250: 250,000 Btu/hr H: Horizontal and Not Convertible N: Horizontal and Convertible Product Series R: Vertical and Convertible H: H series V: Vertical and Not Convertible Controller Type and Evaporator Fin Type H: With Controller, Hydrophilic Blue B: Without Controller, Hydrophilic Blue No.
Refrigerant R: Vertical and Convertible 5: R410A Condenser Fin Type Product Type D: Microchannel F: Epoxy-coating Microchannel MC: Modular Condensing Unit Market Capacity I: Indonesia 125: 125,000 Btu/hr Power Supply Product Series F: 3 Phase 50Hz 380-415V H: H series...
Application Information Application Information Operating Range Ensure the operating temperature is in allowance range. Cooling Outdoor DB (°C) The use of your air conditioner outside the range of working temperature and humidity can result in serious failure. Indoor WB (°C) Cooling Operation Range DB: Dry Bulb WB: Wet Bulb...
Application Information Installation Guideline INDOOR PRELIMINARY SITE SURVEY a) Electrical supply and installation is to conform to local authority’s (e.g. National Electricity Board) codes and regulations. b) Voltage supply fl uctuation must not exceed +/- 10% of rated voltage. Electricity supply line must be independent of welding transformers which can cause supply fl...
Page 12
Application Information INDOOR CLEARANCE Mounting Ensure that the overhead supports are strong enough to hold the unit’s weight. Position hanger rods and check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level in the two horizontal directions, taking into account the gradient recommended for drainage fl...
Page 13
Application Information OUTDOOR LOCATION FOR INSTALLATION OF THE CONDENSING UNITS As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum cooling capacity, the location selected should fulfi ll the following requirements:- a) Install the condensing (outdoor) unit in a way such that hot air distributed by the outdoor condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air).
Page 14
Application Information OUTDOOR CLEARANCE SINGLE UNIT PATTERN 1 PATTERN 2 1200 TOP VIEW TOP VIEW M5MC80H SERVICE PANEL PATTERN 1 PATTERN 2 PATTERN 1 PATTERN 2 1500 AIR DISCHARGE DIRECTION TOP VIEW TOP VIEW TOP VIEW TOP VIEW WALL / CEILING PATTERN 3 <1500 AIR DISCHARGE GRILL...
Page 15
Application Information Cable Size Cooling only M5DB80H M5DB100H M5DB125H Model Unit M5MC80H M5MC100H M5MC125H Indoor 380 - 415V / 3Ph /50Hz + N + Voltage range** Outdoor 380 - 415V / 3Ph /50Hz + N + Power supply cable size* a) Indoor Unit b) Outdoor Unit c) Total...
Page 16
Application Information M5DB300H2 M5DB300H3 M5DB350H3 Model Unit M5MC150H M5MC100H M5MC125H M5MC100H Indoor 380 - 415V / 3Ph /50Hz + N + Voltage range** Outdoor 380 - 415V / 3Ph /50Hz + N + Power supply cable size* a) Indoor Unit b) Outdoor Unit c) Total 16.0...
Page 17
Application Information M5DB600H4 M5DB750H5 Model Unit M5MC150H x 4 M5MC150H x 5 Indoor 380 - 415V / 3Ph /50Hz + N + Voltage range** Outdoor 380 - 415V / 3Ph /50Hz + N + Power supply cable size* a) Indoor Unit b) Outdoor Unit c) Total 35.0...
Page 18
Application Information REFRIGERANT PIPING Maximum Piping Length and Maximum Number of Bends When the pipe length becomes too long, both the capacity and reliability will drop and as the number of bends increases, system piping resistance to the refrigerant fl ow increases, thus lowering the cooling capacity.
Sound Data Sound Data Sound Pressure Level Indoor 1/1 Octave Sound Pressure (dB, ref 20μPa) Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High M5DB80H High M5DB100H M5DB125H High M5DB150H High M5DB200H2 High M5DB250H2 High M5DB300H2/H3 High M5DB350H3...
