people, rotate the heat exchanger to vertical on the three carton inserts. Then, remove the inner and outer hose access panels while one person hold the heat exchanger. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 339
Figure 373. Removing the hose access panels Step 14. Hold the heat exchanger with three people on the handles/spots as illustrated. Then, carefully lift the heat exchanger and turn it upright. Figure 374. Lifting the heat exchanger with three people Handles that the first person hold on to Spots that the third person hold on to Handles that the second person hold on to...
Page 340
Step 16. Hold the heat exchanger in place with two people. Insert the top hinge pin to the heat exchanger; then, secure the hinge with seven screws. Note: Do not fully tighten the seven screws in this step. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Figure 376. Installing the top hinge Step 17. Follow the sequence below to fully tighten the screws. Note: Hold the handles on the heat exchanger and slightly lift it in steps 17-a to 17-c. 1. Four top hinge screws on the right side in Step 16 Step 16 on page 332 2.
Page 342
Step 4. Unfasten the six screws, and remove the extension top cover. Figure 378. Removing the extension top cover Step 5. Unfasten the fourteen screws, and remove the two extension panels. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 343
Figure 379. Removing the extension panels Step 6. Remove the bottom hinge. Figure 380. Removing the bottom hinge Loosen the four screws from the hinge. Chapter 5 Hardware removal, installation and reversion...
Secure an extension panel to the side of the rack with seven screws, and repeat the step on the other extension panel. Note: It is advised not to fully tighten the screws in this step. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 345
Figure 382. Installing an extension panel Chapter 5 Hardware removal, installation and reversion...
Page 346
Then, secure the screws through the panel and the baying kit. Step 2. Align the extension top cover with the screw holes on the front of the rack, and secure each side with two screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 347
Figure 384. Installing the extension top cover Step 3. Secure each of the two support brackets to the extension panels with four screws. If the extension panel screws have not been fully tightened, tighten them now. Chapter 5 Hardware removal, installation and reversion...
Page 348
Figure 385. Installing the support brackets Step 4. Install the two hinges, two doorstops, and the door latch to the rack. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 349
Figure 386. Install the hinges, doorstops, and door latch Step 5. Install the door back to the rack. Chapter 5 Hardware removal, installation and reversion...
Step 2. Remove the door from the rack cabinet (see “Remove a door” on page 199). Step 3. Remove the two hinges, two door stops, and the door latch if necessary. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 351
Figure 388. Removing the door hinges, doorstops and latch Step 4. Remove the four screws that secure each of the two support brackets, and remove the support brackets. Chapter 5 Hardware removal, installation and reversion...
Page 352
Figure 389. Removing the support brackets Step 5. Remove the four screws that secure the top cover, and remove the cover. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 353
Figure 390. Removing the extension top cover Step 6. Remove the seven screws that secure the extension panel, and repeat the step on the other extension panel. Chapter 5 Hardware removal, installation and reversion...
Page 354
Figure 391. Installing an extension panel After this task is completed Complete the following steps to install the door back to the rack if necessary. 1. Install the door latch. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 355
Figure 392. Installing the door latch 2. Install the two hinges and the two doorstops. Figure 393. Installing the hinges and doorstops 3. Install the door. Chapter 5 Hardware removal, installation and reversion...
Procedure Step 1. Insert the two PDU pegs into the keyhole slots in the side of the rack cabinet, and push down the PDU to secure it to the rack. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 357
Figure 395. Installing a 0U PDU Note: 0U PDU can be installed with sockets facing either rear or center of the rack cabinet. Remove a 0U PDU Procedure Step 1. Lift the PDU to detach it from the rack, and remove it. Chapter 5 Hardware removal, installation and reversion...
Install or remove a 1U device into or from the rack side See this topic to learn how to install or remove a 1U device into or from the rack side. About this task S001 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 359
DANGER Electrical current from power, telephone, and communication cables is hazardous. To avoid a shock hazard: • Connect all power cords to a properly wired and grounded electrical outlet/source. • Connect any equipment that will be attached to this product to properly wired outlets/sources. •...
Page 360
Refer to the document that comes with the device, and install the mounting brackets if necessary. Step 2. Align the mounting brackets with the holes in the rack flange, and secure it with four sets of screw and nut. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 361
Figure 397. Installing a 1U device into the rack side Remove a 1U PDU or console switch from the rack side Procedure Step 1. Remove the four screws and nuts that secure the device, and remove the device. Chapter 5 Hardware removal, installation and reversion...
Refer to the document that comes with the device, and install the mounting brackets if necessary. Step 2. Remove the side cover next to the side pocket (see “Remove a side cover” on page 197 Step 3. Install the device. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 363
Figure 399. Installing a 1U PDU or console switch Install four M6 clip nuts on the rack flanges as shown in the illustration. Slide the device all the way into the side pocket. Secure the device with four M6 screws. Step 4.
Notes: To maintain balance of the rack cabinet, do not remove the outriggers except the following situations: • when two or more rack cabinets are connected with the baying kit. • when the rack cabinet is secured to the floor with stabilizer. Procedure ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 365
Step 1. Extend each of the four leveling pads in turns until they firmly contact the floor and support the rack cabinet. Make sure the cabinet is balanced by gently pushing the cabinet. If it tilts, adjust the length of the leveling pads until the cabinet is well balanced. Figure 401.
Extend each of the four leveling pads in turns until they firmly contact the floor and support the rack cabinet. Make sure the cabinet is balanced by gently pushing the cabinet. If it tilts, adjust the length of the leveling pads until the cabinet is well balanced. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 367
Figure 404. Lowering the leveling pads Step 2. Secure each of the outriggers with four screws. Figure 405. Installing the outriggers Step 3. Install the outrigger stabilizing bars. Chapter 5 Hardware removal, installation and reversion...
See this topic to learn how to remove and install the cable management brackets. Remove a cable management bracket See this topic to learn how to remove a cable management bracket. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 369
Remove a 21U front cable management bracket Procedure Step 1. Open the front door, and release all the cables that are secured by the cable straps on the bracket. Step 2. Remove the six screws that secure the front cable management bracket, and remove the clip nuts. Figure 408.
See this topic to learn how to install cable management brackets. Install a 21U front cable management bracket Procedure Step 1. Install six clip nuts, and secure the front cable management bracket with six screws. ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Page 371
Figure 410. Installing a 21U front cable management bracket Install a rear cable management bracket Procedure Step 1. Secure the rear cable management bracket to the side pocket with four screws. Chapter 5 Hardware removal, installation and reversion...
Page 372
Figure 411. Installing a rear cable management bracket ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide...
Gathering information needed to call Support If you believe that you require warranty service for your Lenovo product, the service technicians will be able to assist you more efficiently if you prepare before you call. You can also see http:// datacentersupport.lenovo.com/warrantylookup...
Electronic Service Request. Submitting an Electronic Service Request will start the process of determining a solution to your problem by making the pertinent information available to the service technicians. The Lenovo service technicians can start working on your solution as soon as you have completed and submitted an Electronic Service Request.
Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any Lenovo intellectual property right may be used instead.