Hitachi airHome Ducted RAD-GJ07QHAA Manual
Hide thumbs Also See for airHome Ducted RAD-GJ07QHAA:

Advertisement

Quick Links

INSTALLATION
Flare nut must use a torque wrench without fail. Tighten with the specifi ed tightening torque. If the fl are nut is tightened
too much, after a long period of time, the fl are nut breaks, Gas leakage, stagnation, touching fi re, rarely cause ignition.
MANUAL
Sharp bending of the pipe use the polyethylene rod, bend not crushed the pipe. Gas leakage from the crushed part,
stagnation, touching fi re, rarely cause ignition.
Please request your sales agent or qualifi ed technician to install your unit. Water leakage, short circuit or fi re may
occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation
may cause water leakage, electric shock and fi re.
Home
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If
not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual
Ducted
when dealing with the electrical work. Use cables which are offi cially approved in your country. Be sure to use the
specifi ed circuit. A short circuit and fi re may occur due to the use of low quality wire or improper work.
Be sure to use the specifi ed cables for connecting the indoor and outdoor units. Please ensure that the connections
are tight after the conductors of the wire are inserted into the terminals to prevent the external force is being applied
to the connection section of the terminal base. Improper insertion and loose contact may cause over-heating and fi re.
SPLIT TYPE AIR CONDITIONER
Please use the specifi ed components for installation work. Otherwise, the units may collapse or water leakage, electric
shock, fi re or stronger vibration may occur.
INDOOR UNIT
Be sure to use the specifi ed piping set for R32. Otherwise, this may result in broken copper pipes or faults.
RAD-GJ07QHAA
When installing or transferring an air conditioner to another location, make sure that air other than the specifi ed
refrigerant(R32) does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration
RAD-GJ09QHAA
cycle may increase abnormally which could result in a rupture and injury.
RAD-GJ12QHAA
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fi re, a
poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant
EN INSTRUCTION MANUAL
gas leaks into the room, coming into contact with fi re in the fan-driven heater, space heater, etc., a poisonous gas
may occur.
Unauthorized modifi cations to the air conditioner may be dangerous. If a breakdown occurs please call a qualifi ed air
FOR SERVICE
conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fi re, etc.
PERSONNEL ONLY
Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor
unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit.
Improper earthing may cause electric shocks.
When fi nishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If
Carefully read through the procedures of
proper installation before starting installation
you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked
work.
and a pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
The sales agent should inform customers
When installing the unit, be sure to install the refrigerant pipe before starting the compressor. If the refrigerant pipe
regarding the correct operation of installation.
is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level
of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
The electric cables should neither be reworked nor added. Make sure to use an exclusive circuit breaker. Otherwise
Tools Needed For Installation Work
fi re or electric shock might occur by connection failure, isolation failure or over current.
+ – Screwdriver
Measuring Tape
Make sure to connect cables to terminal properly and terminal cover should close fi rmly. Otherwise, over heating at
terminal contact, fi re or electric shock might occur.
Knife
Saw
Pipe Cutter
Make sure that there is no dust on any connected points of electric cables and fi x fi rmly. Otherwise, fi re or electric
Hexagonal Wrench Key (
5/32"(4mm))
shock might occur.
Power Drill (ø2-18/32"(65mm) ~
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
ø3-5/32"(80mm))
Vacuum Pump
capabilities or lack of experience and knowledge, unless they have been given supervision or instruction concerning
Pliers or Wrench
Torque Wrench
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Vacuum Pump Adaptor
Flare Tool
Appliance shall be installed in accordance with national wiring regulations and is not intended for use at altitudes
Gas Leakage Detector
Manifold Valve
exceeding 2000m (6561-22/32ft).
Charge Hose
Reamer
File
Refrigerant pipe size (outer diameter): Narrow pipe, Liquid (ø1/4"(6.35mm)); Wide pipe, Gas (ø3/8"(9.52mm))
SAFETY PRECAUTION
Read the safety precautions carefully before
Refrigerant
operating the unit.
Safety Group
A2L
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ....... Incorrect methods of installation
!
may cause death or serious injury.
Make sure to connect earth line.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user's guide. Ask a customer to keep this installation manual together with the instruction manual.
< IA2709: A >
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from
customer before installation.)
!
WARNING
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
!
WARNING
No nearby heat source and no obstruction near the air
outlet is allowed.
The clearance distances from top, right and left are specifi ed
in fi gure below.
The location must be convenient for water drainage and
pipe connection with the Outdoor unit.
No nearby leakage risk of fl ammable gas, and no nearby
source of vapor or oil smoke.
To avoid interference from noise, please place the unit and
its remote controller at least 3.28ft(1m) from the radio and
television.
To avoid any error in signal transmission from the remote
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.
The installation height should be at least 98-14/32"
(2500mm) or more from the fl oor.
The distance from the air outlet to the fi re alarm must
be at least 59-2/32" (1500mm) and there must be no fi re
