Page 2
(NO) or normally closed (NC) contacts and report their status as a multiplex address to the control system. Up to 60 DS7465i Modules can be used on the DS7400Xi. Use up to 20 DS7465i Modules per bus on compatible fire alarm control panels (FACPs).
Page 3
DS7465i Fire applications require NO contacts on DS7436 the input zone. Connect wiring to the DS7465i as shown in Figure 3 through Figure 5. The input loop is designed to monitor NO or NC dry contacts. It is supervised using a 47 kΩ...
Page 4
4.0 Switch Settings Table 2: DS7465i Switch Settings When Using Configure the address switch settings before the DS7430 and DS7436 MUX connecting the DS7465i to the multiplex bus. Refer to Expansion Module Figure 6 Switch Number Do not set any two DS7465i Dual Zone Address •...