Endress+Hauser Deltapilot S FMB70 Operating Instructions Manual
Endress+Hauser Deltapilot S FMB70 Operating Instructions Manual

Endress+Hauser Deltapilot S FMB70 Operating Instructions Manual

Hydrostatic level measurement
Hide thumbs Also See for Deltapilot S FMB70:

Advertisement

Quick Links

Operating Instructions
Deltapilot S FMB70
Hydrostatic Level Measurement
9
BA372P/00/EN/06.09
71095403
Valid from software version:
03.00.zz

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Deltapilot S FMB70 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Endress+Hauser Deltapilot S FMB70

  • Page 1 Operating Instructions Deltapilot S FMB70 Hydrostatic Level Measurement BA372P/00/EN/06.09 71095403 Valid from software version: 03.00.zz...
  • Page 2 Overview of documentation Deltapilot S FMB70 with FOUNDATION Fieldbus Overview of documentation Device Documentation Content Remarks Deltapilot S Technical Information TI416P Technical data – The documentation can be found on the FOUNDATION Fieldbus documentation CD supplied. Operating Instructions BA372P – Identification –...
  • Page 3: Table Of Contents

    Deltapilot S FMB70 with FOUNDATION Fieldbus Table of contents Table of contents Safety instructions ....4 Confirming messages ..... . . 65 Repair .
  • Page 4: Safety Instructions

    Safety instructions Deltapilot S FMB70 with FOUNDATION Fieldbus Safety instructions Designated use The Deltapilot S is a hydrostatic pressure sensor for measuring pressure and level. The manufacturer accepts no liability for damages resulting from incorrect use or use other than that designated.
  • Page 5: Notes On Safety Conventions And Icons

    Deltapilot S FMB70 with FOUNDATION Fieldbus Safety instructions Notes on safety conventions and icons In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding icon in the margin.
  • Page 6: Identification

    Identification Deltapilot S FMB70 with FOUNDATION Fieldbus Identification Device designation 2.1.1 Nameplates Note! • The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference temperature of 20°C (68°F) or 100°F for ANSI flanges. • The pressure values permitted at higher temperatures can be found in the following standards: –...
  • Page 7 Deltapilot S FMB70 with FOUNDATION Fieldbus Identification Devices for use in hazardous areas are fitted with an additional nameplate. Dat.: P01-xMD7xxxx-18-xx-xx-xx-002 Fig. 2: Additional nameplate for devices for hazardous areas EC type-examination certificate number Type of protection e.g. II 1/2 G EEx ia IIC T4/T6 Electrical data Safety Instructions number e.g.
  • Page 8 Identification Deltapilot S FMB70 with FOUNDATION Fieldbus Hygenic stainless steel housing (T17) Deltapilot S Made in Germany, D-79689 Maulburg Order Code: Ser.-No.: Span Mat. Dat.: Bei Sauerstoffeinsatz/for oxygen service: Tmax Pmax P01-FMB70xxx-18-xx-xx-xx-001 Fig. 4: Nameplate for Deltapilot S Order code See the specifications on the order confirmation for the meanings of the individual letters and digits.
  • Page 9: Scope Of Delivery

    The devices comply with the applicable standards and regulations as listed in the EC Declaration of Conformity and thus comply with the statutory requirements of the EC Directives. Endress+Hauser confirms the conformity of the device by affixing to it the CE mark.
  • Page 10: Installation

