INSTALLATION
●
Flare nut must use a torque wrench without fail. Tighten with the specifi ed tightening torque. If the fl are
MANUAL
nut is tightened too much, after a long period of time, the fl are nut breaks, Gas leakage, stagnation,
touching fi re, rarely cause ignition.
●
Sharp bending of the pipe use the polyethylene rod, bend not crushed the pipe. Gas leakage from the
crushed part, stagnation, touching fi re, rarely cause ignition.
●
Please request your sales agent or qualifi ed technician to install your unit. Water leakage, short circuit
or fi re may occur if you do the installation work yourself.
●
Home
Please observe the instructions stated in the installation manual during the process of installation. Improper
installation may cause water leakage, electric shock and fi re.
●
Make sure that the units are mounted at locations which are able to provide full support to the weight
of the units. If not, the units may collapse and impose danger.
●
Observe the rules and regulations of the electrical installation and the methods described in the installation
manual when dealing with the electrical work. Use cables which are offi cially approved in your country.
Be sure to use the specifi ed circuit. A short circuit and fi re may occur due to the use of low quality wire
or improper work.
●
Be sure to use the specifi ed cables for connecting the indoor and outdoor units. Please ensure that
SPLIT UNIT AIR CONDITIONER
the connections are tight after the conductors of the wire are inserted into the terminals to prevent the
external force is being applied to the connection section of the terminal base. Improper insertion and
INDOOR UNIT
loose contact may cause over-heating and fi re.
●
Please use the specifi ed components for installation work. Otherwise, the units may collapse or water
RAK-GJ12PHAA
leakage, electric shock, fi re or stronger vibration may occur.
●
Be sure to use the specifi ed piping set for R32. Otherwise, this may result in broken copper pipes or
OUTDOOR UNIT
faults.
RAC-GJ12WHAA
●
When installing or transferring an air conditioner to another location, make sure that air other than the
specifi ed refrigerant(R32) does not enter the refrigeration cycle. If other air should enter, the pressure
level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
EN INSTRUCTION MANUAL
●
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact
with fi re, a poisonous gas may occur.
●
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the
refrigerant gas leaks into the room, coming into contact with fi re in the fan-driven heater, space heater,
FOR SERVICE
etc., a poisonous gas may occur.
PERSONNEL ONLY
●
Unauthorized modifi cations to the air conditioner may be dangerous. If a breakdown occurs please call
a qualifi ed air conditioner technician or electrician. Improper repairs may result in water leakage, electric
shock and fi re, etc.
●
Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor
and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line
of the telephone unit. Improper earthing may cause electric shocks.
●
Carefully read through the procedures of
●
When fi nishing the refrigerant collection (pumping down), stop the compressor and then remove the
proper installation before starting installation
coolant pipe. If you remove the refrigerant pipe while the compressor is operating and the service valve
work.
is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing an
●
The sales agent should inform customers
explosion or injury.
regarding the correct operation of installation.
●
When installing the unit, be sure to install the refrigerant pipe before starting the compressor. If the
refrigerant pipe is not installed and the compressor is operated with the service valve released, air is
sucked and the pressure level of the refrigeration cycle may increase abnormally which could result in
a rupture and injury.
Tools Needed For Installation Work
●
The electric cables should neither be reworked nor added. Make sure to use an exclusive circuit breaker.
(
mark is tool exclusive use for R32)
Otherwise fi re or electric shock might occur by connection failure, isolation failure or over current.
●
●
+ – Screwdriver
●
Measuring Tape
Make sure to connect cables to terminal properly and terminal cover should close fi rmly. Otherwise, over
heating at terminal contact, fi re or electric shock might occur.
●
Knife
●
Saw
●
Pipe Cutter
●
Make sure that there is no dust on any connected points of electric cables and fi x fi rmly. Otherwise, fi re
●
Hexagonal Wrench Key (
5/32"(4mm))
or electric shock might occur.
●
Power Drill (ø 2-18/32" (65mm) ~ ø 3-5/32"
●
This appliance is not intended for use by persons (including children) with reduced physical, sensory or
●
(80mm))
Vacuum Pump
Pliers or Wrench
mental capabilities or lack of experience and knowledge, unless they have been given supervision or
●
Torque Wrench
Vacuum Pump Adaptor
instruction concerning use of the appliance by a person responsible for their safety.
