Page 1
ADR112E/ADR212E (AM-230) Operating Manual for ASHIDA Numerical Voltage Protection Relay Type : ADR112E / ADR212E Model : AM–230–XX–XX–XX–XX-XX–XX Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 1 of 49...
Page 2
ADR112E/ADR212E (AM-230) Preface The ADR112E Neutral Displacement Voltage Protection Relay, Operating Manual describes common aspects of single pole voltage protection application and use of product. It includes the necessary information to safety, set, test, and operate the relay functionality. The operating manual can be used by power engineers and other experienced protective relaying applications.
Features Ordering Information Technical Specifications Type Test Details Drawing Reference PC SOFTWARE INFORMATION (ONLY FOR ADR212) Overview 3.1.1 Relay-Talk Software Features ASHIDA Relay Talk System ADR112E IED Main Screen 3.3.1 Parameter Display 3.3.2 IEDs Din Display 3.3.3 Control Operation 3.3.4 Private Setting 3.3.5...
Page 4
ADR112E/ADR212E (AM-230) 6.2.4 Communication Ports (Available in ADR212E) 6.2.5 Password MENUS 6.3.1 Default Display 6.3.2 Main Menu List 6.3.3 Main Menu Details 6.3.4 MEASUREMENT 6.3.5 Relay Settings 6.3.6 Faults FLOW CHART Main Menu To View – Measurement. Relay Settings. 7.3.1 To Set –...
ADR112E/ADR212E (AM-230) SAFETY GUIDE INTRODUCTION This guide and the relevant operating or service manual documentation for the equipment provide full information of safe handling, commissioning and testing of this equipment and also includes description of equipment label markings. The technical data in this safety guide is typical only see the technical data section of the relevant product publication(s) for data specific to particular equipment.
(AM-230) information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate person of Ashida Technical / Sales office and request the necessary information. SYMBOLS AND EXTERNAL LABELS ON THE EQUIPMENT...
Page 7
ADR112E/ADR212E (AM-230) To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used. The equipment must be connected in accordance with the appropriate connection diagram. Protection Class I Equipment Before energizing the equipment it must be earthed using the protective conductor terminal, if provided, or the appropriate termination of the supply plug in the case of plug connected equipment.
Page 8
ADR112E/ADR212E (AM-230) and replacement internal battery, as specified in the equipment documentation. For external protective fuses a UL or CSA Listed fuse shall be used. The Listed type shall be a Class J time delay fuse, with a maximum current rating of 15A and a minimum D.C. rating of 250 Vdc.
ADR112E/ADR212E (AM-230) Insertion of modules and PCB cards Modules and PCB cards must not be inserted into or withdrawn from the equipment whilst it is energized, since this may result in damage. Insertion and withdrawal of extender cards Extender cards are available for some equipment. If an extender card is used, this should not be inserted or withdrawn from the equipment whilst it is energized.
ADR112E/ADR212E (AM-230) DANGER - CTs must NOT be fused since open circuiting them may produce lethal hazardous voltages 7.2 Protective Class 1.4.2 Protective Class Class I (unless otherwise specified in the equipment documentation). IEC 60255-27: 2005 EN 60255-27: 2005 This equipment requires a protective conductor (earth) connection to ensure user safety.
(AM-230) INTRODUCTION AND SPECIFICATIONS Overview ASHIDA has designed economical & reliable Neutral Displavement Protection, Control and metering Relay. The ADR112E is Single phase neutral displacement voltage protection relay. The simple and compact construction of ADITYA series, ADR112E relay continuously monitors line voltage and provides integrated Protection, Control and Monitoring functions for low and medium switchgear Control.
ADR112E/ADR212E (AM-230) Ordering Information Definition of Model No For Aditya Series Relays AM XXX – XX – XX – XX – XX – XX – XX XX = PT XX = Communication Protocol 190VAC Not Applicable XX = Auxiliary Supply XX = CT 18 –...
Page 13
ADR112E/ADR212E (AM-230) Nominal Burden on 24 – : Less than 10VA. 230V Auxiliary Power Supply Tolerable AC ripple : Up to 15% of highest dc supply, As per IEC 60255- Relay power up time : <50ms Output contact: Output Contacts Make &...
ADR112E/ADR212E (AM-230) Type Test Details Sr. No. Tests Standard High Voltage Test : IEC 60255-5 Impulse Voltage Test : IEC 60255-5 High Frequency test : IEC 60255-22-1 Electro static Discharge : IEC 60255-22-2 and IEC 61000-4-2 Irradiation with radio frequency field, : IEC 60255-22-3 and IEC 61000-4-2 pulse-modulated, Fast transient interference/bursts...
Provides status of the input, output and protection functions tool. Control Provides the control function tool (output, LED) ASHIDA Relay Talk System Following is a brief step by step instruction to down load relay data using ASHIDA Relay Talk software. • Start Relay Talk program from program menu Following is the main screen of Relay talk system.