    • To ensure optimal readability of the onsite display, it is possible to rotate the housing up to 380°. → ä 14, Section 3.3.5 "Rotating the housing". • Endress+Hauser offers a mounting bracket for installations on pipes or walls. → ä 12, Section 3.3.3 "Wall and pipe-mounting (optional)".
  • Page 11 Deltapilot S FMB70 with FOUNDATION Fieldbus Installation 3.3.1 Installation instructions Note! • Do not clean or touch the process isolating diaphragm with hard or pointed objects. • If a heated Deltapilot S is cooled during the cleaning process (e.g. by cold water), a vacuum develops for a short time, whereby moisture can penetrate the sensor through the pressure compensation (1).
  • Page 12 3.3.3 Wall and pipe-mounting (optional) Endress+Hauser offers a mounting bracket for installations on pipes or walls. P01-PMx7xxxx-06-xx-xx-xx-001 Please note the following when mounting: • When mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at least 5 Nm.
  • Page 13 Deltapilot S FMB70 with FOUNDATION Fieldbus Installation 3.3.4 Assembling and mounting the "separate housing" version r ³ 120 mm P01-FMB70xxx-11-xx-xx-xx-003 Fig. 7: "Separate housing" version In the "separate housing" version, the sensor is supplied with the process connection and cable ready-fitted.
  • Page 14: Post-Installation Check

    Installation Deltapilot S FMB70 with FOUNDATION Fieldbus 3.3.5 Rotating the housing The housing can be rotated up to 380° by loosening the setscrew. max. 380° P01-FMB70xxx-17-xx-xx-xx-000 Fig. 8: Aligning the housing – For aluminum housings (T14/T15): Loosen setscrew with a 2 mm Allen key.
  • Page 15: Wiring

    Deltapilot S FMB70 with FOUNDATION Fieldbus Wiring Wiring Connecting the device Note! • When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings.
  • Page 16: Connecting The Measuring Unit

    Wiring Deltapilot S FMB70 with FOUNDATION Fieldbus 4.1.1 Connecting devices with 7/8" connectors – + – 7/8” – P01-xxx7xxxx-04-xx-xx-xx-003 Fig. 11: Left: electrical connection for devices with 7/8" connector Right: view of the connector at the device Connecting the measuring unit...
  • Page 17: Overvoltage Protection (Optional)

    Deltapilot S FMB70 with FOUNDATION Fieldbus Wiring 4.2.4 Grounding and shielding Deltapilot S must be grounded, for example by means of the external ground terminal. Different grounding and shielding installation methods are available for FOUNDATION Fieldbus networks such as: • Isolated installation (see also IEC 61158-2) •...
  • Page 18: Operation

    Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Feature 20 "Output; operation" in the order code provides you with information on the operating options available to you. Versions in the order code Operation FOUNDATION Fieldbus; external operation, LCD Via onsite display and 1 key on the exterior of the device FOUNDATION Fieldbus;...
  • Page 19 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation The following table illustrates the symbols that can appear on the onsite display. Four symbols can occur at one time. Symbol Meaning Alarm symbol – Symbol flashing: warning, device continues measuring. – Symbol permanently lit: error, device does not continue measuring.
  • Page 20: Operating Elements

    Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Operating elements 5.2.1 Position of the operating elements On the aluminum housing (T14/T15), the operating key is located either under the protective flap on the exterior of the device or inside on the electronic insert. In the case of the hygenic stainless steel housing (T17), the operating key is always inside on the electronic insert.
  • Page 21 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation 5.2.2 Function of the operating elements – onsite display not connected Operating elements Meaning – Position adjustment (zero point correction): press key for at least 3 seconds. The LED on the electronic insert lights up briefly if the pressure applied has been accepted for position adjustment.
  • Page 22 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 5.2.3 Function of the operating elements – onsite display connected Key(s) Meaning – Navigate upwards in the picklist – Edit numerical values or characters within a function – Navigate downwards in the picklist –...
  • Page 23: Foundation Fieldbus Interface

