Endress+Hauser Deltapilot S FMB70 Operating Instructions Manual
Endress+Hauser Deltapilot S FMB70 Operating Instructions Manual

Endress+Hauser Deltapilot S FMB70 Operating Instructions Manual

Hydrostatic level measurement profibus pa
Hide thumbs Also See for Deltapilot S FMB70:

Advertisement

Quick Links

BA00356P/00/EN/19.22-00
71556698
2022-05-04
Valid as of software version:
04.01.zz
Products
Operating instructions
Deltapilot S FMB70
Hydrostatic level measurement
PROFIBUS PA
Solutions
Services

Advertisement

loading
Need help?

Need help?

Do you have a question about the Deltapilot S FMB70 and is the answer not in the manual?

Questions and answers

Summary of Contents for Endress+Hauser Deltapilot S FMB70

  • Page 1 Products Solutions Services BA00356P/00/EN/19.22-00 71556698 2022-05-04 Valid as of software version: 04.01.zz Operating instructions Deltapilot S FMB70 Hydrostatic level measurement PROFIBUS PA...
  • Page 2 The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to this manual. Endress+Hauser...
  • Page 3 Onsite operation – onsite display connected . . . 44 Endress+Hauser operating program ..47 HistoROM®/M-DAT (optional) ....47 Locking/unlocking operation .
  • Page 4 About this document Deltapilot S FMB70 with PROFIBUS PA About this document Document function These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 5 Deltapilot S FMB70 with PROFIBUS PA About this document 1.2.4 Symbols for certain types of Information Symbol Meaning Permitted Indicates procedures, processes or actions that are allowed. A0011182 Not permitted Indicates procedures, processes or actions that are forbidden. A0011184 Indicates additional information.
  • Page 6 The manufacturer is not liable for damage caused by improper or unintended use. Clarification for borderline cases: In the case of special fluids and fluids used for cleaning, Endress+Hauser is glad to provide assistance in clarifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
  • Page 7 It meets general safety standards and legal requirements. It also conforms to the EC directives listed in the device-specific EC Declaration of Confor- mity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
  • Page 8 Identification Deltapilot S FMB70 with PROFIBUS PA Identification Product identification The measuring instrument can be identified in the following ways: • Nameplate specifications • Order code with breakdown of the device features on the delivery note • Enter the serial number from the nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All the information about the measuring instrument is...
  • Page 9 The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EC Directives. Endress+Hauser confirms the device' s conformity by affixing the CE mark.
  • Page 10 Mounting Deltapilot S FMB70 with PROFIBUS PA Mounting Incoming acceptance, storage 4.1.1 Incoming acceptance • Check the packaging and contents for any signs of damage. • Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 11 • To ensure optimum readability of the onsite display, it is possible to rotate the housing by up to 380°. → ä 15, Chap. 4.4.5 "Rotating the housing". • Endress+Hauser offers a mounting bracket for installations on pipes or walls. → ä 13, Chap. 4.4.3 "Wall and pipe mounting (optional)".
  • Page 12 Mounting Deltapilot S FMB70 with PROFIBUS PA Level measurement P01-PMP75xxx-11-xx-xx-xx-000 Fig. 1: Measuring arrangement for level • Always install the device below the lowest measuring point. • Do not install the device at the following positions: – in the filling curtain –...
  • Page 13 A0017743 Fig. 2: Process membrane Seal 4.4.3 Wall and pipe mounting (optional) Endress+Hauser offers a mounting bracket for installation on pipes or walls (for pipe diameters from 1 ¼" to 2"). ø42...60 (1.65...2.36) 122 (4.8) 140 (5.51) 158 (6.22) 175 (6.89)
  • Page 14 Mounting Deltapilot S FMB70 with PROFIBUS PA 4.4.4 Assembling and mounting the "separate housing" version r ³ 120 mm P01-FMB70xxx-11-xx-xx-xx-003 Fig. 3: "Separate housing" version In the "separate housing" version, the sensor is supplied with process connection and cable fitted.
