TECHNICAL GUIDE
R-410A
ZT SERIES
3 - 5 TON
60 Hertz
ZT 3 THROUGH 5 TON
®
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Description
ASHRAE 90.1 COMPLIANT
®
®
YORK
Predator
units are convertible single packages with a
common footprint cabinet and common roof curb for all 3
through 5 ton models. The units were designed for light
commercial applications and can be easily installed on a roof
curb, slab, or frame.
®
All Predator
units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and down
discharge applications, as well as all tonnage sizes.
®
Predator
units are available in the following configurations:
cooling only, cooling with electric heat and cooling with gas
heat. Electric heaters are available as factory-installed options
or field-installed accessories.
All units meet ASHRAE 90.1 single-zone variable supply air
volume standard. Featuring a variable frequency drive on 3
through 5 ton ZT models.
Tested in accordance with:
1041165-YTG-C-0614

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZT Series and is the answer not in the manual?

Questions and answers

Summary of Contents for York ZT Series

  • Page 1 1041165-YTG-C-0614 ® TECHNICAL GUIDE R-410A Description ZT SERIES ASHRAE 90.1 COMPLIANT ® ® 3 - 5 TON YORK Predator units are convertible single packages with a common footprint cabinet and common roof curb for all 3 60 Hertz through 5 ton models. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame.
  • Page 2 Roof curbs for transitioning (stainless steel option) from York Sunline™ footprint to the ZT Series footprint One or Two stage gas heating to are available Side entry power maintain warm, comfortable (field-installed accessory)
  • Page 3 Johnson Controller UNT 1126 (N2 protocol), DFS, APS 061 = 5 Ton Honeywell Controller, DFS, APS Novar Controller, DFS, APS York Commercial Comfort System (YCCS) Rtu Controller Heat Type and Nominal Heat Capacity Simplicity IntelliComfort II Controller C00 = Cooling Only. No heat installed Simplicity IntelliComfort II Controller w/Simplicity®Linc...
  • Page 4 High Efficiciency 3 to 5 ton units) Communicates on a and 2 stage gas heating. The first stage of a gas heat MODBUS RTU protocol network - The York® Simplicity® ® Predator unit provides 70% or 75% of the heating INTELLI-Comfort II™...
  • Page 5 Factory Installed Options • Nuisance Trip Protection and Strikes - To prevent ® nuisance trouble calls, the control board uses a “three YORK offers several equipment options factory installed, for ® line. times, you’re out” philosophy. The high and low-pres -...
  • Page 6 1041165-YTG-C-0614 selected. The economizer has spring return, fully wiring. The “Powered” option is powered by a stepdown modulating damper actuators and is capable of introducing transformer in the unit. Factory installed option only. up to 100% outdoor air. As the outdoor air intake dampers •Smoke Detectors - The smoke detectors stop operation open, the return air dampers close.
  • Page 7 Includes air supply sensor, return air sensor, dirty filter of the unit by interrupting power to the control board if indicator switch, and air proving switch. smoke is detected within the air compartment. •York Commercial Comfort System (YCCS) - Provides •CO Sensor - Senses CO levels and automatically...
  • Page 8 1041165-YTG-C-0614 •Roof Curbs - The roof curbs have insulated decks and are •Thermostat - The units are designed to operate with 24- shipped disassembled The roof curbs are available in 8” and volt electronic and electro-mechanical thermostats. All 14” heights. For applications with security concerns, burglar Ultra High Efficiency 3-5 Ton units (with or without an bars are available for the duct openings of the roof curbs.
  • Page 9 1041165-YTG-C-0614 Accessories (Continued) Field Installed Accessories - Electric Heat MODEL VOLTAGE DESCRIPTION WHERE USED 2TP04510325 3kW Electric Heat All 42" Cabinet 3 Ton Models 2TP04510346 2TP04510625 6kW Electric Heat All 42" Cabinet 3, 4 and 5 Ton Models 2TP04510646 2TP04510825 2TP04510846 9kW Electric Heat All 42"...