Page 16
ADR112E/ADR212E (AM-230) For successful communication, setting of relay should match with software settings. Here we have shown essential screens for ADR112E relay. • To check communication setting click Com Port button: After pressing Com Port button display will show following screen, and follow steps Communication Setting •...
ADR112E/ADR212E (AM-230) • Now press the Load IED button, the display will show following IED Main screen. IED main screen ADR112E IED Main Screen After checking all settings and loading the IED, the following window will display on the PC screen.
This is use to operate, relay control operation through PC General/Analogue This used to view Relay name, Version and compatibility. NOTE: The above features are generally provided with all the ASHIDA Relays but the * marked features are not applicable to this product 3.3.1 Parameter Display Online Parameters along with their values &...
Page 19
ADR112E/ADR212E (AM-230) 3.3.2 IEDs Din Display These are IED Din s; these IEDs along with their online status are display. Auxiliary Status 3.3.3 Control Operation The IEDs Controls are listed in the list and depending on their type either pulse or latch the control operation Control Operation 3.3.4...
Page 20
ADR112E/ADR212E (AM-230) 3.3.5 Settings This window is to view and edit the parameter of the relay. The settings are of two types General Settings and Bank Settings. 3.3.5.1 General Settings This window is to view and edit the parameters in general settings of the relay General Setting 3.3.5.2 Relay Settings...
Page 21
ADR112E/ADR212E (AM-230) 3.3.6 History Fault When the History fault selected, the following window displayed History Fault The windows/Buttons functions are as follows Sr. No Name Description Fault Buffer To view the fault buffer number Read Fault To read the fault selected in the fault buffer Refresh To refresh all windows and parameters Clear...
ADR112E/ADR212E (AM-230) PROTECTION LOGIC Neutral Displacement Voltage (50N/51N) ADR112E relay provides Neutral displacement voltage protection with Definite Time Delay. The ADR112E sense the input voltage (Open Delta) from line PT. The NDV protection provides two independent stages Alarm and Trip with difinite Time delay. The voltage can be set from 5% to 55% in step of 5%.
ADR112E/ADR212E (AM-230) SETTING SHEET All the relay parameters can be customized using RTV2 Software and HMI as per the functional requirements. The function wise parameter settings are described in the following sections. Relay settings Sr. No Parameter Setting / Ranges Password 000 to 999 New Password...
Page 24
ADR112E/ADR212E (AM-230) USER GUIDE Front Panel and Control Front panel Sr. No Legend Function GREEN LED – Power ‘ON’ indicator. RED LED – Relay ‘PKP Indication, switched ON when relay is picked up on protection functions FAULT RED LED – Relay ‘FAULT’ Indicator, switched ON when relay is tripped on protection functions.
ADR112E/ADR212E (AM-230) BYPASS Feather Touch Key ‘BYPASS’ for Bypassing Trip command. RESET Feather Touch Key ‘RESET’ for Reset the Hardware of relay. USER INTERFACE 6.2.1 LCD Display 16 x 2 LCD with back-lit is used as humans machine interface (HMI) for the followings: •...
Page 26
To enter password in all ADR112E refer following steps (User can go to this screen by pressing TEST + RESET Simultaneously This is default window showing the relay name Ashida Neutral Disp. Vol. Relay This is default window showing the relay type and unit ID.
Page 27
ADR112E/ADR212E (AM-230) To Enter the previously set Password Password = 000 Use Inr/Dec By using the plus / up arrow key ( + / ) or the minus / down arrow key ( - / 4) a given value can be set for each of the digits.
Page 28
2. Release ‘RESET’ + ‘TEST’ and keeping the MODE pressed till the following message is display. This will Reset password to ‘0’ (Zero). This is default window showing the relay name Ashida Neutral Disp. Vol. Relay This is default window showing the relay type and unit ID. ADR112E V1.01...
Page 29
ADR112E/ADR212E (AM-230) This window will flash momentarily showing the following Ashida Neutral Relay Name: Ashida Numerical UV/OV Protection Relay Disp. Vol. Relay Then the control will go automatically to next window. This window will flash momentarily showing the following ADR112E V1.01...
Page 30
ADR112E/ADR212E (AM-230) 6.3.3 Main Menu Details This is default window showing the actual Secondary Measurement Voltage. Press the Plus / up arrow (+ / ) Push Button to move to the next option. Password protected window for “Relay Settings’’ for Relay Settings setting New Password, Unit ID, Alarm OV%, Alarm Delay, Trip OV%, Trip Delay, Trip Test and Ann Cont.
Page 31
ADR112E/ADR212E (AM-230) This menu is to view the fourth latest Fault data stored Fault 5 by the relay. That is Trip Flags, Fault Voltage, and Trip Counter (TC) Press the Plus / up arrow (+ / ) Push Button to move to the next option.
