Table of contents 1 Special information ........... 3 13 Shutdown (qualified contractors) ......18 13.1 Draining the brine circuit......... 18 2 General information..........3 Symbols in this document ........ 3 14 Specification............. 19 Units of measurement ........3 14.1 Dimensions and connections......19 Other applicable documents ......
Special information Standard: EN 14511, EN 14825 Special information The output data specifically mentioned in text, diagrams and – The following groups of people are not per- technical datasheets has been calculated according to the test conditions of the standard shown in the heading of this section. mitted to use the appliance: Generally, these standardised test conditions will not fully meet –...
Appliance description Property damage, consequential losses, environmental Signal Meaning word pollution NOTICE Failure to observe this information may result in – Unsuitable spare parts and accessories may jeopardise the property damage, consequential losses or environ- safety of the product and persons using the appliance. Al- mental damage.
– Flow temperature sensor T33 ter. WPE-I 57 Premium H | WPE-I 85 Premium H Ventilation: Inverter cooling WPE-I 57 Premium H and WPE-I 85 – Pressure hose SD 40-0.8 G Premium H – Pressure hose SDB 50-0.8 G A fan is installed at the top right-hand side of the appliance.
– Ensure that the entire appliance frame is in full contact with WPE-I 57 Premium H | WPE-I 85 Premium H the substrate. Uneven substrates can increase sound emis- sions.
Installation (qualified contractors) WPE-I 57 Premium H | WPE-I 85 Premium H D0000117952 D0000082845 Siting the appliance u Undo the closures on the top cover. Unpacking the appliance u Pull the top of the front panel forwards. u Remove the packaging material.
Page 8
Charge the brine circuit via the "brine drain" connection. PG 10 Heat transfer medium as concentrate 236307 based on propylene glycol WPE-I 57 Premium H Content: 10 l WPE-I 85 Premium H PG 30 Heat transfer medium as concentrate 236306 based on propylene glycol Content: 30 l...
Connect the heat pump on the heating side. u Install air vent valves at the required positions. WPE-I 57 Premium H u Install the circulation pump in the heating flow. WPE-I 85 Premium H u Install a fill connector with a non-return valve.
Installation (qualified contractors) 6.7.1 DHW heating with hot gas technology u The refrigerant is highly flammable. Mark the installation area with an Atex symbol. u Connect the "Heat pump DHW flow" connection from the DHW cylinder to the "Hot gas DHW flow optional" connec- tion.
Page 11
6.9.3 Routing supply lines Heat pump Short-circuit capacity [MVA] WPE-I 57 Premium H WPE-I 85 Premium H 6.9.1 Opening the terminal area The terminals are located inside the appliance control panel, behind the front fascia.
Commissioning (qualified contractors) 6.9.4 Additional components Temperature [°C] PT 1000 sensor Resistance [Ω] u If you want to install a mixer, use one with a control voltage 1155 of 10 V. 1194 u Connect the power cables for the additional components in 1232 accordance with the wiring diagrams.
Commissioning (qualified contractors) 7.1.4 High limit safety cut-out of the electric emergency/ Diverter valve auxiliary heater u Test the diverter valve. At ambient temperatures of below -15 °C, the high limit safety – 0 = Heating cut-out of the electric emergency/auxiliary heater may trip. –...
Commissioning (qualified contractors) Commissioning: Adjusting the heating curve Checkpoint Reference to instruc- Com- tions pleted? The efficiency of a heat pump decreases as the flow temperature Have all the pipes in the rises. Therefore adjust the heating curve with care. A heating heating system been curve that is set too high leads to the zone or thermostatic sized correctly?
Cleaning Checkpoint Reference to instruc- Com- 11 Troubleshooting tions pleted? Has the high pressure switch been tested? Fault Possible cause Remedy There is no hot wa- No voltage at the Check the fuses / ter or the heating appliance. MCBs in your fuse Cleaning system remains box / distribution...
Page 16
Troubleshooting (qualified contractors) Message Class Description Message Class Description High pressure High pressure switch activ- DHW control sensor B Sensor alarm switch ated DHW return Sensor alarm Low pressure Paused at low pressure, Cooling cylinder Sensor alarm more than 5 times in sensor 5 hours, low pressure limit Cooling circuit flow...
Page 17
Troubleshooting (qualified contractors) Other faults Message Class Description Heating circuit 2 Temperature deviation ac- Fault Possible cause Remedy control cording to alarm settings for heating circuit 2 The heat pump is The wrong heat u Check which not running. pump is set on the Heating circuit 3 Temperature deviation ac- model has been...
13.1 Draining the brine circuit u Use the connection on the low pressure side and the high pressure connection in the liquid refrigerant line next to the dry filter. WPE-I 57 Premium H WPE-I 85 Premium H D0000117945 | WPE-I 57/85 Premium H...
Specification 14.1 Dimensions and connections 14 Specification WPE-I 57 Premium H WPE-I 85 Premium H D0000117920 WPE-I 57 Premium WPE-I 85 Premium Entry electrical cables I Entry electrical cables II Hot gas DHW flow optional Diameter Hot gas DHW return optional...
Specification 14.3 Output diagrams 14.3.1 WPE-I 57 Premium H Heating output WPE-I 57 heating output Power consumption WPE-I 57 power consumption www.stiebel-eltron.com WPE-I 57/85 Premium H |...
Page 22
Specification Coefficient of performance WPE-I 57 coefficient of performance 14.3.2 WPE-I 85 Premium H Heating output WPE-I 85 heating output | WPE-I 57/85 Premium H www.stiebel-eltron.com...
Page 23
Specification Power consumption WPE-I 85 power consumption Coefficient of performance WPE-I 85 coefficient of performance www.stiebel-eltron.com WPE-I 57/85 Premium H |...
Specification 14.4 Data table WPE-I 57 WPE-I 85 Premium H Premium H Performance data applies to new appliances with clean heat ex- Weights changers. Weight The power consumption figures for the integral auxiliary drives Connections are maximum values and may vary subject to operating point. Connection, hot gas mm 28.00 28.00...
Guarantee 15 Guarantee The guarantee conditions of our German companies do not ap- ply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products a guarantee can only be issued by those subsidiaries. Such guarantee is only granted if the subsidiary has issued its own terms of guarantee.
Page 26
| WPE-I 57/85 Premium H www.stiebel-eltron.com...
Page 27
www.stiebel-eltron.com WPE-I 57/85 Premium H |...
Page 28
Co m f o r t t h r o u gh Te c h n o l o g y STIEBEL ELTRON GmbH & Co. KG Dr.-Stiebel-Straße 33 | 37603 Holzminden | Germany info@stiebel-eltron.com | www.stiebel-eltron.com 4 0 1 7 2 1 3 6 6 3 9 9 7...
Need help?
Do you have a question about the WPE-I 57 Premium H and is the answer not in the manual?
Questions and answers