Products Solutions Services BA00372P/00/EN/19.22-00 71556699 2022-05-04 Valid as of software version: 04.00.zz Operating Instructions Deltapilot S FMB70 Hydrostatic level measurement FOUNDATION Fieldbus...
Page 2
The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to this manual. Endress+Hauser...
Deltapilot S FMB70 with FOUNDATION Fieldbus Table of contents About this document ....4 Scaling OUT parameter ..... 58 Configuring diagnostic behavior in Document function .
About this document Deltapilot S FMB70 with FOUNDATION Fieldbus About this document Document function These Operating Instructions contain all the information that is required in the various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
Deltapilot S FMB70 with FOUNDATION Fieldbus About this document 1.2.4 Symbols for certain types of Information Symbol Meaning Permitted Indicates procedures, processes or actions that are allowed. A0011182 Not permitted Indicates procedures, processes or actions that are forbidden. A0011184 Indicates additional information.
The manufacturer is not liable for damage caused by improper or unintended use. Clarification for borderline cases: In the case of special fluids and fluids used for cleaning, Endress+Hauser is glad to provide assistance in clarifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
It meets general safety standards and legal requirements. It also conforms to the EC directives listed in the device-specific EC Declaration of Confor- mity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
Identification Deltapilot S FMB70 with FOUNDATION Fieldbus Identification Product identification The measuring instrument can be identified in the following ways: • Nameplate specifications • Order code with breakdown of the device features on the delivery note • Enter the serial number from the nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All the information about the measuring instrument is...
The devices comply with the applicable standards and regulations as listed in the EC Declaration of Conformity and thus comply with the statutory requirements of the EC Directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
Mounting Deltapilot S FMB70 with FOUNDATION Fieldbus Mounting Incoming acceptance, storage 4.1.1 Incoming acceptance • Check the packaging and contents for any signs of damage. • Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
• To ensure optimum readability of the onsite display, it is possible to rotate the housing by up to 380°. See ä 15, section 4.4.5 "Rotating the housing". • Endress+Hauser offers a mounting bracket for installations on pipes or walls. See ä 13, section 4.4.3 "Wall and pipe mounting (optional)".
Mounting Deltapilot S FMB70 with FOUNDATION Fieldbus Level measurement P01-PMP75xxx-11-xx-xx-xx-000 Fig. 1: Measuring arrangement for level • Always install the device below the lowest measuring point. • Do not install the device at the following positions: – in the filling curtain –...
A0017743 Fig. 2: Process membrane Seal 4.4.3 Wall and pipe mounting (optional) Endress+Hauser offers a mounting bracket for installation on pipes or walls (for pipe diameters from 1 ¼" to 2"). ø42...60 (1.65...2.36) 122 (4.8) 140 (5.51) 158 (6.22) 175 (6.89)
Mounting Deltapilot S FMB70 with FOUNDATION Fieldbus 4.4.4 Assembling and mounting the "separate housing" version r ³ 120 mm P01-FMB70xxx-11-xx-xx-xx-003 Fig. 3: "Separate housing" version In the "separate housing" version, the sensor is supplied with process connection and cable fitted.
Deltapilot S FMB70 with FOUNDATION Fieldbus Mounting 4.4.5 Rotating the housing The housing can be rotated by up to 380° by loosening the setscrew. A0019996 1. T14 housing: loosen the setscrew with a 2 mm (0.08 in) Allen key. T15 and T17 housing: loosen the setscrew with a 3 mm (0.12 in) Allen key.
Mounting Deltapilot S FMB70 with FOUNDATION Fieldbus Post-installation check After installing the device, carry out the following checks: • Are all screws firmly tightened? • Are the housing covers screwed down tight? Endress+Hauser...
Deltapilot S FMB70 with FOUNDATION Fieldbus Wiring Wiring Connecting the device WARNING Risk of electric shock! If the operating voltage is > 35 VDC: Dangerous contact voltage at terminals. ‣ In a wet environment, do not open the cover if voltage is present.
Wiring Deltapilot S FMB70 with FOUNDATION Fieldbus 5.1.1 Devices with 7/8" plug PIN assignment for 7/8" plug Meaning Signal – Signal + Not assigned Shielding A0011176 Connecting the measuring unit For further information on the network structure and grounding and for further bus system components such as bus cables, see the relevant documentation, e.g.
Deltapilot S FMB70 with FOUNDATION Fieldbus Wiring Overvoltage protection (optional) NOTICE Device could be destroyed! Devices with integrated overvoltage protection must be grounded. Devices showing version "M" in feature 100 "Additional options 1" or feature 110 "Additional options 2" in the order code are equipped with overvoltage protection (see also Technical Information TI00416P "Ordering information".