alarm in the front direction of the indoor unit.
Do not install the indoor unit in a machine shop, kitchen
and laundry rooms when vapor from oil or its mist fl ows to
the indoor unit. The oil will deposit on the heat exchanger,
thereby reducing the indoor unit performance and may
deform and in the worst case, break the plastic parts of
the indoor unit.
California Proposition 65
Proposition 65: This product contains chemicals known to the state
WARNING
!
of California to cause cancer, birth defects, and other reproductive
harm. For more information, go to www.P65Warnings.ca.gov
[Indoor unit installation]
Be sure to completely
seal any gap with putty.
The
connecting
pipe,
irrespective of the size,
should all be insulated with
insulation pipe and then
wrapped with vinyl tape. (The
insulator will deteriorate if it
is not wrapped with tape).
Drain pipe
Must be installed separately.
Insulate indoor part of pipe to
prevent condensation.
"Height difference" and "Piping length" of Indoor and Outdoor unit are different by Outdoor unit.
Please refer to the installation manual in Outdoor unit.
<IA2709: A >
WARNING
!
This appliance is fi lled with R32.
!
CAUTION ......... Improper installation may
result in serious consequence.
This sign in the fi gures indicates prohibition.
Accessories to indoor Unit:
No.
Item
Flare Insulator
1
Binder
2
4.0 x 10 Screw
3
Insulation Pipe
4
Aluminium Tape (large)
5
Band
6
Suspension Clamp (right, left) each
7
4.0 x 10 Screw
8
Other optional parts for display panel wireless remote
controller SPX-RKDN1
No.
Item
Quantity
Display panel
1
Panel installation plate
2
Panel cover
3
Remote controller (wireless)
4
Remote Controller Holder
5
3.1 x 16 screw
6
Optional part for wired remote controller SPX-URFG1
No.
Item
Quantity
Remote controller (wired)
7
CAUTION
!
Always install the indoor unit at level. If the
indoor unit is inclined, water may leak.
Electrical box
Air outlet
The indoor piping should
b e i n s u l a t e d w i t h t h e
enclosed insulation pipe. (If
the insulator is insuffi cient,
7
please use commercial
products.)
The Choice of Mounting Site
!
CAUTION
A circuit breaker must be installed in the house
distribution box for the direct connected power
supply cables to the outdoor unit. In case of other
installations a main switch with a contact gap or
more than 4/32" (3mm) has to be installed. Without
a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location
where there is flammable gas. The
outdoor unit may catch fi re if fl ammable
gas leaks around it.
Please ensure smooth fl ow of water when installing
the drain hose. Improper installing may wet your
furniture.
Piping shall be suitable supported with a maximum
spacing of 3-9/32' (1m) between the supports.
Please ensure fi eld selected electrical components
(switches,wires,etc) are following approved local
regulation requirements.
This air conditioner is an appliance that should not be accessible to the general public.
One ducted unit shall be supplying to one room.
1. RECOMMENDATION FOR INSTALLATION
The fi gures below are the recommended installation type for this duct model.
All the optional parts mentioned for each installation type and screws should be purchased locally prior to the installation.
Full duct type
Need optional parts
when installing full duct type (Local purchase)
1
Discharge grille
Chamber of discharge grille ø5-29/32"(150mm)
2
3
Chamber of discharge of unit side ø5-29/32"(150mm)
4
Chamber of suction of unit side ø5-29/32"(150mm)
Chamber of suction grille ø5-29/32"(150mm)
5
Suction grille with fi lter
6
Flexible duct ø5-29/32"(150mm) 3-9/32'(1m)
7
Flexible duct ø5-29/32"(150mm) 6-18/32'(2m)
Quantity
1
2
2
2. Installation procedure and notice
1
Select the installation location carefully for the split type
1
air conditioner. It is very diffi cult to move a split type air
1
conditioner after the fi rst installation.
2
2.1
Make a hole on the wall as shown in Fig. 2-1.
8
2.2 Connecting pipe installation
1
Seal the end of the pipes to prevent damage from
1
moisture and water.
1
1
1
2
1
2.3 Drain pipe installation
Use PVC pipe VP20 (O.D. 1"(25mm)) for drain pipe.
You must roll an insulation (thickness 13/32"(10mm) or more) over the indoor section of the drain pipe.
Position the drain pipe in the downward direction to enable free-fl ow of water. Fix it with a hanger and avoid twisting the pipe as
shown in Fig. 2-3.
Downward 1/25 ~ 1/100
Insulation
(Thickness 13/32"(10mm) or more)
In case drain piping cannot be done smoothly due to obstacles, it can also be arranged outside of the main unit as shown
in the drawing below.
5-14/16"(150mm) or less
Air inlet
Wired
remote
controller
(Please note the following matters and obtain permission from customer before installation).
Refrigerant
Safety Group
This appliance is fi lled with R32
A2L
This symbol shows that the Operation
Instructions should be read carefully.
This symbol shows that a service personnel
should be handling this equipment with
reference to the Installation Manual.
This symbol shows that there is information
included in the Operation Manual and/or
Installation Manual.
NOTE
!
Semi duct type
Need optional parts
when installing semi duct type (Local purchase)
1
Discharge grille
2
Chamber of discharge grille ø5-29/32"(150mm)
3
Chamber of discharge of unit side ø5-29/32"(150mm)
4
Suction grille
Flexible duct ø5-29/32"(150mm) 3-9/32'(1m)
5
Flexible duct ø5-29/32"(150mm) 6-18/32'(2m)
Non duct type
Need optional parts
when installing non duct type (Local purchase)
1
Discharge grille
2
Discharge duct
3
Suction grille
3/32~6/32"(2~5mm)
2-18/32"
(65mm)
Indoor
Outdoor
side
side
Fig. 2-1
25/32"~1-18/32"
(20mm~40mm)
Large diameter pipe
2-12/32"
(60mm)
3-30/32"
(100mm)
Small diameter pipe
Insulation pipe
Fig. 2-2
Seal
No trap
Do not do the installation as shown as above
Insulation (Thickness 3-15/16"(100mm) or more)
Fig. 2-3
WARNING
CAUTION
CAUTION
CAUTION
The hole on the wall
should be made
with some inclination
like Fig. 2-1 to keep
the smooth fl ow of
condensed water.
2-12/32"
60mm)
25/32"~1-18/32"
(20mm~40mm)
Tape
7-28/32"
(200mm)
(Unit : inch)
No insulation
Stagnant water