  • Page 10 Units shall be manufactured by Unitary Products in an ISO ® vice factor. Units shall be designed to operate within the service 9001 certified facility. YORK® Predator units are convertible factor. Fan wheel shall be double inlet type with forward curve...
  • Page 11 1041165-YTG-C-0614 Unit Controls: with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required). a. Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker on UNIT OPERATING CHARACTERISTICS the 24-volt transformer side.
  • Page 12 1041165-YTG-C-0614 optional indoor blower motors that provide higher static •STAINLESS STEEL HEAT EXCHANGER – For output and/or higher airflow. applications in a corrosive environment, this option provides a full stainless steel heat exchanger assembly. •CONVENIENCE OUTLET (POWERED/NON-POWERED)– Unit can be provided with an optional 120VAC GFCI outlet •SMOKE DETECTOR –...
  • Page 13 1041165-YTG-C-0614 Physical Data ZT037-061 Single Stage Gas Physical Data Models Component ZT037 ZT049 ZT061 Nominal Tonnage AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (MBh) 39000 54000 66000 AHRI net capacity (MBh) 38000 52000 64000 14.15 14.35 13.85 SEER 18.1 17.5 IPLV...
  • Page 14 1041165-YTG-C-0614 ZT037-061 Single Stage Gas Physical Data (Continued) Models Component ZT037 ZT049 ZT061 Nominal Tonnage CONDENSER FAN DATA Quantity of fans Fan diameter (Inch) Type Prop Prop Prop Drive type Direct ECM Direct ECM Direct ECM Quantity of motors Motor HP each No.
  • Page 15 1041165-YTG-C-0614 ZT037-061 Two Stage Gas Physical Data Models Component ZT037 ZT049 ZT061 Nominal Tonnage AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (MBh) 39000 54000 66000 AHRI net capacity (MBh) 38000 52000 64000 14.15 14.35 13.85 SEER 18.1 17.5 IPLV Nominal CFM 1200...
  • Page 16 1041165-YTG-C-0614 ZT037-061 Two Stage Gas Physical Data (Continued) Models Component ZT037 ZT049 ZT061 Nominal Tonnage CONDENSER FAN DATA Quantity of fans Fan diameter (Inch) Type Prop Prop Prop Drive type Direct ECM Direct ECM Direct ECM Quantity of motors Motor HP each No.
  • Page 17 1041165-YTG-C-0614 ZT037-061 Unit Limitations Unit Limitations Size Model Unit Voltage Applied Voltage Outdoor DB Temp (Tons) Max (°F) 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 Johnson Controls Unitary Products...
  • Page 18 1041165-YTG-C-0614 Capacity Performance ZT037-061 Cooling Capacities ZT037 High Speed Compressor (3.0 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW)
  • Page 19 1041165-YTG-C-0614 ZT037 High Speed Compressor (3.0 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 20 1041165-YTG-C-0614 ZT037 Low Speed Compressor (3.0 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW)
  • Page 21 1041165-YTG-C-0614 ZT037 Low Speed Compressor (3.0 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 22 1041165-YTG-C-0614 ZT049 High Speed Compressor (4.0 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW)
  • Page 23 1041165-YTG-C-0614 ZT049 High Speed Compressor (4.0 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 24 1041165-YTG-C-0614 ZT049 Low Speed Compressor (4.0 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW)
  • Page 25 1041165-YTG-C-0614 ZT049 Low Speed Compressor (4.0 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 26 1041165-YTG-C-0614 ZT061 High Speed Compressor (5.0 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW)
  • Page 27 1041165-YTG-C-0614 ZT061 High Speed Compressor (5.0 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 28 1041165-YTG-C-0614 ZT061 Low Speed Compressor (5.0 Ton) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh) (kW)
  • Page 29 1041165-YTG-C-0614 ZT061 Low Speed Compressor (5.0 Ton) (Continued) Temperature of Air on Condenser Coil Air on Evaporator Coil Sensible Capacity (MBh) Sensible Capacity (MBh) Total Total Total Total Capacity Input Return Dry Bulb (°F) Capacity Input Return Dry Bulb (°F) (MBh) (kW) (MBh)
  • Page 30 1041165-YTG-C-0614 Drive Selection Determine side or bottom supply duct Application. Determine desired airflow. Calculate or measure the amount of external static pressure. • Add or deduct any additional static resistanc e from “Additional Static Resistance Table”. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table.
