Table 14. Environmental and Safety
Operating Temperature
Transit/Storage
Temperature
Relative Humidity
Operating Altitude
Audible Noise
Fan Speed
Surge Suppression
Safety Conformance
Agency Markings
EMC
100/120V Models
Up to 1,500 meters: 0°C to 40°C (32°F to 104°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Up to 3,048 meters (0–10,000 ft) above sea level
Normal mode: less than 40 dBA typical
Battery mode: less than 50 dBA typical
Off: when the UPS is in Standby mode or there is no load
Low speed: when the load is < 80%
High speed: when the load is >80% or the UPS is in Battery mode
ANSI/IEEE C62.41; 2002 Category B
UL 1778 4th Edition
CSA C22.2, No. 107.3
UL, cUL, NOM/NYCE
FCC, VCCI, ICES-003,
BSMI
208V Models
-15°C to 60°C (5°F to 140°F)
0–95% noncondensing
UL, cUL
FCC, VCCI
230V Models
UL 1778 4th Edition;
CSA C22.2, No. 107.3;
IEC/EN 62040-1-1;
IEC/EN 60950-1
UL, cUL, CE, GS, GOST,
BSMI, S-MARK, KC,
CQC, NRCS, SIRIM
CE, BSMI, CQC, C-tick