USER MANUAL
SPIROVENT
SUPERIOR S600
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUPERIOR S600 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Spirotech SUPERIOR S600

  • Page 1 USER MANUAL SPIROVENT SUPERIOR S600 ®...
  • Page 2 Copyright © All rights reserved. No part of this manual may be duplicated and/or made public through the Internet, by means of printing, photocopying, microfilm or in any other way without prior written permission from Spirotech.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Introduction ........................5 1.1. About the device ..........................5 1.2. About this document ........................... 6 1.3. Scope of delivery ..........................6 1.4. Symbols .............................. 6 Safety instructions ......................7 Description ........................8 3.1. Overview of the unit ..........................8 3.2.
  • Page 4 Maintenance ......................... 26 8.1. Maintenance instructions ........................26 8.2. Maintenance schedule ........................26 Troubleshooting ......................27 9.1. Remedy failures ..........................27 9.2. Function code table .......................... 27 9.3. Troubleshooting table ........................28 9.4. Instructions ............................30 Spare parts ........................31 Guarantee ........................
  • Page 5: Introduction

    1. INTRODUCTION 1.1. About the device This user manual describes the installation, commissioning and operation of the following SpiroVent Superior types: S600 MV06A.. S600-R MV06R.. S600-B MV06B.. S600-I MV06A..I S600-RI MV06R..I S600-BI MV06B..I S600-L MV06AL.. S600-RL MV06RL.. S600-BL MV06BL.. S600-LI MV06AL..I S600-RLI MV06RL..I...
  • Page 6: About This Document

    1.2. About this document Read the instructions before installation, commissioning and operation. Keep the instructions for future reference. The original language of the document is English. All other available language versions are translations of the original instructions. The illustrations in this document show a typical setup with relevant details for instructional use only.
  • Page 7: Safety Instructions

    2. SAFETY INSTRUCTIONS Refer to the safety instructions document for the safety instructions and other safety information. Read these safety instructions prior to installation. This document is available on the website and can be opened by scanning the QR-code below. The installation and operation of the unit must be in compliance with the local safety and health regulations and accepted codes of good practice.
  • Page 8: Description

    3. DESCRIPTION 3.1. Overview of the unit S600-B(L) S600(-L) S600-R(L) Power cable connector 11. Solenoid valve 21. Outlet connection Control unit - Power box 12. Pressure sensor 22. Refill connection SmartSwitch 13. Y-filter 23. Solenoid valve refill Automatic air vent 14.
  • Page 9: Working Principle

    3.2. Working principle The figure below schematically shows the operation of the unit. The number indications correspond with the main figure on the previous page. S S 600(-L) S S 600-B(L) S S 600-R(L)
  • Page 10: Operation

    3.3.4. Operating conditions 3.3. Operation 3.3.1. General The unit is suitable for use in systems filled with clean water or mixtures of water and glycol up to 40%. The SpiroVent Superior is a fully automatic vacuum Operation in combination with other fluids may result in degasser for heating and cooling installations, filled with irreparable damage.
  • Page 11: Type Plate

    3.5. Type plate The type plate of the device can be found on the side of the product, which is demonstrated in the figure below. SPIROVENT SUPERIOR  Article No: Type:  Max. Power input:   Voltage/Frequency: UL50E:  Pressure PS: ...
  • Page 12: Technical Specifications

    4. TECHNICAL SPECIFICATIONS 4.1. General specifications ITEM S600(-L) S600-R(L) S600-B(L) Empty weight [lbs] Noise level [dBA], at 1 m Fluid connections inlet/ Swivel G¾" female Swivel G¾" female Swivel G¾" female outlet NPT adapter" NPT adapter NPT adapter Swivel G¾" female Swivel G¾"...
  • Page 13: Internet Specifications

    4.4. Internet specifications ITEM ALL TYPES RJ45; Cat 5e WLAN 802.11 B/G/N 4.5. Dimensions HEIGHT WIDTH DEPTH 40" 26 ½" 15" 15" 26 ½"...
  • Page 14: Installation

    5. INSTALLATION 5.1. Installation conditions • Read all instructions before using the appliance • Do not use outdoor • Unplug the power cable when the appliance is not in use and before servicing or cleaning. • For a grounded appliance - connect to a properly grounded outlet only.
  • Page 15 Remove the packaging. 5. Remove the fasteners. Keep them for future use. Remove the brackets. Keep them for future use. 3. Remove the fasteners (A). 4. Remove the cover (B) from the unit.
  • Page 16: Mounting

    5.4. Mechanical installation ≥20” 7. Move the unit to its location of installation. Lift the unit with a hoist. Make two branch lines ¾” (A) on the side of the main 5.3. Mounting line. The distance between them should be at least 20".
  • Page 17: Electrical Installation

    Connect the line (A) to the flexible outlet line (D). into an appropriate outlet that is properly installed Connect the line (B) to the flexible inlet line (C). and grounded in accordance with all local codes and ordinances. Only applicable to units with direct refill connections (-R(L) versions): Improper connection of the equipment- grounding conductor can result in a risk of...
  • Page 18 2. For internet connection, connect the LAN cable to the LAN connector (A). 3. For Modbus settings, please go to the installer settings. Access code is 5705BK. Make sure that the LAN cable does not touch warm parts.
  • Page 19: Commissioning