  • Page 31 1041165-YTG-C-0614 Altitude and Temperature Correction for CFM, Static Pressure and Power. The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases.
  • Page 32 1041165-YTG-C-0614 The 1.5" static pressure given is at an elevation of 5,000 ft. The Enter the blower table at 6000 sCFM and static pressure of first step is to convert this static pressure to equivalent sea level 1.8". The rpm listed will be the same rpm needed at 5,000 ft. conditions.
  • Page 33 1041165-YTG-C-0614 Additional Static Resistance Electric Heat kW Size Model CFM Cooling Only Economizer 4” Pleated Filter (Tons) 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01 1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02 1100 0.04 -0.02 0.03 0.01 0.01 0.01...
  • Page 34 1041165-YTG-C-0614 Airflow Performance ZT037-061 Side Duct Application ZT037 (3.0 Ton) Side Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 Hp &...
  • Page 35 1041165-YTG-C-0614 ZT037-061 Bottom Duct Application ZT037 (3.0 Ton) Bottom Duct Available External Static Pressure - IWG Air Flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 Hp & Drive High Static 1.5 Hp &...
  • Page 36 1041165-YTG-C-0614 Sound Performance Indoor Sound Power Levels (3 thru 5 Ton) Indoor Sound Power Levels (Horizontal Ducted Inlet, Standard Static Belt Drive) UNIT DESCRIPTION / MODEL ZT037 / 3 Ton / Standard Static Belt Drive TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet Indoor Blower Speed (RPM) 612 - 3 Turns Open Equivalent 709 - 1 Turn Open Equivalent...
  • Page 37 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT061 / 5 Ton / Standard Static Belt Drive TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet Indoor Blower Speed (RPM) 814 - 3 Turns Open Equivalent 918 - 1 Turn Open Equivalent External Static Pressure (IWG) Airflow (CFM) 1700 1950...
  • Page 38 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT049 / 4 Ton / Standard Static Belt Drive TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge Indoor Blower Speed (RPM) 610 - 3 Turns Open Equivalent 710 - 1 Turn Open Equivalent External Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 0.37...
  • Page 39 1041165-YTG-C-0614 Indoor Sound Power Levels (Vertical Ducted Inlet, Standard Static Belt Drive) UNIT DESCRIPTION / MODEL ZT037 / 3 Ton / Standard Static Belt Drive TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 708 - 1 Turn Open Equivalent External Static Pressure (IWG) Airflow (CFM)
  • Page 40 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT061 / 5 Ton / Standard Static Belt Drive TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet Indoor Blower Speed (RPM) 812 - 3 Turns Open Equivalent 915- 1 Turn Open Equivalent External Static Pressure (IWG) Airflow (CFM) 1575 1800...
  • Page 41 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT049 / 4 Ton / Standard Static Belt Drive TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge Indoor Blower Speed (RPM) 609 - 3 Turns Open Equivalent 712 - 1 Turn Open Equivalent External Static Pressure (IWG) Airflow (CFM) Blower Motor BHP 0.32...
