Sounder Strobe is a kind of optical and visual alarm device used to warn people in field when fire occurs. I-9401N addressable sounder strobe can be started directly by fire alarm control panel. It can be electronically programmed and modified by P-9910 Hand Held Programmer in field.
10. IP Rating: IP43 11. Material and Color of Enclosure: ABS/ ivory white, front inlaid with plexiglass/red 12. Weight:I-9401N:about 255g(with base) 13. Hole Distance: 65mm IV Structure and Operation Principle Structure of the sounder strobe is shown in Fig. 1.
Fig. 2 Mounting The base box of I-9401N is shown in Fig. 3, please note direction when installing. Fig. 3 I-9401N Base box Terminals: D1, D2: Connecting DC24V power, non-polarized; Z1, Z2: Connecting signal loop of the control panel, non-polarized;...
put into operation. Before testing, notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to avoid unwanted alarms. Testing: Providing close signal to the outer control contact by manual call point, the sounder strobe is activated and gives audio and visual alarm;...
Page 7
TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND SECURITY RELATED PRODUCTS. For more information on warranty disclaimers and product safety information, please check https://firesecurityproducts.com/policy/product-warning/ or scan the following code: Page 5...
Page 8
Gulf Security Technology Co., Ltd. No. 80, Changjiang East Road, ETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502434 service.gst@carrier.com www.gst.com.cn 30312588...