  • Page 15 Deltapilot S FMB70 with PROFIBUS PA Mounting 4.4.5 Rotating the housing The housing can be rotated by up to 380° by loosening the setscrew. A0019996 1. T14 housing: loosen the setscrew with a 2 mm (0.08 in) Allen key. T15 and T17 housing: loosen the setscrew with a 3 mm (0.12 in) Allen key.
  • Page 16 Mounting Deltapilot S FMB70 with PROFIBUS PA 4.4.7 Mounting of the profile seal for universal process adapter For details on mounting, see KA00096F/00/A3. Post-installation check After installing the device, carry out the following checks: • Are all screws firmly tightened? •...
  • Page 17 Deltapilot S FMB70 with PROFIBUS PA Wiring Wiring Connecting the device WARNING Risk of electric shock! If the operating voltage is > 35 VDC: Dangerous contact voltage at terminals. ‣ In a wet environment, do not open the cover if voltage is present.
  • Page 18 Wiring Deltapilot S FMB70 with PROFIBUS PA 5.1.1 Connection of devices with M12 plug PIN assignment for M12 plug Meaning Signal + Not assigned Signal – Ground A0011175 5.1.2 Devices with 7/8" plug PIN assignment for 7/8" plug Meaning Signal –...
  • Page 19 Deltapilot S FMB70 with PROFIBUS PA Wiring 5.2.2 Current consumption Up to HW Version 1.10: 11 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21. As of HW Version 02.00: 13 mA ±1 mA, switch-on current corresponds to IEC 61158-2, Clause 21.
  • Page 20 Operation Deltapilot S FMB70 with PROFIBUS PA Operation Feature 20 "Output; operation" in the order code provides you with information on the operating options available to you. Version in the order code Operation PROFIBUS PA; external and LCD Via onsite display and 1 key on the exterior of the device PROFIBUS PA;...
  • Page 21 Deltapilot S FMB70 with PROFIBUS PA Operation The following table illustrates the symbols that can appear on the onsite display. Four symbols may appear at the same time. Symbol Meaning Alarm symbol – Symbol flashing: warning, device continues measuring. – Symbol permanently lit: error, device does not continue measuring.
  • Page 22 Operation Deltapilot S FMB70 with PROFIBUS PA 6.2.2 Function of operating elements – onsite display not connected Operating elements Meaning – Position adjustment (zero point correction): Press key for at least 3 seconds. If the LED on the electronic insert lights up briefly, the pressure applied has been accepted for position adjustment.
  • Page 23 Deltapilot S FMB70 with PROFIBUS PA Operation 6.2.3 Function of operating elements – onsite display connected Operating key(s) Meaning – Navigate upwards in the picklist – Edit the numerical values or characters within a function – Navigate downwards in the picklist –...
  • Page 24 6.3.2 Number of devices • The Endress+Hauser Deltapilot S devices meet the requirements of the FISCO model. • Due to the low current consumption, the following can be operated at one bus segment when installation is performed according to FISCO: Up to HW Version 1.10:...
  • Page 25 Operation You can obtain special configuration and operating programs from various manufacturers for the configuration, such as the Endress+Hauser operating program FieldCare (→ ä 44, Chap. 6.4). This operating program makes it possible to configure the PROFIBUS PA and device-specific parameters. The predefined function blocks allow uniform access to network and device data.
  • Page 26 Operation Deltapilot S FMB70 with PROFIBUS PA Table of the identification numbers: Value for "IDENT Identification Selection text Status Diagnostic NUMBER SEL" number 0x9700 0x9700 Classic status / New diagnostic messages (Profile-specific 3.x) Condensed status 0x1503 0x1503 Classic status Old diagnostic messages...
  • Page 27 Deltapilot S FMB70 with PROFIBUS PA Operation 6.3.5 Device identification and addressing Note the following: • An address must be assigned to every PROFIBUS PA device. Only when the address is configured correctly will the measuring instrument be recognized by the control system/ master.