  • Page 42 1041165-YTG-C-0614 Indoor Sound Power Levels (Horizontal Ducted Inlet, High Static Belt Drive) UNIT DESCRIPTION / MODEL ZT037 / 3 Ton / High Static Belt Drive TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet Indoor Blower Speed (RPM) 876 - 4 Turns Open Equivalent 1,064 - 1/2 Turn Open Equivalent 1,190 - 2.5 Turns Open Equivalent External Static Pressure (IWG)
  • Page 43 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT061 / 5 Ton / High Static Belt Drive TEST CONFIGURATION Horizontal (Side Return) Ducted Inlet Indoor Blower Speed (RPM) 1,012- 5.5 Turns Open Equivalent 1,134 - 3 Turns Open Equivalent 1,174 - 2 Turns Open Equivalent External Static Pressure (IWG) Nominal Airflow (CFM) 2,000...
  • Page 44 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT049 / 4 Ton / High Static Belt Drive TEST CONFIGURATION Horizontal (Side Supply) Ducted Discharge Indoor Blower Speed (RPM) 922 - 6 Turns Open Equivalent 1,069 - 4 Turns Open Equivalent 1,165 - 2.5 Turns Open Equivalent External Static Pressure (IWG) Nominal Airflow (CFM) 1,600...
  • Page 45 1041165-YTG-C-0614 Indoor Sound Power Levels (Vertical Ducted Inlet, High Static Belt Drive) UNIT DESCRIPTION / MODEL ZT037 / 3 Ton / High Static Belt Drive TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet Indoor Blower Speed (RPM) 927 - 3 Turns Open Equivalent 1,085 - 1/2 Turn Open Equivalent 1,190 - 2.5 Turns Open Equivalent External Static Pressure (IWG)
  • Page 46 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT061 / 5 Ton / High Static Belt Drive TEST CONFIGURATION Vertical (Bottom Return) Ducted Inlet Indoor Blower Speed (RPM) 1,039 - 5 Turns Open Equivalent 1,143 - 3 Turns Open Equivalent 1,201 - 2 Turns Open Equivalent External Static Pressure (IWG) Nominal Airflow (CFM) 2,000...
  • Page 47 1041165-YTG-C-0614 UNIT DESCRIPTION / MODEL ZT049 / 4 Ton / High Static Belt Drive TEST CONFIGURATION Vertical (Bottom Supply) Ducted Discharge Indoor Blower Speed (RPM) 962 - 5.5 Turns Open Equivalent 1,092 - 3.5 Turns Open Equivalent 1,190 - 2.0 Turns Open Equivalent External Static Pressure (IWG) Nominal Airflow (CFM) 1,600...
  • Page 48 1041165-YTG-C-0614 Electrical Data ZT037-061 Standard Indoor Blower - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh (Amps)
  • Page 49 1041165-YTG-C-0614 ZT037-061 Hi Static Indoor Blower - Without Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh RLA LRA Model...
  • Page 50 1041165-YTG-C-0614 ZT037-061 Standard Indoor Blower - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh RLA LRA Model Stages...
  • Page 51 1041165-YTG-C-0614 ZT037-061 Hi Static Indoor Blower - With Powered Convenience Outlet OD Fan Supply Max Fuse Compressors Max Fuse Motors Blower Conv Electric Heat Option Breaker (each) Size w/Pwr Breaker (each) Motor Motor Outlet Volt Size w/ (Tons) (Amps) Size Pwr Exh (Amps) (Amps)
  • Page 52 1041165-YTG-C-0614 Electric Heat Multipliers Voltage kW Capacity Multipliers Nominal Applied 0.75 0.92 0.92 0.92 1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages. Johnson Controls Unitary Products...
  • Page 53 1041165-YTG-C-0614 Typical Wiring Diagrams ZT037-061 Typical Wiring Diagrams Typical ZT037-061 Cooling Unit with Gas Heat 230 Volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 54 1041165-YTG-C-0614 Typical ZT037-061 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 55 1041165-YTG-C-0614 Typical ZT037-061 Cooling Unit with/without Electric Heat Wiring Diagram Johnson Controls Unitary Products...
