Ultrasonic Level Meter SLM1000 Series (USER’S MANUAL) IS Technologies Co., Ltd.
Page 2
IABILITY IS Technologies Co., Ltd. guarantees for a period of 1 year from the date of delivery that it will either exchange or repair any part of this product returned to IS Technologies Co., Ltd. if it is found to be defective in material or workmanship, subject to the defect not being due to unfair wear and tear, misuse, modification or alteration, accident, misapplication or negligence.
Chapter 2 Installation Power Supply Requirements The SLM1000 Series operate from an AC supply of 90 –260V or DC 12/24V. All electronic products are susceptible to electrostatic shock, so follow proper grounding procedures during installation. The construction of the SLM1000 Series can be mounted easily using the thread (3/4” NPT, 1”NPT). When choosing a location to mount the XDS800/1200/1500(Sensor), bear in mind the following: •...
SLM1000 SLM-1000 MODE DOWN ALARM Sondar Ultrasonic Level Meter (185) (107) Terminal Connection 25 terminals are aligned inside the terminal box. Input & Output Terminals DIGITAL...
Page 7
Function Terminal Function Note ①Sensor Connect to positive wire(red) of ultrasonic sensor ②Sensor Connect to shield wire(blue) of ultrasonic sensor ③ This terminal is used only at factory ④mA+ 4~20mA current output Maximum :600Ω ⑤mA- Current output return RS232C interface in use, connect to reception part ⑥...
Outdoor and Open Vessel Installation The XDS800/1200/1500 can be simply mounted on a bracket, suitable for the application and secured using the thread located at the top of the transducer (3/4”NPT, 1” NPT). Care should be taken to ensure that the XDS800/1200/1500 are not installed in direct sunlight, in order to avoid errors in the measurement of ambient temperature.
Chapter 3 How To Use Controller Operating the Controller Display Window SLM1000 is designed to display various data at the same time by adopting 40 letter LCD. The display below shows an example of a normal operation of SLM1200S. Conditions : The distance between the sensor and bottom of the tank : 12m Current liquid level : 10m L : 10.
Page 10
1) MODE Button : Used for setting data and moving to another mode. 2) UP Button : Used for increasing the value. 3) DOWN Button : Used for decreasing the value. 4) RUN Button : Used for starting measurement. Alarm Display 1) HH LED Lamp : Lighted in case of upper limit operated 2) H LED Lamp : Lighted in case of upper alarm operated 3)L LED Lamp : Lighted in case of lower alarm operated...
Chapter 4 Menu Guide Application Menu Option 1) Password PASSWORD IDENTITY PASSWORD : Password is needed to enter the operation mode. After setting the password using UP/DOWN button, press MODE to get into the operation mode. If the user forgets the password that he or she set, the master password is 413. 2) Measure Type MEASURE TYPE SET LEVEL...
Page 12
4) 4mA Setpoint 4mA POINT SET 4mA : 0m Factory Set = 0 This option sets the distance ( or level or space, depending on the selected Measure Type at which the 4mA output will occur. By default 4mA will represent Empty(0% of Span). 5) 20mA Setpoint 20mA POINT SET 20mA : 12.00m...
Process Menu Options 7) HH ON Point Setting HH ON POINT SET ON : 11.00m This option determines the high limit “ON” point for HH relay - Setting Range SLM800S - 0.35~8m SLM1200S - 0.5~12m SLM1500S - 0.5~15m 8) HH OFF Point Setting HH OFF POINT SET OFF : 10.00m This option determines the high limit “OFF”...
Page 14
11) L ON Point Setting L ON POINT SET ON : 2.00m This option determines the “ ON” point for L switched output - Setting Range SLM800S - 0.35~8m SLM1200S - 0.5~12m SLM1500S – 0.5~15m 12) L OFF Point Setting L OFF POINT SET OFF : 3.00m This option determines the “...
Page 15
15) Measuring Response MEASURE RESPONSE RESP : 2 This option determines the maximum rate at which the unit will respond to an increase/decrease in level. - Setting Range 1=0.1M/min (Reponse to changes to a max. 0.1m/min) 2=1M/min (Reponse to changes to a max. 1m/min) 3=10M/min (Reponse to changes to a max.
18) Fail Safe Time FAIL SAFE TIME TIME : 120 In the event of a fail-safe condition occurring (Lost of Echo) the fail safe timer determines the time before the mA output indicates a fault condition (Lost of Echo) Compensation Menu Options 19) Detection Threshold Voltage DETECTION THRESHOLD LEV : 4...
Page 17
The table below gives details of the velocity of sound in various gaseous atmospheres In all cases the velocity indicated is that in a 100% gaseous atmosphere at 0 C. In atmospheres less than 100% it may be necessary to check the level indicated at near empty and near full and compare with the actual level, several times, then adjust the Sound Velocity accordingly to obtain an accurately displayed reading.
Page 18
24) Material Temperature Weighting MATERIAL T WEIGHTING WET : 0% This option is used in conjunction with Mode 23, Material Temperature. This option determines the effect the material temperature has on the air temperature in front of the transducer. Where the temperature of the material has no effect on the air temperature.
Chapter 5 Digital Communication The SLM1000 Series provides RS232/485 digital communication interface function as option The kinds of data and its format are as follows; Output Data 1. Kinds of Output Data 1) Distance Data Distance from the sensor to the surface of measuring material. Unit is mm 2) Temperature Data This is temperature data measured by built-in temperature sensor.
Chapter 6 Troubleshooting This section describes some problem symptoms, with suggestions as to what to do. Symptom What to Do Display blank, transducer not Check power supply firing. Display shows “S”, “ ERROR! “S” means there is an abrupt liquid change or an obstacle in the LOST ECHO”...