Page 32
ADR112E/ADR212E (AM-230) Enter the previously set password, by using the plus / up Password = 0000 arrow (+ /) or the minus / Right arrow (- /4) Push Use Inr/Dec Button. The setting range is 000 to 099. As per the Enter the Password selection.
Page 33
ADR112E/ADR212E (AM-230) Press the Mode Push Button to move to the next option. By using the plus / up arrow (+ /) or the minus / Right Trip Delay = 00.0 arrow (- / 4) Push Button the desired Trip Delay can be Range Ins –...
Page 34
ADR112E/ADR212E (AM-230) 6.3.5.2 To View – Relay Settings Press the right arrow key (4) to view the Relay Settings. Relay Settings This window will show Unit Id setting done previously. Unit ID = 001 Press the right arrow key (4) to move to the next option. This window will show Alarm OV and Alarm Delay setting Alarm OV% = 055% done previously.
Page 35
ADR112E/ADR212E (AM-230) Fault 1 Display windows for Fault 2 to Fault 5 will be similar to that of Fault 1. Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 35 of 49...
After the Power ON or when the relay is reset the following windows will be displayed and the user can scroll the main menu as given below Model AM00201 ADR112E V1.01 Ashida Neutral 100% = 190V Unit ID = Disp. Vol. Relay Voltage = 000.0V MEASUREMENTS...
ADR112E/ADR212E (AM-230) To View – Measurement. Measurement Voltage = 000.0V Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 37 of 49...
Page 38
ADR112E/ADR212E (AM-230) Relay Settings. 7.3.1 To Set – Relay Settings. Relay Setting Password = 0000 Use Inr/Dec New Passw = 0000 Trip OV% = 055 New Password Range 5 – 55% Trip Delay = 00.0 Unit ID = 001 Range Ins – 99.9s Alarm OV% = 055 Trip Test = 001 Range 5 –...
Page 39
ADR112E/ADR212E (AM-230) 7.3.2 To View – Relay Settings. Relay Setting Unit ID = 001 Alarm OV% = 055% Alarm Delay = 00.0 Trip OV% = 055% Trip Delay = 00.0 Trip Test = Yes Ann. Cont. = SR To View – Faults. Fault 1 TC : 0001 V: 000.0 v...
Page 40
ADR112E/ADR212E (AM-230) INSTALLATION, COMMISSIONING & TESTING Overview The first steps in applying the ADR112E Voltage Relay are installing and connecting the relay. This section describes common installation features and requirements. To install and connect the relay safely and effectively, user must be familiar with relay configuration features and options.
Page 41
ADR112E/ADR212E (AM-230) Figure 2: Tightening Fitting clamps Caution: All screws are to be properly tightened. The Relay after fastening to the Panel with the help of M5 X 12 Screws is shown below. Figure 3: Relay mounted on the panel-front view Doc ID : ADR112E/OM/01 Rev No.
A PC with serial port, terminal emulation software, and serial communications cable with the following software (minimum configuration) For IEC 60870-5-103 communication check: Ashida Relay Talk-V1 software. Ashida Relay Assist software (Electrical Parameter Calculator) to verify Measured value of normal and sequence current.
ADR112E/ADR212E (AM-230) Check Relay Setting The relay setting check ensures that all of application specific relay setting for the particular installation have been correctly applied to the relay. Enter all setting manually via the relay front panel interface. The commissioning of following points: •...
Page 44
ADR112E/ADR212E (AM-230) Voltage Source 11 – 12 Auxiliary Supply (+ / -) 17 – 18 Power Supply (+ / -) Step1. Connect the PT terminals to voltage injector as per the chart. Step2. Adjust rated PT voltage (190 V AC). Observe the voltage value from measurement menu.
ADR112E/ADR212E (AM-230) Case dimensions Note: All dimensions in mm. Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 45 of 49...
Page 46
ADR112E/ADR212E (AM-230) 8.10 Back Terminal and Electrical wiring connection diagrams for ADR112E (Non Draw out) Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 46 of 49...
Page 47
ADR112E/ADR212E (AM-230) 8.11 Back Terminal and Electrical wiring connection diagrams for ADR112E (Draw out) Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 47 of 49...
Page 48
ADR112E/ADR212E (AM-230) REVISION CONTROL SHEET Rev. No. with Brief description of Revision Prepared by Reviewed by Approved by Date Original Version Saurabh Suyash 09.04.2022 Doc ID : ADR112E/OM/01 Rev No. : 01 Page No. : 48 of 49...
No ASHIDA trademarks may be used without written permission. The information in this document is provided for informational use only and is subject to change without legal notice. ASHIDA ELECTRONICS PVT LTD. has approved only the English language document.