Sound Data Indoor Model Measuring Location M5DB250H2 M5DB300H2/H3 M5DB350H3 M5DB400H4 UNIT M5DB450H3 M5DB500H4 M5DB600H4 M5DB750H5 2m discharge duct length Free return duct Microphone position: 1m away from every side panel of the unit and 1m above the fl oor level. (Tested with 2m length duct at the air discharge outlet only) Standard: JIS B 8615 Sound Power Level...
Selection Process Selection Process Fan Performance Chart Example 1 : The following are the design requirements for A5DB250H2 unit: Model: M5DB250H2 Supply Air Quantity 9000 External Static Pressure Step 1: From the fan curve (at 9000 CFM), Standard operating system; Total Static Pressure Internal Static Pressure External Static Pressure...
Page 29
Selection Process The following table summarizes the pulley data, motor size used for the M5DB-H series, as manufactured: Pulley Centre Distance, C Motor Motor Model (kW) Horizontal (mm) Vertical (mm) M5DB125H 1500 M5DB150H 1500 M5DB200H2 1420 M5DB250H2 1440 M5DB300H2/H3 1440...
Page 30
Selection Process Example 1: M5DB250H2 Blower Curve 5.5 kW 4.0 kW Selected Point 3.0 kW Standard Point Internal Static Pressure with filter Internal Static Pressure w/o filter 6000 6500 7000 7500 8000 8500 9000 9000 4250 2830 3300 3100 3700 4100 Air Flow...
Page 31
Selection Process FAN PERFORMANCE CURVE M5DB80H (with filter) MEDIUM SUPER HIGH SUPER HIGH HIGH 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 1040 1180 1320 Air Flow...
Page 32
Selection Process M5DB80H (without filter) HIGH MEDIUM SUPER HIGH 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 1040 1180 1320 Air Flow...
Page 33
Selection Process M5DB100H (with filter) MEDIUM HIGH 2000 2200 2400 2600 2800 3000 3200 3400 3600 1570 1320 1450 1700 1080 1210 Air Flow...
Page 34
Selection Process M5DB100H (without filter) MEDIUM HIGH 2000 2200 2400 2600 2800 3000 3200 3400 3600 1570 1700 1210 1320 1450 1080 Air Flow...
Engineering & Physical Data Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT M5DB80H M5DB100H M5DB125H M5DB150H MODEL OUTDOOR UNIT M5MC80H M5MC100H M5MC125H M5MC150H Btu/h 80,000 100,000 125,000 150,000 NOMINAL COOLING CAPACITY 23,400 29,300 36,600 44,000 NOMINAL TOTAL INPUT POWER (COOLING) 7,100 10,000 11,350...
Page 47
Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT M5DB200H2 M5DB250H2 M5DB300H2 M5DB300H3 MODEL OUTDOOR UNIT M5MC100H x 2 M5MC125H x 2 M5MC150H x 2 M5MC100H x 3 Btu/h 200,000 250,000 300,000 300,000 NOMINAL COOLING CAPACITY 58,600 73,200 88,000 88,000...
Page 48
Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT M5DB350H3 M5DB400H4 M5DB450H3 MODEL OUTDOOR UNIT M5MC100H M5MC125H x 2 M5MC100H x 4 M5MC150H x 3 Btu/h 350,000 400,000 450,000 NOMINAL COOLING CAPACITY 102,500 117,200 131,900 NOMINAL TOTAL INPUT POWER (COOLING) 34,550 39,330 45,930...
Page 49
Engineering & Physical Data Engineering Data – R410A COOLING MODEL INDOOR UNIT M5DB500H4 M5DB600H4 M5DB750H5 MODEL OUTDOOR UNIT M5MC125H x 4 M5MC150H x 4 M5MC150H x 5 Btu/h 500,000 600,000 750,000 NOMINAL COOLING CAPACITY 146,500 175,850 219,900 NOMINAL TOTAL INPUT POWER (COOLING) 49,990 61,620 78,640...