  • Page 28 Operation Deltapilot S FMB70 with PROFIBUS PA Setting a new address via FieldCare. DIP switch 8 (SW/HW) is set to "On" (SW): Using the "Device Operation" menu, select the "Connect" option. The "Open Connection Wizard" screen is displayed. The device reports its current address. Factory setting: 126 The device has to be disconnected from the bus before you can assign the device a new address.
  • Page 29 Each device receives an ID number from the Profibus User Organization (PNO). The name of the Device Master File (GSD) is derived from this. For Endress+Hauser, this ID No. starts with the manufacturer ID "15xx". The Profile 3.02 GSD file with the "Condensed status" option is only compatible with SW 04.01.zz and must be imported individually into the configuration tool.
  • Page 30 Operation Deltapilot S FMB70 with PROFIBUS PA The Device Master Files (GSD) for Endress+Hauser devices can be acquired in the following manner: • Endress+Hauser website: http://www.endress.com → Download → Search for "GSD" • Internet PNO: http://www.profibus.com (Products – Product Guide) •...
  • Page 31 Deltapilot S FMB70 with PROFIBUS PA Operation 6.3.7 Cyclic data exchange Deltapilot S block model Measured variable Display Physical Block Sensor Signal evaluation with scaling Device-specific characteristics, e.g. software revision SEL. DISPLAY VAL. PA INPUT VALUE Main Process Value MEASURED VALUE...
  • Page 32 Operation Deltapilot S FMB70 with PROFIBUS PA Parameter description Parameter name Description OUT VALUE This parameter shows the digital output value of the Analog Input Block. Menu path FieldCare: PROFILE VIEW → ANALOG INPUT BLOCK → AI PARAMETER Menu path onsite display: GROUP SELECTION →...
  • Page 33 Deltapilot S FMB70 with PROFIBUS PA Operation Modules for the cyclic data diagram Deltapilot S makes the following modules available for the cyclic data diagram: • Main Process Value Depending on the operating mode selected, a pressure or level value is transmitted here.
  • Page 34 Operation Deltapilot S FMB70 with PROFIBUS PA Status codes Deltapilot S supports the "Condensed status" function as defined in the PNO specification. However, the "Classic" status is also supported to ensure compatibility with older devices in the S series and due to the profile-specific identification number ("0x9700").
  • Page 35 Deltapilot S FMB70 with PROFIBUS PA Operation The following "Condensed" status codes are configured via the device. Status Device status Meaning Output value (OUT 2ND CYCLIC code value) (Analog Input 1) VALUE 0010 01xx Bad Maintenance alarm, advanced diagnostics present...
  • Page 36 Operation Deltapilot S FMB70 with PROFIBUS PA 6.3.8 Acyclic data exchange Acyclic data exchange is used: • to transmit device parameters during commissioning and maintenance • to display measured variables not contained in the cyclic data diagram. Using acyclic data exchange, device parameters can be modified even when the device is involved in cyclic data exchange with a PLC.
  • Page 37 Deltapilot S FMB70 with PROFIBUS PA Operation 6.3.9 Slot/index tables The device parameters are listed in the following tables. You can access the parameters by means of the slot and index number. The individual blocks each contain standard parameters, block parameters and manufacturer-specific parameters.
  • Page 38 Operation Deltapilot S FMB70 with PROFIBUS PA Physical block Parameter Slot Index Object type Data type Size (byte) Storage class Read Write Physical Block standard parameters BLOCK OBJECT Record DS-32 STATIC REVISION NO. Simple Unsigned16 Simple Visible String STRATEGY Simple...
  • Page 39 Deltapilot S FMB70 with PROFIBUS PA Operation Parameter Slot Index Object type Data type Size (byte) Storage class Read Write PCB TEMPERATURE Simple Float Allowed Min.TEMP Simple Float Allowed Max. TEMP Simple Float PCB COUNT T>Tmax Simple Unsigned16 PCB MAX. TEMP...