    6. COMMISSIONING 6.1. Filling the unit 3. Open the deaeration valve (A) to deaerate the pump. 1. Open the valve (C) behind the pressure gauge (D). 2. Open system valves (A and B). 4. For units of -R(L) and -B(L) versions: Open the shutoff valve (A) in the refill line.
  • Page 20 Automatic Commissioning Procedure operating pressure. The Automatic Commissioning Procedure will guide you 3. For units of -R(L) and -B(L) versions: Drag the label through the startup via several screens. of the refill pressure (C) to the desired refill pressure. The Automatic Commissioning consists of several steps: 1.
  • Page 21: Check The Operation When The Functional Test Was Aborted

    The functional test only starts if the unit meets 6. Check the indication of the pressure gauge (A). the following conditions: This should alternately display overpressure and • The deaeration tank is filled with system underpressure. fluid. • The measured pressure is above the The SmartSwitch will automatically turn minimum pressure (11.6 PSI).
  • Page 22: Operation

    7. OPERATION 7.1. User interface description BUTTON/INDICATOR DESCRIPTION Next page button This section shows an overview of the content on the display. System connection indi- cator Wi-Fi indicator Standby System pressure: xxx PSI Error indicator Warning indicator Radio button (not select- Radio button (selected) Action button (available) Degass start...
  • Page 23: Overview Of The Pages

    The refill process always has priority - Counters over the degassing process. As soon as system pressure drops below the “refill Software upgrade Only accessible for Spirotech pressure”, the refill process will start. Network Shows the type of network...
  • Page 24: User Settings

    7.3.3. Refill 7.4. User settings GENERAL SETTINGS The refill process is automatically controlled by the pressure limits as defined under settings. Available PARAMETER DESCRIPTION in the direct refill version -R(L) or the break tank refill Language The language of the display texts. version -B(L).
  • Page 25: Navigate & Control

    Refill pressure The preferred system DEGASSING SETTINGS pressure at which the PARAMETER DESCRIPTION refilling starts. Set this Auto degass time 1 Time setting for daily start value as low as possible time and stop time of the when the refilling is degassing process.
  • Page 26: Maintenance

    8. MAINTENANCE 8.1. Maintenance instructions 1. Make sure to complete preventive maintenance within the time frames described in the maintenance schedule. 2. During maintenance, always check the user interface for warnings or errors and visually check for damages and leakages. 3.
  • Page 27: Troubleshooting

    9. TROUBLESHOOTING 9.1. Remedy failures 1. ‘Use the troubleshooting table in § 9.3’ to find the cause. 2. If necessary, take the unit out of operation. In case of a failure always warn the installer. Refer to §9.4.2. Remove the power and pressure from the unit 3.
  • Page 28: Troubleshooting Table

    9.3. Troubleshooting table In case the Superior continues to run only 10 minutes per event, please check the The number indications correspond with the main SmartSwitch hose connection. figures in § 3.1 and § 3.2. An overview of the replacement parts has been included in Chapter 10. Faults and warnings are indicated on the display of the unit as Exx or Wxx, where xx designates a problem (abnormal behaviour).
  • Page 29 GENERAL - ALL TYPES PROBLEM POSSIBLE CAUSE CORRECTION The inlet valve is closed Open the valve. Pressure drop inlet too high The inlet is (partly) blocked Remove the obstruction. The Y-filter (13) is clogged Clean the Y-filter element. W33 / E33 The outlet valve is closed Open the valve.
  • Page 30: Instructions

    9.4. Instructions 9.4.1. Replace a fuse 1. If the unit is switched on, select the on/off button on the display and select “turn off” to stop the unit. 2. TDisconnect the unit from the electricity network. 3. Close the valve (A) of the inlet line and the valve (B) •...
  • Page 31: Spare Parts

    10. SPARE PARTS The number indications correspond with the main figures in § 3.1. MAIN ITEM SPARE PART ARTICLE NUMBER Pump Pump, 50Hz R15.328 Pump, 60Hz R75.648 Capacitor, 50Hz R15.789 Capacitor, 60Hz R76.176 Seal set R15.731 Frame and cover Cover S600 R73.255 Control unit Power box (HV)
  • Page 32 Miscellaneous O-ring EPDM 17 x 1.5 R61.537 O-ring EPDM Ø33 x 2 Gasket 3/8” R61.538 Gasket 3/4” Gasket 1/2”...
  • Page 33: Guarantee

    11. GUARANTEE Terms of guarantee • The guarantee for these Spirotech Superior products is valid until 2 years following the purchasing date. • The guarantee lapses in cases of faulty installation, incompetent use and/or non-authorised personnel trying to make repairs.
  • Page 34: Commissioning Checklist

    12. COMMISSIONING CHECKLIST Type: Serial number: Installation date: Installed by firm: Installed by technician Inspection date: Technician: Initials: Nature of the maintenance: Inspection date: Technician: Initials: Nature of the maintenance: Inspection date: Technician: Initials: Nature of the maintenance: Inspection date: Technician: Initials: Nature of the maintenance:...
  • Page 35 NOTES...
  • Page 36 MAXIMIZING PERFORMANCE FOR YOU Spirotech 462 Camden Dr Bloomingdale, IL 60108 www.spirotech.com © 2024 Spirotech - Modifications and printing/typographic errors reserved...