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Feature 20 "Output; operation" in the order code provides you with information on the operating options available to you. Version in the order code Operation FOUNDATION Fieldbus; external operation, LCD Via onsite display and 1 key on the exterior of the device FOUNDATION Fieldbus;...
Page 21
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Parameter Measured value display Identification Function name Value number Header line Main line Unit Information line Symbol – Bargraph Bargraph Editing modes Operating keys Selection options Value that can be edited Current measured value P01-xxxxxxxx-07-xx-xx-en-011 The following table illustrates the symbols that can appear on the onsite display.
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Operating elements 6.2.1 Position of operating elements With regard to aluminum housings (T14/T15), the operating key is located either outside the device under the protective cap or inside on the electronic insert. In hygienic stainless steel housings (T17), the operating key is always located inside on the electronic insert.
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation 6.2.2 Function of operating elements – onsite display not connected Operating elements Meaning – Position adjustment (zero point correction): Press key for at least 3 seconds. If the LED on the electronic insert lights up briefly, the pressure applied has been accepted for position adjustment.
Page 24
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 6.2.3 Function of operating elements – onsite display connected Operating key(s) Meaning – Navigate upwards in the picklist – Edit the numerical values or characters within a function – Navigate downwards in the picklist –...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation FOUNDATION Fieldbus interface 6.3.1 System architecture Industrial Network FF-HSE FF-H1 FF-H1 P01-xxxxxxxx-02-xx-xx-xx-001 Fig. 8: FOUNDATION Fieldbus system architecture with associated components FF-HSE: High Speed Ethernet, FF-H1: FOUNDATION Fieldbus-H1, LD: Linking Device FF-HSE/FF-H1, PS: bus power supply unit, SB: safety barrier, BT: bus terminator The following system connection options are possible: –...
6.3.2 Number of devices • The Endress+Hauser Deltapilot S devices meet the requirements of the FISCO model. • Due to the low current consumption, the following can be operated at one bus segment when installation is performed according to FISCO: –...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation 6.3.5 Device identification and addressing FOUNDATION Fieldbus identifies the device using its ID code and automatically assigns it a suitable field address. The identity code cannot be changed. The device appears in the network display once you have started the FF configuration program and integrated the device into the network.
Page 28
The guideline provides an overview of the standard function blocks that are described in FOUNDATION Fieldbus Specifications FF 890 - 894. It is designed as an aid when using these blocks that are implemented in the Endress+Hauser field devices. Endress+Hauser...
Page 29
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Default (as-delivered) block configuration The block model shown below illustrates the block configuration when the device is delivered. Measured variable Sensor Display Resource Block with scaling Signal evaluation Primary value Pressure Analog Input Block 1...
Page 30
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 6.3.7 Assignment of Transducer Blocks (CHANNEL) Settings for the Analog Input Block Process variable Transducer Block Parameter name CHANNEL parameter in the Analog Input Block Primary Value, a pressure or Pressure Transducer PRIMARY_VALUE/...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Discrete Input Block settings Alarm conditions Transducer Block Parameter name Parameter CHANNEL, Discrete Input Block General device error Configuration error Sensor over pressure Sensor low pressure Sensor over temperature Sensor under temperature Process membrane broken...
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 6.3.8 Index tables of Endress+Hauser parameters The following tables list the manufacturer-specific device parameters for the Resource Block, the Transducer Blocks and the Analog Input Blocks. For the FF parameters, see either the FF specification or Operating Instructions BA00303P "Description of Device Functions,...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Pressure Transducer Block Parameter name, Parameter name, Index Data type Size Storage Read Write MODE_BLK Reset codes option "Symbolic name" option "Label" [byte] Class MEASURED_TEMPERATURE Temperature DS-65 MEASURED_TEMPERATURE_UNIT Temp. eng. unit Unsigned16 DEVICE_DIALOG...
Page 34
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Parameter name, Parameter name, Index Data type Size Storage Read Write MODE_BLK Reset codes option "Symbolic name" option "Label" [byte] Class SENSOR_MEAS_TYPE Sensor meas. type Unsigned16 LEVEL_SELECTION Level selection Unsigned8 7864, 333 HEIGHT_UNIT_EASY...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Display Transducer Block Parameter name, Parameter name, Index Data type Size Storage Read Writ BLK_MODE Reset codes option "Symbolic name" option "Label" [byte] Class DEVICE_DIALOG Device dialog Unsigned8 DISPLAY_MAINLINE_CONTENT Main line cont. Unsigned8...