Performance Data Performance Data Calculation Steps Interpolation method can be used to get the total Solution: cooling capacity, TC and sensible cooling capacity, Based on the Performance Table, SC and power input, PI at those temperatures which 1. Refer to the Indoor DB column, are not stated out in the table.
Page 51
Performance Data (b) Indoor Condition: 25°C DB, 16°C WB By Interpolation Method Outdoor Condition: 35°C DB 25°C – 24°C – 29.18kW Outdoor temperature 27°C – 24°C 29.30kW – 29.18kW 35°C x = 29.22kW Similarly, = 19.11kW 29.18 18.11 9.99 = 9.99kW 29.30...
Outlines & Dimensions Outlines & Dimensions Indoor Unit Model: M5DB80H/100H Note: Dimension in mm Model / Dimension 80H/100H 1502 1402 1462 Model / Dimension 80H/100H 1242 Model / Dimension 80/H100H Model / Dimension 80H/100H...
Page 67
Outlines & Dimensions Model: M5DB125H/150H (Vertical Discharge) Note: Dimension in mm Model / Dimension 125H/150H 1640 1540 1600 Model / Dimension 125H/150H 1377 Model / Dimension 125H/150H Model / Dimension 125H/150H...
Page 68
Outlines & Dimensions Model: M5DB125H/150H (Horizontal Discharge) Note: Dimension in mm Model / Dimension 125H/150H 1640 1040 1540 1600 Model / Dimension 125H/150H 1377 Model / Dimension 125H/150H Model / Dimension 125H/150H...
Page 69
Outlines & Dimensions Model: M5DB200H2 (Vertical Discharge) Note: Dimension in mm Model / Dimension 200H2 1794 1624 1854 1894 47.7 754.6 Model / Dimension 200H2 Model / Dimension 200H2...
Page 70
Outlines & Dimensions Model: M5DB200H2 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 200H2 1794 1624 1854 1894 47.7 754.6 Model / Dimension 200H2 Model / Dimension 200H2 1040...
Page 71
Outlines & Dimensions Model: M5DB250H2/300H2 (Vertical Discharge) Note: Dimension in mm Model / Dimension 250H2 1766 1636 1826 1866 300H2 1766 1636 1826 1866 Model / Dimension 250H2 1291 300H2 1291 Model / Dimension 250H2 1199 1069 1196 1073 300H2 1199 1069 1196...
Page 72
Outlines & Dimensions Model: M5DB250H2/300H2 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 250H2 1766 1636 1826 1866 300H2 1766 1636 1826 1866 Model / Dimension 250H2 1291 300H2 1291 Model / Dimension 250H2 1199 1069 1196 1073 300H2 1199 1069 1196...
Page 73
Outlines & Dimensions Model: M5DB300H3 (Vertical Discharge) Note: Dimension in mm Model / Dimension 300H3 1766 1636 1826 1866 Model / Dimension 300H3 1291 Model / Dimension 300H3 1199 1069 1196 1073 Model / Dimension 300H3...
Page 74
Outlines & Dimensions Model: M5DB300H3 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 300H3 1766 1636 1826 1866 Model / Dimension 300H3 1291 Model / Dimension 300H3 1199 1069 1196 1073 Model / Dimension 300H3...
Page 75
Outlines & Dimensions Model: M5DB350H3 (Vertical Discharge) Note: Dimension in mm Model / Dimension 350H3 2022 1852 2082 2122 Model / Dimension 350H3 1546 Model / Dimension 350H3 1199 1069 1451 1326 Model / Dimension 350H3...
Page 76
Outlines & Dimensions Model: M5DB350H3 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 350H3 2022 1852 2082 2122 Model / Dimension 350H3 1546 Model / Dimension 350H3 1199 1069 1451 1326 Model / Dimension 350H3...
Page 77
Outlines & Dimensions Model: M5DB400H4 (Vertical Discharge) Note: Dimension in mm Model / Dimension 400H4 2174 2004 2234 2274 1240 Model / Dimension 400H4 1546 Model / Dimension 400H4 1466 1336 1451 1326 Model / Dimension 400H4 96.5 266.5...
