CAUTION: DO NOT JOIN BATTERY CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC
POWER IS SUPPLIED TO THE EMERGENCY INVERTER.
CAUTION: RISK OF SHOCK-disconnect emergency and normal input power sources before servicing.
ASSEMBLY and FIELD INSTALLATION WIRING: WARNING: AC power must be off before proceeding with assembly or installation of
emergency driver.
IMPORTANT: An unswitched AC power source is required (100-347 VAC, 50/60 Hz).
IMPORTANT: Customers are advised to charge emergency LED driver 24 hours every 6 months during storage
For IHB-EM-DVR-40W-XX suggested to use for LED lamp less than 300W (when dimming to minimum the power
IMPORTANT:
needs to be less than 35W)
IMPORTANT: Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and any local
regulations.
CAUTION: To reduce the risk of electric shock disconnect both normal and emergency sources within this unit before servicing any
equipment connected to this unit
CAUTION: Do not mount near gas or electric heaters.
CAUTION: Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized
personnel.
CAUTION: The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
CAUTION: Do not use this equipment for other than its intended use.
CAUTION: Use with grounded, UL Listed, dry or damp location rated fixtures. Case should also be grounded.
CAUTION: This product is for use in indoor fixtures only. Do NOT use near heated air handling outlets or hazardous locations.
Suitable for use in 5°C -50°C ambient temperatures. Max. mounting height: 48.65ft.
CAUTION: Battery is rechargeable Li-ion type and must be recycled or disposed of properly
Do not use this emergency driver with accessory equipment other than recommended by the manufacturer.
Failure to follow this may cause an unsafe condition and will void warranty.
Servicing of this equipment should be performed by qualified personnel only
IMPORTANT: Illuminated Indicator (LED light) means battery is in charge mode when AC power is applied.
It is recommended and required by applicable code to test emergency function to ensure proper operation of
the system; press the remote controller ON button every 30 days to ensure the emergency driver is functioning and LED light source is
illuminated. Conduct a ninety minute (90) discharge test one time (1) per year;
LED light source should be illuminated for a minimum of ninety minutes (90).
TESTING SYSTEM: The emergency battery requires a minimum charge of one (1) hour before testing the circuit.
A full charge requires twenty four(24) hours.
4/18/2024
page
1
www.lightolier.com
This device is designed for fixtures listed for dry, damp or wet locations.
LED High Bay
Emergency Battery
IHB-EM-DVR-40W-XX