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Parameter name, Parameter name, Index Data type Size Storage Read Write BLK_MODE Reset codes option "Symbolic name" option "Label" [byte] Class FF912_STATUS_SELECT4 Status Select Event 717 Enumerated AUTO, OOS, 7864 FF912_STATUS_SELECT5 Status Select Event 718...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Onsite operation – onsite display connected If the onsite display is connected, the three operating keys are used to navigate through the operating menu, ä 24, section 6.2.3 "Function of operating elements – onsite display connected".
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 6.4.2 Selecting an option Example: Selecting the "Pressure" measuring mode. Onsite display Operation "Level" has been selected as the measuring mode. A in front of the menu text indicates the option that is currently active.
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Onsite display Operation Keep pressing "+" or "–" until "0" is displayed. 2. Confirm "0" with "E". The cursor jumps to the next position. is displayed and is highlighted in black. See next graphic.
FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. You can find hardware and software requirements on the Internet: www.endress.com Search: FieldCare FieldCare ...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation 6.6.1 Copying configuration data ➁ ➀ Zero Display Sensor OUNDATION HW-Version: SW-Version: P01-xxxxxxxx-19-xx-xx-xx-123 Electronic insert with optional HistoROM®/M-DAT memory module ® Optional HistoROM /M-DAT To copy configuration data from the HistoROM/ ® M-DAT to a device or from a device to a HistoROM ®...
Page 42
Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Copying configuration data from a HistoROM®/M-DAT to a device: Operation must be unlocked. Disconnect the device from the supply voltage. ® Attach the HistoROM /M-DAT module to the electronic insert. Configuration data from ®...
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Locking/unlocking operation Once you have entered all the parameters, you can lock your entries against unauthorized and undesired access. You have the following possibilities for locking/unlocking operation: • Via the DIP switch on the electronic insert, locally at the device.
• Any customer-specific configuration carried out at the factory is not affected by a reset (customer-specific configuration remains). If, after a reset, you wish the parameters to be reset to the factory settings, please contact Endress+Hauser Service. • The OUT Value may have to be rescaled after resetting with code 7864.
Page 45
Deltapilot S FMB70 with FOUNDATION Fieldbus Operation 6.9.2 Performing reset via the FieldCare operating program If operating via FieldCare, enter the code via the ENTER RESET CODE parameter (menu path: OPERATING MENU OPERATION). The following table illustrates which parameters are reset by the particular reset codes.
Page 46
– The device is restarted. The table uses the group and parameter names as they appear in Field Care. See ä 32, section 6.3.8 "Index tables of Endress+Hauser parameters" for the assignment of the FieldCare parameter names and the FF configuration program.
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Commissioning The device is configured for the "Level" measuring mode as standard. The measuring range and the unit in which the measured value is transmitted correspond to the data on the nameplate. WARNING...
Page 48
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Identify the device using the DEVICE_ID (see Point 2). Assign the desired tag name to the device by means of the PD_TAG parameter. Configuring the Resource Block Open the Resource Block. If necessary, disable the lock for device operation. See ä 43, section 6.7 "Locking/ unlocking operation".
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Enter the alarm and critical alarm messages by means of the HI_HI_LIM, HI_LIM, LO_LIM and LO_LO_LIM parameters. The limit values entered have to be within the value range specified for the OUT_SCALE parameter.
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus 7.4.2 Selecting the language and measuring mode by means of the FieldCare operating program Selecting the measuring mode WARNING Changing the measuring mode affects the span (URV)! This situation can result in product overflow.
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Position adjustment Due to the orientation of the device, there may be a shift in the measured value, i.e. when the vessel is empty or partly filled, the measured value does not display zero. There are two ways to perform position adjustment.
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Level measurement 7.6.1 Information on level measurement • A Quick Setup menu is available for each of the measuring modes Pressure and Level which guides you through the most important basic functions. See ä 54 for the "Level"...
Page 53
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning 7.6.2 Overview of level measurement Measuring task LEVEL SELECTION/ Measured Description Note Measured value display LEVEL MODE variable options The measured variable is LEVEL SELECTION: Via OUTPUT UNIT – Calibration with refer- – Incorrect entries are...
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus 7.6.3 Quick Setup menu for the Level measuring mode • Some parameters are only displayed if other parameters are appropriately configured. For example, the EMPTY CALIB. parameter is only displayed in the following cases: –...
