CTC Union SSB2000 Series Product Manual
CTC Union SSB2000 Series Product Manual

CTC Union SSB2000 Series Product Manual

Modular switch box 12 sensor inputs

Advertisement

Quick Links

SSB2000 Series Modular Switch Box
SSB2000 Series Modular Switch Box
12 Sensor Inputs
12 Sensor Inputs
Product Manual
Product Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SSB2000 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CTC Union SSB2000 Series

  • Page 1 SSB2000 Series Modular Switch Box SSB2000 Series Modular Switch Box 12 Sensor Inputs 12 Sensor Inputs Product Manual Product Manual...
  • Page 2: Table Of Contents

    Table of Contents • Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 •...
  • Page 3: Introduction

    . SSB2000 Series Modular Switch Box Overview: Four to 12 sensor inputs (four to 12 measurement channel outputs), stainless steel enclosure CTC modular switch box solutions allow for the monitoring of remotely-mounted vibration sensors, which would otherwise be restricted to human access due to safety considerations .
  • Page 4: Product Dimensions And Diagram

    Product Dimensions Side View Rear View Figure 1. Dimensions Two-pin MIL Output Connector Measurement Location Card BNC Output Connector Switch Figure 2. Diagram...
  • Page 5: Mounting Instructions

    Mounting Instructions Note: If you have purchased a modular switch box without cable entries provided, you should add your own entry prior to mounting the modular switch box . CTC does not recommend drilling holes in the top of the enclosure due to access and moisture concerns .
  • Page 6: Conduit Entry

    Conduit Entry If you are running conduit to your enclosure, ensure the conduit cable entry is located at the bottom of the enclosure when mounted . Note: To ensure moisture will not flow into the enclosure, a hole should be drilled at the lowest point in the conduit to provide drainage for any moisture .
  • Page 7: Grounding

    Grounding Ensure the shield ground wire on the SSB2000 Series modular switch box is grounded to earth ground . A. Mounting to Earth Ground When mounting SSB2000 Series modular switch boxes to earth ground (such as an I-Beam), no additional steps are necessary, as the enclosure is grounded internally .
  • Page 8: Sensor Installation

    B. Mounting to Non-Grounded Structure When mounting the modular switch box to a non-grounded structure, ensure the shield ground wire or customer-supplied ground wire is tied to a source of earth ground . Figure 6. Ground Wire Placement Sensor Installation Installation of Sensors/Signal Input Cable Feed blunt-cut end through the cable entry at the bottom of the enclosure .
  • Page 9 Figure 8. Bottom View Figure 7. Front View Strip outer jacket of cable back 1¼ in . and remove all of the shielding . Separate the internal wires from the shield and twist the shield . Strip red and black insulation back ¼ in . Shield / Drain Wire Figure 9.
  • Page 10 Inputs Inputs Inputs Inputs ENSIONS E SHEET Sensor Inputs Red = Signal/Power (+) Sensor Inputs Black = Common (-) Red = Signal/Power (+) Grey = Shield (Ground) Black = Common (-) Grey = Shield (Ground) Figure 10. Connecting Cables to Modular Switch Box (SSB2000) Inputs Inputs Inputs...
  • Page 11: Post-Installation Testing

    Post-Installation Testing The TM1018 Accelerometer Verification Meter can be used to verify cable conductivity, sensor location and proper wiring connections . The Verification Meter will indicate if the sensor, cable and/or junction box is in working condition . It will also confirm bias voltage of the accelerometer, which will inform you of the operation of the internal accelerometer amplifier .
  • Page 12: Contact Information

    The following LED Readout indicates the circuit integrity: Green LED: Normal . Indicates proper connection and an output bias will be given, indicating the health of the sensor (4 – 16 V indicates a healthy accelerometer) . Yellow LED: Open Circuit . Indicates one of the following: a .