●
Flare Tool
●
Gas Leakage Detector
Children should be supervised to ensure that they do not play with the appliance.
●
Manifold Valve
Charge Hose
Appliance shall be installed in accordance with national wiring regulations and is not intended for use at
altitudes exceeding 2000m (6561-22/32ft).
●
Reamer
●
File
SAFETY PRECAUTION
Read the safety precautions carefully before
Refrigerant
operating the unit.
Safety Group
A2L
●
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation
!
CAUTION ......... Improper installation may result in
!
may cause death or serious injury.
Make sure to connect earth line.
This sign in the fi gures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user's guide. Ask a customer to keep this installation manual together with the instruction manual.
<IA2691: A >
1
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
!
CAUTION
●
The draining of the water container inside the indoor unit can be done from the left.
Therefore the mounting plate must be fi xed horizontally or slightly tilted towards the
side of drain hose. Otherwise, condensed water may overfl ow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the mounting plate.
●
25-31/32" (660mm)
5-23/32"
5-23/32"
(145mm)
(145mm)
2-18/32"
4 -4/32"
2-20/32"
(65mm)
(67mm)
(105mm)
37-13/32" (950mm)
Level
Screw for Hanger
Screw the hanger at the positions
Hanger
possibly near the upper and lower
hooks where the indoor unit is
hung. Use 4 or more screws to
fi x the hanger.
Line
Weight
Wall hole
Procedures of Installation and Precautions
Procedures to fi x the mounting plate.
●
1. Drill holes on wall.
2. Push plug into the holes. 3. Fix the mounting plate on wall
(As shown below)
(As shown below)
1-17/64"
(32mm)
5/32 x 1-17/64 (4,1 x 32) Screw
Procedures to fi x the holder of remote control.
●
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
25/32"
(20mm)
Wall Penetration and Installation of Protection Pipe
Drill a ø 2-9/16" (65mm)
●
hole on wall which is
slightly tilted towards the
5/64" (2mm) -
outdoor side. Drill the
13/64" (5mm)
wall at a small angle.
●
Cut the protection pipe
according to the wall
thickness.
Empty gap in the sleeve
●
of protection pipe should
be completely sealed with
putty to avoid dripping of
rain water into the room.
<
>
IA2691: A
WARNING
!
This appliance is fi lled with R32.
serious consequence.
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
●
Pull out the pipe, connecting cord and drain
●
hose.
Installation
The upper part of the indoor unit is hanged on the mounting plate.
●
The projection at the lower part of the indoor unit is hooked onto the mounting plate.
●
2-18/32"
(65mm)
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown
●
in fi gure below. Be sure to plug in the drain hose until the insulating material folds
upon itself.
Please use pliers to pull out
●
with 5/32 x 1-17/64 (4.1 x 32) screw
the drain cap.
(As shown in fi gure be
low)
(This is an easier way to
remove the drain cap).
above 1-31/32"
(50mm)
Drain cap
Remove the cap for
●
drain hose installation
!
WARNING
Be sure that the wire is not
in contact with any metal
in the wall. Please use
the protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
!
CAUTION
flows from outdoor and
Condensed water may leak out if not
dew may drop.
inserted properly.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation).
WARNING
!
●
The unit should be mounted at stable, non-vibratory
location which can provide full support to the unit.
●
CAUTION
!
●
No nearby heat source and no obstruction near the
air outlet is allowed.
●
The clearance distances from top, right and left are
●
specifi ed in fi gure below.
●
The location must be convenient for water drainage
●
and pipe connection with the Outdoor unit.
●
To avoid interference from noise please place the unit
●
and its remote controller at least 3-9/32ft (1m) from the
radio, television and inverter type fl uorescent lamp.
●
To avoid any error in signal transmission from the
remote controller, please put the controller far away
●
from high-frequency machines and high-power wireless
●
systems.
●
●
The installation height of indoor unit must be 7-35/64ft
(2.3m) or more.
●
●
Names of Indoor Components
●
Direction of Piping
Component's Name
Qty
No.
●
●
Mounting Plate
●
1
1
●
●
There are 6 directions
●
allowed, namely,
Screw for Mounting
horizontally perpendicular
Plate
6
2
(5/32 x 1-17/64)
to the unit, vertically down
●
from right, horizontally out
(4.1 x 32)
from right, horizontally out
to left,
Holder for Remote
horizontally out to right,
Controller
vertically down from left.