Page 55
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Onsite operation FieldCare POS. ZERO ADJUST POS. ZERO ADJUST Due to the orientation of the device, there may be a Due to the orientation of the device, there may be a shift in the measured value. You correct the shift in the measured value.
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Pressure measurement 7.7.1 Information regarding pressure measurement • A Quick Setup menu is available for both the "Pressure" and "Level" measuring modes and guides you through the most important basic functions. You specify which Quick Setup menu should be displayed with the setting in the MEASURING MODE parameter.
Page 57
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Onsite operation FieldCare POS. INPUT VALUE POS. INPUT VALUE Due to the orientation of the device, there may be a Due to the orientation of the device, there may be a shift in the measured value. Specify the desired set shift in the measured value.
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Scaling OUT parameter In the Analog Input Block, the input value or input range can be scaled in accordance with the automation requirements. Example: The measuring range 0 to 500 mbar (0 to 7.5 psi) should be rescaled to 0 to 100 %.
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Configuring diagnostic behavior in accordance with FOUNDATION Fieldbus Specification FF912 Field Diagnostic Profile The device complies with FOUNDATION Fieldbus specification FF912. Among other things this means that: • The diagnostic category as per NAMUR Recommendation NE 107 is transmitted over the fieldbus in a format that is independent of the manufacturer: –...
Page 60
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Event severity Default Event source Events in this group event category High severity Function check (C) Sensor • Not used Electronics • 704: C>Measurement error • 746: C>Sensor connection error - initializing Configuration •...
Page 61
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning 7.9.2 Assignment parameters Event categories are assigned to the event groups via four assignment parameters. These parameters are located in the RESOURCE (RB2) Block: • FD_FAIL_MAP: for event category Failure (F) • FD_CHECK_MAP: for event category Function check (C) •...
Page 62
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Example The Highest Severity / Electronics group contains the events 131: Checksum error in EEPROM: min/max segment, among others. These should no longer be categorized as Failure (F), and should be categorized as Function check (C) instead.
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning 7.9.3 Configurable area The event category can be individually defined for the following events - irrespective of the event group they are assigned to in the default setting: • 115: Sensor overpressure • 120: Sensor low pressure •...
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Select the "Configurable area" tab. In the factory setting, all the bits in the Configurable Area Bits column have the value not assigned (A). (A) (B) Select one of these bits (here Configurable Area Bit 15, for instance) and select the Sensor overpressure (B) option from the associated picklist.
Page 65
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning The "Simulation" tab makes it possible to simulate an event. Endress+Hauser...
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus 7.9.4 Transmission of independent event messages on the bus Event priority Event messages are only transmitted on the bus if their priority is between 2 and 15. Priority 1 events are displayed but are not transmitted on the bus. Priority 0 events are ignored. All events are assigned the priority 0 in the factory setting.
Page 67
Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning 7.9.5 Overview of the settings made and the current events In the FieldCare navigation window, go to Diagnostics Alarm Indication (Polling) The following overview is displayed: – "Troubleshooting information" if an event has occurred –...
Page 68
Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus To change the measured value status (Bad, Uncertain, Good) assigned to an event, select the desired status from the picklist. Example The status "Bad" should be used for error 115 "Sensor overpressure" instead of the status "Uncertain".
Deltapilot S FMB70 with FOUNDATION Fieldbus Maintenance Maintenance ® Keep the pressure compensation and GORE-TEX filter (1) free from contamination. P01-FMB70xxx-17-xx-xx-xx-003 Exterior cleaning Please note the following points when cleaning the measuring instrument: • The cleaning agents used should not corrode the surface and the seals.
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Troubleshooting 9.1.1 General errors Error Possible cause Remedy Device is not Supply voltage does not match the value Connect the correct voltage. responding. indicated on the nameplate. The polarity of the supply voltage is wrong. Reverse polarity of supply voltage.
See ä 71, section 9.2.2 "Onsite display error messages" for the error messages. • For support and further information, please contact Endress+Hauser Service. • If the category of a diagnostic event is being changed, an empty field might be displayed instead of "F, C, S, M".
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Message Measure Initialization, VU Electr. Defect A110 Replace onsite display. Initialization, VU Electr. Defect A114 Initialization, VU Electr. Defect A281 Initialization, VU Checksum Err. A110 Initialization, VU Checksum Err. A112 Initialization, VU Checksum Err. A171 Initialization Supply voltage too low.
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Diagnostic messages in the DIAGNOSTIC Transducer Block (TRDDIAG) • The Actual Diagnostics parameter shows the message with the highest priority. Every message is also displayed as per the FOUNDATION Fieldbus Specification by means of the XD_ERROR and BLOCK_ERROR parameters.