  • Page 56 1041165-YTG-C-0614 Weights and Dimensions ZT037-061 Unit Weights Unit 4 Point Load Weight FRONT LEFT FRONT LEFT Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) Size Model (Tons) Shipping Operating 42.4 24.7 42.5 25.5 41.6 25.5 Johnson Controls Unitary Products...
  • Page 57 1041165-YTG-C-0614 ZT037-061 Unit Accessory Weights Weight (lbs.) Unit Accessory Shipping Operating Economizer Power Exhaust Electric Heat Gas Heat Variable Frequency Drive 1. Weight given is for the maximum heater size available (24KW). 2. Weight given is for the maximum number of tube heat exchangers available (8 tube).
  • Page 58 1041165-YTG-C-0614 ZT037-061 Unit Physical Dimensions Dimension (in.) Unit Model Number ZT037, 049, 061 22 1/8 18 3/16 15 3/16 6 3/16 Detail A Detail B 3.184 Gas Pipe Inlet Ø 2.000 Gas Exhaust Vent 5-3/8 Ø 3.126 3/4” FPT 14.594 ZT037-061 Unit Clearances 7.705 Direction...
  • Page 59 1041165-YTG-C-0614 ZT037-061 Unit Bottom Duct Openings TOP VIEW 32 11/16 6 13/16 6 13/16 SUPPLY RETURN 27 1/2 LEFT RIGHT 20 1/8 19 1/8 17 1/8 12 5/16 Bottom condensate drain 14 1/2 25 9/16 Bottom gas supply entry 16 3/8 18 1/16 FRONT Bottom power, control...
  • Page 60 1041165-YTG-C-0614 ZT037-061 Unit Electrical Entry Disconnect Swith Cover Power Entry Ø 2-1/2 Control Entry Ø 7/8 Power Entry Ø 2-1/2 Convenience Outlet Cover Convenience Outlet Power Entry Ø 7/8 FRONT ZT037-061 Unit Side Duct Openings 1 8 - 1 /4 D o t P l u g s Return Supply Air...
  • Page 61 1041165-YTG-C-0614 ZT037-061 Unit Left Duct Opening 30-3/8 4-5/16 ZT037-061 Unit Accessory Dimensions ZT037-061 Roof Curb RIGHT 80-5/8 INSULATED DECK UNDER CONDENSER SECTION SUPPLY RETURN 2 TYP. 50-1/2 INSULATED DECK UNDER COMPRESSOR SECTION FRONT 8 or 14 Johnson Controls Unitary Products...
  • Page 62 1041165-YTG-C-0614 ZT037-061 Transition Roof Curb 2 TYP 23 4 30-1/2 50-1/2 80-5/8 RETURN SUPPLY 76-5/8 59-1/4 FRONT RIGHT 64-1/4 ZT037-061 Roof Curb Cutaway 2“ 3/4” X 1-1/4” WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES UNIT BASE 3.75” WOOD NAILER 3.56”...
  • Page 63 1041165-YTG-C-0614 ZT037-061 Economizer Assembly 58 1/4 88 1/4 24 3/4 Tall Units 26 1/8 Short Units 32 1/16 39 1/2 47 1/2 Fresh Air Hood For Economizer Outside Air 35 3/4 Intake Hood Relief Hood For Power Exhaust Or Barometric Relief 25 3/4 31 7/8 23 3/4...
  • Page 64 1041165-YTG-C-0614 Economizer Options Economizer Usage Application Cabinet Height Description Model Side Return Horizontal economizer without barometric relief 2EE04706024 ERV or End Return 42" Slab Economizer, 42” tall cabinet 2EE04707524 1. Barometric relief must be ordered separately and installed in duct work. 2.
  • Page 65 Slab Low Leak Economizer Power Exhaust Barometric Relief Damper Barometric Relief Hood Subject to change without notice. Printed in U.S.A. 1041165-YTG-B-0514 Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 1041165-YTG-A-0413 York International Corporation 5005 York Drive Norman, OK 73069...