  • Page 40 Operation Deltapilot S FMB70 with PROFIBUS PA Transducer Block Parameter Slot Index Object type Data type Size (byte) Storage class Read Write Transducer Block standard parameters BLOCK OBJECT Record DS-32 STATIC REVISION NO. Simple Unsigned16 Simple Visible String STRATEGY Simple...
  • Page 41 Deltapilot S FMB70 with PROFIBUS PA Operation Parameter Slot Index Object type Data type Size (byte) Storage class Read Write COUNTER T<Tmin Simple Unsigned16 MEAS. VAL. TREND Simple Unsigned8 TOTALIZER 1 Simple Visible String TOTAL. 1 OVERFLOW Simple Visible String...
  • Page 42 Operation Deltapilot S FMB70 with PROFIBUS PA Parameter Slot Index Object type Data type Size (byte) Storage class Read Write HI TRIM MEASURED Simple Float PERCENT UNIT Simple Unsigned16 X-VAL: Simple Float Y-VAL: Simple Float MASS FLOW UNIT Simple Unsigned16 SIM.
  • Page 43 Deltapilot S FMB70 with PROFIBUS PA Operation 6.3.10 Data format In the case of PROFIBUS PA, the cyclic transmission of analog values to the PLC is effected in data blocks 5 bytes long. The measured value is represented in the first 4 bytes in the form of floating point numbers in accordance with the IEEE standard.
  • Page 44 Operation Deltapilot S FMB70 with PROFIBUS PA Onsite operation – onsite display connected If the onsite display is connected, the three operating keys are used to navigate through the operating menu, → ä 23, Chap. 6.2.3 "Function of operating elements – onsite display connected".
  • Page 45 Deltapilot S FMB70 with PROFIBUS PA Operation 6.4.2 Selecting an option Example: selecting "English" as the menu language. Onsite display Operation "German" has been selected as the menu language. A  in front of the menu text indicates the option that is currently active.
  • Page 46 Operation Deltapilot S FMB70 with PROFIBUS PA 6.4.4 Editing a value Example: adjusting DAMPING VALUE function from 2.0 s to 30.0 s. → ä 23, Chap. 6.2.3 "Function of operating elements – onsite display connected". Onsite display Operation The onsite display shows the parameter to be changed.
  • Page 47 Deltapilot S FMB70 with PROFIBUS PA Operation Endress+Hauser operating program The FieldCare operating program is an Endress+Hauser asset management tool based on FDT technology. Using FieldCare, you can configure all Endress+Hauser devices and devices from other manufacturers that support the FDT standard. You can find hardware and software requirements on the Internet: www.endress.com →...
  • Page 48 Operation Deltapilot S FMB70 with PROFIBUS PA 6.6.1 Copying configuration data ➁ ➀ Zero Display Sensor S D A 0 1 2 3 4 5 6 7 8 Address HW-Version: SW-Version: P01-xxxxxxxx-19-xx-xx-xx-110 Electronic insert with optional HistoROM®/M-DAT memory module ®...
  • Page 49 Deltapilot S FMB70 with PROFIBUS PA Operation Copying configuration data from a HistoROM®/M-DAT to a device: Operation must be unlocked. Disconnect the device from the supply voltage. ® Attach the HistoROM /M-DAT module to the electronic insert. Configuration data from ®...
  • Page 50 Operation Deltapilot S FMB70 with PROFIBUS PA The table provides an overview of the locking functions: Locking via View/read Modify/write via Unlocking via parameters Onsite Remote DIP switch Onsite Remote display operation display operation DIP switch Onsite display Remote operation Parameters that refer to how the display appears, e.g.
  • Page 51 • Any customer-specific configuration carried out at the factory is not affected by a reset (customer-specific configuration remains). If, after a reset, you wish the parameters to be reset to the factory settings, please contact Endress+Hauser Service. • The OUT value may have to be rescaled after resetting with code 1, 40864 or 33333.
  • Page 52 Operation Deltapilot S FMB70 with PROFIBUS PA Reset code Description and effect 2506 PowerUp reset (warm start) – This reset resets all the parameters in the RAM. Data are read back anew from the EEPROM (processor is initialized again). – Any simulation running is terminated.