1
3
Dimension of Mounting Stand
of the outdoor unit
AAA Size Battery
(unit : mm)
2
4
mounting stand
2-1/4"(57mm)
Screw for holder of
Remote Controller
2
5
( 1 / 8 x 5 / 8 )
( 3 . 1 × 1 6 )
Remote Controller
15/32"(12mm)
1-3/8"(35mm)
1
6
19-45/64"(500mm)
4-57/64"(124mm)
Purifying Filter
7
2
CAUTION
!
●
Installation of pipe length less than
minimum pipe length requirement
Wi-Fi Adapter
9-27/32ft(3m) may generate an
abnormal sound.
1
8
WARNING
!
●
Flare connection only at
outside of building
CAUTION
Refrigerant piping must
●
A brazed, welded or mechanical
be protected from physical
connection shall be made before
damage. Install a plastic
opening the valves to permit
cover or equivalent.
refrigerant to fl ow between the
refrigerating system parts. A vacuum
valve shall be provided to evacuate
the interconnecting pipe and/or any
uncharged refrigerating system.
●
Mechanical connectors used indoor
shall comply with ISO 14903.
When mechanical connectors are
reused indoors, sealing parts shall
be renewed. When fl are joints are
above
reused indoors, the fl are part shall
be re-frabricated.
●
Refrigerant tubing shall be protected
or enclosed to avoid damage.
above 27-37/64"
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fi t into the hole on the wall and
●
then ready for further connection.
The terminals of 2 connected pipes must be covered with insulator used for
●
terminal connection. Then the pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical cover. (Refer to
●
"CONNECTION OF POWER CORD")
After adjustment, fi t the connecting cord and pipes into the space available
●
under the indoor unit.
Connecting cords, pipe and
When connection is at left side, refrigerating pipe and cabinet shall be tied
●
drain hose must be laid
together.
together with Vinyl tape.
Failing to do so may cause the unit bottom side become warping.
Excess binder shall be cut to prevent abnormal sound and water dripping.
!
CAUTION
Please pull the lower
Binder
part of the indoor unit
outwards to check if
Insulation pipe (must be wrapped with
the unit is hooked onto
vinyl tape at every 4-47/64"(120mm)).
the mounting plate.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
Improper installation
INSTALLATION OF INDOOR UNIT
may cause vibration
and noise.
Preparation To Install Refrigerating Pipes
The end of the refrigerating pipes are at locations
●
marked with "
43-10/32 (1100mm)
Installation
Hang the Indoor unit onto the mounting plate. Use the temporary stand at the back
of the Indoor unit to push its lower part 5-29/32" (150mm) forwards.
●
Place the drain hose through the hole on the wall.
●
Wrap the refrigerating pipes with insulation pipe after connecting refrigerating pipe.
●
Connect the connecting cord after removing electrical cover. (Refer to "Connection
of Power Cord")
●
After adjustment, the connecting cord and refrigerating pipes are placed into the
space available under the Indoor unit.
●
The projection of Indoor unit must hook to the mounting plate.
Pipe
Cable
Drain layout of backward piping from left
Refrigerating pipe
Heat insulation pipe
Connecting cord
3
Installation of Drain Hose
●
Do not guide the drain hose to places where corrosive gases (sulfur, ammonia, etc.) are generated,
such as septic tanks and sewer.
Corrosive gas may fl ow backward from the drain hose to the indoor unit, corrode the copper pipe, or
it may cause offensive odors in the room.
●
Cut the drain hose at a position 3-15/16"(100mm) higher than the fl oor surface. It may cause water
leakage due to air lock or clogging of foreign matter.
!
CAUTION
OUTDOOR UNIT
WARNING
!
The outdoor unit must be mounted at a location which can support heavy weight. Otherwise,
noise and vibration will increase.
CAUTION
!
A circuit breaker or fuse must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
The external switch shall be incorporated to completely disconnect from power supply. It should disconnect all
poles, and a contact separation of at least 4/32" (3mm) must be present.
Do not install the unit near a location where there is fl ammable gas. The outdoor unit may
catch fi re if fl ammable gas leaks around it.
