When to Replace Batteries

When the status summary screen displays the UPS fault icon with the "Service Battery" alarm and the
audible alarm sounds continuously, the batteries may need replacing. Contact your service
representative to order new batteries.
NOTE:
With the user-replaceable battery feature, UPS batteries can be replaced easily without turning the UPS
off or disconnecting the load.

Testing Batteries

For a battery test to run:
S The batteries must be fully charged.
S The UPS must be in Normal mode with no active alarms.
S The load must be higher than 10%.
To test the batteries:
1
Plug the UPS into a power outlet for at least 48 hours to charge the batteries.
2
Press the
button for one second to go to the main menu selection and scroll down to the
Control menu using the
3
Press the
button to enter the Control menu.
4
Use the
button to scroll to the Battery Test option.
5
Press the
button to start the battery test.
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25% of
the original expected runtime. The front panel displays "Battery test running" and the percentage
of the test completed. The results display on the UPS front panel when complete.