  • Page 53 Deltapilot S FMB70 with PROFIBUS PA Commissioning Commissioning The device is configured for the "level" measuring mode and level selection "Level Easy Pressure" as standard. The measuring range and the unit in which the measured value is transmitted, as well as the digital output value of the Analog Input Block OUT, correspond to the data on the nameplate.
  • Page 54 Commissioning Deltapilot S FMB70 with PROFIBUS PA Commissioning via Class 2 master (FieldCare) The procedure for commissioning and operating the FieldCare program is described in the integrated FieldCare online help. Proceed as follows to commission the device: Check the hardware write protection on the electronic insert (→ ä 49, Chap. 6.7 "Locking/unlocking operation").
  • Page 55 Deltapilot S FMB70 with PROFIBUS PA Commissioning 7.4.2 FieldCare The MEASURING MODE parameter is displayed in FieldCare in the QUICK SETUP menus and in the BASIC SETUP function group. The following measuring modes are available: • Pressure • Level The LANGUAGE parameter is arranged in the DISPLAY group.
  • Page 56 Commissioning Deltapilot S FMB70 with PROFIBUS PA Position adjustment Due to the orientation of the device, there may be a shift in the measured value, i.e. when the vessel is empty or partly filled, the measured value does not display zero. There are three ways to perform position adjustment.
  • Page 57 Deltapilot S FMB70 with PROFIBUS PA Commissioning Level measurement 7.6.1 Information on level measurement • The Level and Pressure operating modes each have a quick setup menu which guides you through the most important basic functions. → ä 59 "Quick Setup menu for the Level measuring mode".
  • Page 58 Commissioning Deltapilot S FMB70 with PROFIBUS PA 7.6.2 Overview of level measurement Measuring task LEVEL SELECTION/ Measured Description Note Measured value display LEVEL MODE variable options The measured variable is LEVEL SELECTION: Via OUTPUT UNIT – Calibration with refer- – Incorrect entries are...
  • Page 59 Deltapilot S FMB70 with PROFIBUS PA Commissioning 7.6.3 Quick Setup menu for the Level measuring mode • Some parameters are only displayed if other parameters are appropriately configured. For example, the EMPTY CALIB. parameter is only displayed in the following cases: –...
  • Page 60 Commissioning Deltapilot S FMB70 with PROFIBUS PA Onsite operation FieldCare POS. ZERO ADJUST POS. ZERO ADJUST Due to the orientation of the device, there may be a Due to the orientation of the device, there may be a shift in the measured value. You correct the shift in the measured value.
  • Page 61 Deltapilot S FMB70 with PROFIBUS PA Commissioning Pressure measurement 7.7.1 Information regarding pressure measurement • A Quick Setup menu is available for both the "Pressure" and "Level" measuring modes and guides you through the most important basic functions. You specify which Quick Setup menu should be displayed with the setting in the MEASURING MODE parameter.
  • Page 62 Commissioning Deltapilot S FMB70 with PROFIBUS PA Onsite operation FieldCare POS. ZERO ADJUST POS. ZERO ADJUST Due to the orientation of the device, there may be a Due to the orientation of the device, there may be a shift in the measured value. You correct the shift in the measured value.
  • Page 63 Deltapilot S FMB70 with PROFIBUS PA Commissioning Scaling OUT value In the Analog Input Block, the input value or input range can be scaled in accordance with the automation requirements. Example: The measuring range 0...500 mbar (7.5 psi) should be rescaled to 0...10000.
  • Page 64 Commissioning Deltapilot S FMB70 with PROFIBUS PA System units (SET UNIT TO BUS) The Deltapilot S onsite display and the MEASURED VALUE (FieldCare) show the same value as standard. The bar graph on the onsite display corresponds to the standardized value of the Analog Input Block.
  • Page 65 Deltapilot S FMB70 with PROFIBUS PA Maintenance Maintenance ® Keep the pressure compensation and GORE-TEX filter (1) free from contaminations. P01-FMB70xxx-17-xx-xx-xx-003 Exterior cleaning Please note the following points when cleaning the measuring instrument: • The cleaning agents used should not corrode the surface and the seals.
