Dell 1000W User Manual page 47

Line-interactive rack ups 1000w, 1920/1500w, and 2700/2300w
Hide thumbs Also See for 1000W:
Table of Contents

Advertisement

Table 7. Settings (continued)
Description
Set Date and Time
Control Commands from Serial
Port
Output Voltage
Output Frequency
Overload Alarm Level
Automatic Start Delay
Automatic on Battery Shutdown
Start on Battery
Available Settings
Set Month, Day, Year, Hours, Minutes, and Seconds
Date:mm/dd/yyyy
Time: hh:mm:ss
The date format is dependent on the
NOTE:
language selection.
Time is a 24-hour clock.
NOTE:
[Enabled] [Disabled]
If Enabled, control commands are accepted through
the serial port, USB ports, or option card.
If Disabled, configuration and load control
commands are restricted to LCD only.
[100V] [110V] [120V] [Auto-sensing]
[200V] [208V]
[220V] [230V] [240V]
[50Hz] [60Hz] [Auto-sensing]
[10%] [20%] [30%]...[100%]
If 100%, the UPS issues an Output Overload alarm
at load > 100%.
Output Overload Level 1 by default is set to
NOTE:
100% and is configurable from 10% to 100% in 10%
increments through the LCD setting menu. This
allows customers to be alerted before the UPS has
reached its rated capacity limits.
[Off] [0s] [1s] [2s]...[32767s]
See "Configuring Load Segments" on page 51.
[Off] [0s] [1s] [2s]...[32767s]
See "Configuring Load Segments" on page 51.
[Enabled] [Disabled]
Battery start is disabled from the factory and
NOTE:
remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. After this is
set by the user, it remains set.
Default Setting
01/01/2009
12:00:00
Enabled
Auto-sensing
Auto-sensing
100%
0s
Off
Enabled
47
|