Do not install the indoor unit in a machine shop, kitchen and laundry rooms when vapor
from oil or its mist fl ows to the indoor unit. The oil will deposit on the heat exchanger,
thereby reducing the indoor unit performance and may deform and in the worst case, break the plastic parts
of the indoor unit.
Please ensure smooth fl ow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 3-9/32ft (1m) between the supports.
Selecting the installation location: Suitable location that will reduce the impact from rain and direct sun that
may affect the unit performance. Besides that, ventillation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right and front are specifi ed in fi gure below. At least three of the
above sides must be open air.
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
Do not install at a location where there is fl ammable gas, steam, oil and smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connection wire at least 3-9/32ft (1m) away from the antenna or signal line of
television, radio or telephone. This is to avoid noise interference.
Do not install outdoor unit facing strong wind direction. It may damage the fan motor.
Do not install the outdoor unit in a place where small animals may build their nests. If small animal goes
inside the unit and touches the electrical parts, failure of the unit, smoke or fi re may be caused. Request your
customer to keep the surrounding of the unit is clean.
Safely dispose all packing and transportation materials in accordance with federal/state/local laws orordinances.
Packing materials such as nails and other metal or wood parts, including plastic packing materials used for
transportation may cause injuries or death by suffocation.
The maximum number of pieces of equipment permitted to be stored together will be determined by local
regulations. Storage package protection should be constructed in such a way that mechanical damage to the
equipment inside the package will not cause a leak of the REFRIGERANT CHARGE.
Figure showing the Installation of Indoor and Outdoor Unit.
CAUTION
!
In case the pipe length is more than the recommended length for chargeless, add refrigerant
R32 as below. Do not exceed the maximum pipe length.
CAUTION
!
●
This unit is chargeless up 49-7/32ft (15m) pipe length.
●
Installation of pipe length less than minimum pipe length requirement 9-27/32ft (3m)
may generate an abnormal sound.
Max. Pipe
Chargeless up to
Additional R32
The maximum refrigerant
Model
ft(m)
ft(m)
oz/ft(g/m)
82-1/32ft (25m)
49-7/32ft (15m)
0.11oz/ft (10g/m)
RAC-GJ12WHAA
Be sure to
completely
above
above
3-15/16"
(100mm)
seal any gap
above 3-15/16"
with putty.
(100mm)
90-5/8" (2300mm) or more
6
●
The difference in height
between the indoor and
4
outdoor unit should be
3
kept max 49-7/32ft (15m).
●
The connecting pipe,
no matter big or small,
should all be insulated
with insulation pipe and
then wrapped with vinyl
above 7-7/8"(200mm)
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
above
3-15/16"
(100mm)
The connection of insulated
drain hose.
inner diameter ø5/8"(16mm)
3-15/16"
(100mm)
Please use insulated drain
hose for the indoor piping
(commercial product).
)
(700mm
above 7-7/8" (200mm)
Connecting cord
Pipe
!
CAUTION
●
The rubber strap used
for fixing the insulator
should not be tied with
Hook portion for binder tightening
great force. Otherwise,
this will damage heat
Binder
insulation and causes
water condensation.
Refrigerating
Pipe
Insulator
Hook
Hook
Pipe
Drain Hose
Rubber strap tied with
great force
!
CAUTION
Please fi x in the plastic core
●
after fl aring to avoid copper
" symbol.
chips entering the pipes.
Please bend at a small
radius to form an arc
Projection
about 5-29/32"(150mm)
Wall hole
Drain hose
Protection
pipe
Pull this to the front
Drain hose
during the connection
of refrigerating pipes
to ease task.
Connecting cord
!
CAUTION
CAUTION
!
Be sure that the
drain hose is not
loosely connected
Above
or bend.
3-15/16"
(100mm)
You are free to choose the side (left or right) for the installation of drain hose.
Please ensure the smooth fl ow of condensed water of the Indoor unit during
installation. (Carelessness may result in water leakage.)
charge (mmax)
44.45oz (1260g)
3-15/16"
(100mm)
The indoor piping
should be insulated
with the enclosed
i n s u l a t i o n p i p e .
(If the insulator is
insufficient, please
u s e c o m m e r c i a l
products).
Drain hose
below
13/64"
(5mm)
Hook
Connected
section
Need help?