  • Page 66 → For the error messages → ä 73, Chap. 9.1.1 "Onsite display error messages". • For support and further information, please contact Endress+Hauser Service. • → See also Chap. 9.4 ff. • The PROFIBUS status is updated depending on the message type, or depending on the setting for flexible alarms.
  • Page 67 Deltapilot S FMB70 with PROFIBUS PA Troubleshooting Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 110 (A110) Alarm Failure (F) F>Checksum error in – The supply voltage is – Reestablish supply voltage. If EEPROM: disconnected when writing.
  • Page 68 Troubleshooting Deltapilot S FMB70 with PROFIBUS PA Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 Warning Function C>Linearization table Note! From software version "03.10.xx" onwards, there is no min. span (W604) check (C) not valid. Less than 2 for the Y-points.
  • Page 69 Deltapilot S FMB70 with PROFIBUS PA Troubleshooting Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 Warning Maintenance M>Configuration in – Configuration (parameters) in – Copy data from the device to the (W706) required (M) HistoROM and device the HistoROM and in the device HistoROM.
  • Page 70 Troubleshooting Deltapilot S FMB70 with PROFIBUS PA Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 718 (E718) Error Out of S>Transmitter under – The temperature measured in – Increase ambient temperature. specification temperature the electronics is smaller than Insulate device if necessary.
  • Page 71 Deltapilot S FMB70 with PROFIBUS PA Troubleshooting Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 728 (A728) Alarm Failure (F) F>RAM error – Fault in the main electronics. – Briefly disconnect device from the power supply.
  • Page 72 Troubleshooting Deltapilot S FMB70 with PROFIBUS PA Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 740 (E740) Error Maintenance M>Calculation – Level measuring mode: Level – Check configuration and required (M) overflow, bad mode* "LINd. MEASURAND.":...
  • Page 73 Deltapilot S FMB70 with PROFIBUS PA Troubleshooting Code Corresponds Message Message/description Cause Measure Prior- to NA 64 category NE 107 750 (A750) Warning Function C>Configuration not – By means of the operation – Check configuration. check (C) permitted profile, options were selected for –...
  • Page 74 Troubleshooting Deltapilot S FMB70 with PROFIBUS PA Response of outputs to errors The device differentiates between the message types "Alarm", "Warning" and "Error". → See the following table and → ä 66, Chap. 9.1 "Messages". Output A (Alarm) W (Warning)
  • Page 75 Deltapilot S FMB70 with PROFIBUS PA Troubleshooting 9.2.1 Analog Input Block If the Analog Input Block receives an input or simulation value with the status BAD, the Analog Input Block uses the failsafe mode defined in the FSAFE_TYPE parameter. The following options are available by means of the FSAFE_TYPE parameter: •...
  • Page 76 Troubleshooting Deltapilot S FMB70 with PROFIBUS PA In the FieldCare navigation window, go to PROFILE VIEW → PB Parameter In the default setting, all the bits have "Uncertain" for "Status Select Events", apart from 716. Select the "Bad" option for the row "Status Select Event 115". Press ENTER to confirm your entries.
  • Page 77 Explosion hazard! When repairing Ex-certified devices, please note the following: • Repairs to Ex-certified devices must be carried out by Endress+Hauser Service or by specialist personnel according to national regulations. • Relevant standards, national hazardous area regulations and Safety Instructions and Certificates must be observed.
  • Page 78 Technical data Deltapilot S FMB70 with PROFIBUS PA Software history Date Software version Software changes 05.2007 04.00.zz Original software. Compatible with: – FieldCare version 2.15.00 07.2013 04.01.zz Profile 3.02 Integration 9.10 Hardware history Date Hardware version Hardware changes 05.2005 Original hardware 06.2007...
  • Page 79 Deltapilot S FMB70 with PROFIBUS PA Index Acyclic data exchange ......36 Pipe mounting ........13 Alarm messages.