Advertisement

loading
Need help?

Need help?

Do you have a question about the airHome Ducted RAD-GJ07QHAA and is the answer not in the manual?

Questions and answers

Summary of Contents for Hitachi airHome Ducted RAD-GJ07QHAA

  • Page 1 The Choice of Mounting Site (Please note the following matters and obtain permission from customer before installation). WARNING CAUTION WARNING INSTALLATION ● A circuit breaker must be installed in the house Refrigerant Safety Group ● Flare nut must use a torque wrench without fail. Tighten with the specifi ed tightening torque. If the fl are nut is tightened This appliance is fi...
  • Page 2 2.4 Installation method of unit type (4) Preparation for installing indoor unit Install 4 suspension clamps at both sides of indoor unit, 2 INSTALLATION OF FULL DUCT TYPE clamps at each side, using 8 tapping screws (Since size of left and right clamps are different for certain Select the indoor unit position, fi...
  • Page 3 Chamber of discharge grille (2) Opening on ceiling and suspension bolt position Opening for discharge 37-4/5"(960mm) Use M10 bolt for suspension. 5-1/2"(140mm) 7-5/6"(199mm) Suspension bolt Opening of ceiling and suspension bolt position are as 29-1/7"(740mm) Suspension bolt 31-1/9"(790mm) 1-1/6" (M10: Local purchase) Reinforcement Suspension bolt shown on the left.
  • Page 4 2.6 Preparation of pipe Bushing for refrigerating pipes Refrigerating pipes Use a pipe cutter to cut the copper pipe. Connecting cord Trimming tool Sealer CAUTION Jagged edge will cause leakage. Protection pipe Copper pipe Point the side to be trimmed downwards Drain hose during trimming to prevent copper chips from entering the pipe.

This manual is also suitable for:

Airhome ducted rad-gj09qhaaAirhome ducted rad-gj12qhaa