Page 74
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Alarm Electronics failure Sensor failure BAD_DEVICE_FAILURE Pressure, Level, Flow Electronics failure Sensor failure BAD_DEVICE_FAILURE Pressure, Level, Flow Electronics failure Other BAD_DEVICE_FAILURE Pressure, Level, Flow Electronics failure Other BAD_DEVICE_FAILURE Pressure, Level, Flow...
Page 75
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Configuration error 0 Other GOOD Pressure, Level, Flow None Configuration error 0 Other GOOD Pressure, Level, Flow None Warning General error Other STATUS_UNCERTAIN Pressure, Level, Flow General error Other GOOD Pressure, Level, Flow...
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Overview of diagnostic events 9.5.1 Failure (F) Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm F>Sensor electronic – Electromagnetic effects are – Wait a few minutes.
Page 77
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm F>Sensor connection – Electromagnetic effects are – Block off electromagnetic error, cycle disturbance greater than specifications in effects or eliminate source of the technical data.
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm F>Memory failure in – Electromagnetic effects are – Block off electromagnetic signal processor greater than specifications in effects or eliminate source of the technical data.
Page 79
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm C>LRV or URV out of – Lower range value and/or – Reconfigure lower range...
Page 80
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Warning C>Configuration not – By means of the operation – Check configuration. permitted profile, options were selected –...
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting 9.5.3 Maintenance required (M) Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Warning M>Checksum error in – Main electronics defect. – Replace main electronics.
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm/ M>Calculation – Level measuring mode: the – Check configuration and carry warning overflow, bad...
Page 83
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm/ S>Sensor – The temperature measured in – Increase process warning under temperature the sensor is less than the...
Page 84
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostic Failure Message/ BLOCK_ Cause Measure Priori code mode description ERROR ERROR Value Bit Value Bit Alarm/ S>Tmin ALARM – Temperature measured value – Check system/temperature warning WINDOW has undershot the value measured value.
Deltapilot S FMB70 with FOUNDATION Fieldbus Diagnostics and troubleshooting Response of outputs to errors The device makes a distinction between the output behavior "Alarm", "Warning" and "Error". See the following table and ä 71, section 9.2 "Diagnostic information on onsite display".
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus 9.6.1 Analog Input Block If the Analog Input Block receives an input or simulation value with the status BAD, the Analog Input Block uses the failure mode defined in the FSAFE_TYPE parameter.
Explosion hazard! When repairing Ex-certified devices, please note the following: • Repairs to Ex-certified devices must be carried out by Endress+Hauser Service or by specialist personnel according to national regulations. • Relevant standards, national hazardous area regulations and Safety Instructions and Certificates must be observed.
Diagnostics and troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus 9.13 Software history Date Software version Software changes 08.2008 03.00.zz Original software. Compatible with: – FieldCare version 2.15.00 01.2013 04.00.zz FF912 Field Diagnostic Profile Integration Endress+Hauser...
Deltapilot S FMB70 with FOUNDATION Fieldbus Technical data Technical data For technical data, please refer to Technical Information Deltapilot S TI00416P. Appendix 11.1 Assignment of English parameter names on the onsite display Display German parameter name English parameter name EINHEIT DICHTE DENSITY UNIT EINHEIT HÖHE...
Page 90
Appendix Deltapilot S FMB70 with FOUNDATION Fieldbus Display German parameter name English parameter name FAKT. BEN. EINH. S1 FACT. U.U. TOTAL.1 FAKT. BEN. EINH. S2 FACT. U.U. TOTAL.2 Pmin PROZESS Pmin ALARM WINDOW Pmax PROZESS Pmax ALARM WINDOW Tmin PROZESS...
Page 91
Deltapilot S FMB70 with FOUNDATION Fieldbus Appendix Display German parameter name English parameter name SENSOR DRUCK – Betriebsart "Füllstand" SENSOR PRESSURE – "Level" measuring mode MINIMALE SPANNE MINIMUM SPAN AUSWAHL ALARME SELECT ALARMTYPE AUSWAHL ALARME SELECT ALARMTYPE RESET MELDUNGEN RESET ALL ALARMS FAKT.
Page 92
Appendix Deltapilot S FMB70 with FOUNDATION Fieldbus Display German parameter name English parameter name AI 3 OUT Value AI 3 OUT Value AI 2 OUT Value AI 2 OUT Value AI 1 OUT Value AI 1 OUT Value DEVICE ADDRESS...