Page 78
Outlines & Dimensions Model: M5DB400H4 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 400H4 2174 2004 2234 2274 1240 Model / Dimension 400H4 1546 Model / Dimension 400H4 1466 1336 1451 1326 Model / Dimension 400H4 96.5 266.5...
Page 79
Outlines & Dimensions Model: M5DB450H3 (Vertical Discharge) Note: Dimension in mm Model / Dimension 450H3 2174 2004 2234 2274 1240 Model / Dimension 450H3 1546 Model / Dimension 450H3 1466 1336 1451 1326 Model / Dimension 450H3...
Page 80
Outlines & Dimensions Model: M5DB450H3 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 450H3 2174 2004 2234 2274 1240 Model / Dimension 450H3 1546 Model / Dimension 450H3 1466 1336 1451 1326 Model / Dimension 450H3...
Page 81
Outlines & Dimensions Model: M5DB500H4 (Vertical Discharge) Note: Dimension in mm Model / Dimension 500H4 2174 2004 2234 2274 1240 Model / Dimension 500H4 1546 Model / Dimension 500H4 1466 1336 1451 1326 Model / Dimension 500H4...
Page 82
Outlines & Dimensions Model: M5DB500H4 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 500H4 2174 2004 2234 2274 1240 Model / Dimension 500H4 1546 Model / Dimension 500H4 1466 1336 1451 1326 Model / Dimension 500H4...
Page 83
Outlines & Dimensions Model: M5DB600H4 (Vertical Discharge) Note: Dimension in mm Model / Dimension 600H4 2234 2004 2174 1680 Model / Dimension 600H4 1978 1883 1905 1775 Model / Dimension 600H4 1758 315.5 Model / Dimension 600H4 145.5...
Page 84
Outlines & Dimensions Model: M5DB600H4 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 600H4 2234 2004 2174 1680 Model / Dimension 600H4 1918 1883 1905 1775 Model / Dimension 600H4 1758 315.5 Model / Dimension 600H4 145.5...
Page 85
Outlines & Dimensions Model: M5DB750H5 (Vertical Discharge) Note: Dimension in mm Model / Dimension 750H5 2234 2004 2174 1680 Model / Dimension 750H5 2257 2162 1905 1775 Model / Dimension 750H5 2037 Model / Dimension 750H5...
Page 86
Outlines & Dimensions Model: M5DB750H5 (Horizontal Discharge) Note: Dimension in mm Model / Dimension 750H5 2234 2004 2174 1680 Model / Dimension 750H5 2197 2162 1905 1775 Model / Dimension 750H5 2037 Model / Dimension 750H5 Note: A5DB80-100H models are available in Horizontal Air Discharge as Standard. Not Convertible. A5DB125-200H models are available in Horizontal Air Discharge as Standard.
Service & Maintenance Service & Maintenance The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit. Upon removal of front and side panel, all the electrical “terminal box”, fan and motor assembly and compressor are easily accessible.
Service & Maintenance MAINTENANCE For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance. Cleaning The Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will become dirty impairing its function and reducing the performance of the air conditioned.
Troubleshooting Troubleshooting When a malfunction of the air conditioner unit is detected, immediately switch off the main power supply before proceeding with the following troubleshooting procedures. The following are common fault conditions and simple troubleshooting tips. If any other fault conditions which are not listed occur, contact your nearest local dealer.
Troubleshooting Error Code Wired Handset : SLM9 When the system is on and an error occurs, the seven segments LED will blink an error code. Each error code blinking represents different message as below: Error Seven Segments Room Sensor missing / Short E1 blinking Indoor coil sensor missing / Short E2 blinking...
Page 99
Troubleshooting Phase Sequencer The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase protector) is fi tted to prevent incorrect wiring of the electrical phases. When the three phases are not connected correctly, the phase protector operates, and the unit will not start. This device is located in the control box of the outdoor unit.