RC GROUP MP2000 User Manual page 70

Air conditioners microprocessor control
Table of Contents

Advertisement

Software per condizionatori d'aria • EPROM CZX.... • Software for air conditioners
PARAMETRI TEMPORIZZAZIONI
ON DISPLAY
Time delay switching main fan on
Time delay switching main fan off
Float. valve running time
Alarm delay time low pressure
Alarm delay time air flow
Alarm delay time oil diff.
Hi/lo temp. alarm delay time
Hi/lo humidity alarm delay time
Minimum compressor off time
Minimum compressor on time
Delay between starts same comp.
Delay between starts diff. comp.
Delay between starts two unload.
Delay between stars diff. heat.
ON DISPLAY
Do you want insert manufacturer
parameters?
ON DISPLAY
Temperature set point limits
Minimum
Maximum
Humiditiy set point limits
Minimum
Maximum
Interg. humidifier production
Local off switch enabled
Reduce humid. in cool position
Control condensing pressure
Setpoint
Differential
Control condensing pressure
(compr. off)
On (max V)
Off (min V)
Condensing output min value
Condensing output max value
Maximum pressure value
Max compensation setpoint
Reaction time
Offset room temp. high preal.
Offset room temp. low alarm
Offset room temp. high alarm
Offset room humidity low alarm
Offset room humidity high alarm
Limit thermostat enable
Threshold limit cooling
70
MP2000 AIR CONDITIONERS
Premere per 4 secondi
quindi inserire Password
TIPO DI SET
ritardo attivazione ventilatore principale
ritardo disattivazione ventilatore principale main fan off delay
tempo funzionamento valvola 3 punti
ritardo allarme bassa pressione
ritardo allarme flusso aria
ritardo allarme pressione differenziale olio differential oil pressure alarm delay 120s
ritardo allarme alta/bassa temperatura
ritardo allarme alta/bassa umidità
tempo minimo di fermo compressore
tempo minimo di funz. compressore
ritardo minimo tra gli avviamenti dello
stesso compressore
ritardo minimo tra l'avviamento di un
compressore ed il successivo
ritardo minimo per passaggio da 100%
a 50% capacità e viceversa.
(parzializzazioni o doppia velocità)
ritardo minimo tra l'attivazione di uno
stadio di riscaldamento e l'altro.
INIZIALIZZAZIONE UNITA'
Premere per 4 secondi
quindi inserire Password
TIPO DI SET
vuoi inserire i parametri "manufacturer"?
ripristino set di base
SET PROGRAMMABILI
Premere
quindi inserire Password
TIPO DI SET
limiti set point temperatura
minimo
massimo
limiti set point umidità
minimo
massimo
produzione vapore umidificatore
abilitazione tasto ON/OFF locale
riduzione umidif. con richiesta freddo
pressione controllo condensazione
valore segnale proporzionale minimo
valore segnale proporzionale massimo
pressione controllo condensazione
(compressore off)
vent. condensatore ON con compr. OFF
vent. condensatore OFF con compr. OFF cond. fan OFF with compr.OFF
valore mimino uscita condensazione
valore massimo uscita condensazione
massimo valore di pressione
massimo valore di compensazione
tempo di reazione compensazione
preallame alta temperatura ambiente
allarme bassa temperatura ambiente
allarme alta temperatura ambiente
allarme bassa umidità ambiente
allarme alta umidità ambiente
abilitazione termostato limite uscita aria
soglia limitazione raffreddamento
TIMING PARAMETERS
Press for 4 seconds
PRG
HOME
than digit Password
3
1
SET TYPE
main fan on delay
floating valve running time
low pressure alarm delay
air flow alarm delay
low/high temperature alarm delay
low/high umidity alarm delay
minimum off time compressor
minimum on time compressor
minimum delay between starts
of the same compressor
minimum delay between start of one
compressor and the next one .
minimum delay to change from 100%
to 50% capacity and viceversa.
(unloading or double speed)
minimum delay between one heating
stage activation and the next one
UNIT INITIALIZATION
Press for 4 seconds
PRG
HOME
than digit Password
1
3
SET TYPE
do you want insert manufacturer
parameters?
reset to default set
PROGRAM SETS
Press
PRG
than digit Password
3
SET TYPE
temperature set point limits
minimum
maximum
humidity set point limits
minimum
maximum
steam humidifier production
local ON/OFF switch enabled
humidif. reduction with cool request
control condensing pressure
proportional signal min. value
proportional signal max. value
control condensing pressure
(compressor off)
cond. fan ON with compr. OFF
condensing output min value
condensing output max value
max pressure value
max compensation value
compensation reaction time
high room temperature prealarm 4,5 C (offset)
low room temperature alarm
high room temperature alarm
low room humidity alarm
high room humidity alarm
outlet air limit thermostat enabling
cooling limit threshold
DEFAULT
RANGE
2s
0 600 s
10s
0 600 s
150s
0 600 s
300s
0 600 s
15s
0 600 s
0 600 s
300s
0 9999 s
1800s
0 9999 s
120s
0 600 s
60s
0 600 s
180s
0 600 s
10s
0 600 s
10s
0 600 s
5s
0 600 s
DEFAULT
RANGE
N
N - Y
DEFAULT
RANGE
10 C
0 50 C
30 C
0 50 C
35%rH
30 90 %rH
80%rH
30 90 %rH
3Kg/h
1,4 5 Kg/h
Y
N - Y
Y
N - Y
1400kPa
0 3000 kPa
300kPa
0 1000 kPa
2200kPa
0 3000 kPa
2000kPa
0 3000 kPa
3V
0 5 V
10V
5 10 V
2500kPa
0 4000 kPa
5 C
20 C
5min
2 30 min
2 20 C
xH.prealarm
4,5 C (offset)
2 20 C
5,5 C (offset)
2 20 C
14%rH (offset)
5 50 %rH
14%rH (offset)
5 50 %rH
N
N - Y
14 C
0 20 C
RC GROUP - 149_ItEn.0102
SYMBOL
SYMBOL
SYMBOL
zPs
zP
zON
zOFF
zPmin
zPmax
zH.Alarm
xL.alarm
xH.alarm
yL.alarm
yH.alarm