    Deltapilot S FMB70 with FOUNDATION Fieldbus Operation FOUNDATION Fieldbus interface 5.3.1 System architecture Industrial Network FF-HSE FF-H1 FF-H1 P01-xxxxxxxx-02-xx-xx-xx-001 Fig. 14: FOUNDATION Fieldbus system architecture with associated components FF-HSE: High Speed Ethernet, FF-H1: FOUNDATION Fieldbus-H1, LD: Linking Device FF-HSE/FF-H1, PS: bus power supply unit, SB: safety barrier, BT: bus terminator The system can be connected in the following ways: –...
  • Page 24 You can obtain special configuration and operating programs from various manufacturers for the configuration, such as the FieldCare operating program from Endress+Hauser → ä 38, Section 5.5 "FieldCare". These configuration programs make it possible to configure FF functions and all the device-specific parameters.
  • Page 25 Typical Deltapilot S display in a configuration program after the connection has been established. Device name Serial number Device ID, consisting of ID code for Endress+Hauser (452B48), ID code for Deltapilot S (100B) and 11-digit serial number 5.3.6 Deltapilot S block model With FOUNDATION Fieldbus, all the device parameters are categorized according to their functional properties and task and are generally assigned to three different blocks.
  • Page 26 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Deltapilot S has the following blocks: • Resource Block (device block) • 4 Transducer Blocks – Pressure Transducer Block This Block supplies the output variables PRIMARY_VALUE and SECONDARY_VALUE. It contains all the parameters to configure the measuring device for the measuring task such as measuring mode selection, linearization function and unit selection.
  • Page 27 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Block configuration when device is delivered The block model shown below illustrates the block configuration when the device is delivered. Measured variable Sensor Display Resource Block with scaling Signal evaluation Primary value Pressure...
  • Page 28 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 5.3.7 Assignment of Transducer Blocks (CHANNEL) Settings for the Analog Input Block Process variable Transducer Block Parameter name CHANNEL parameter in the Analog Input Block Primary Value, a pressure or level Pressure Transducer Block PRIMARY_VALUE...
  • Page 29 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Discrete Input Block settings Alarm conditions Transducer Block Parameter name Parameter CHANNEL, Discrete Input Block General device error Configuration error Sensor overpressure Sensor underpressure Sensor overtemperature Sensor undertemperature Process isolating diaphragm brocken Electronic overtemperature...
  • Page 30 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 5.3.8 Index tables of Endress+Hauser parameters The following tables list the manufacturer-specific device parameters for the Resource Block, the Transducer Blocks and the Analog Input Blocks. For the FF parameters, see either the FF specification or Operating Instructions BA303P "Description of Device Functions, Cerabar S/...
  • Page 31 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Pressure Transducer Block Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write MODE_BLK Reset parameter" option and (Byte) Class codes display in FieldCare DEVICE_DIALOG DEVICE DIALOG Unsigned8...
  • Page 32 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write MODE_BLK Reset parameter" option and (Byte) Class codes display in FieldCare LEVEL_MEASUREMENT_DENSITY_EASY PROCESS DENSITY Float 7864, 333 MEASURED_ACTUAL_LEVEL_EASY MEAS.
  • Page 33 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Display Transducer Block Parameter name as per DD Parameter name, "Label Index Data type Size Storage Read Write BLK_MODE Reset codes parameter" option and (Byte) Class display in FieldCare DEVICE DIALOG DEVICE DIALOG...
  • Page 34 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 5.3.9 Methods The FOUNDATION Fieldbus Specification includes the use of methods to make device operation easier. A method is a sequence of interactive steps to be carried out in the specified order so as to configure certain device functions.
  • Page 35: Local Operation

    Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Local operation – onsite display connected If the onsite display is connected, the three operating keys are used to navigate through the operating menu, → ä 22, Section 5.2.3 "Function of the operating elements – onsite display connected".
  • Page 36 Operation Deltapilot S FMB70 with FOUNDATION Fieldbus 5.4.2 Selecting an option Example: selecting "English" as the menu language. Onsite display Operation "German" has been selected as the menu language. The option currently active is indicated by a ✓ in front of the menu text.
  • Page 37 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation Onsite display Operation Press "E" to save the new value and exit the editing mode. → See next graphic. P01-xxxxxxxx-19-xx-xx-en-031 The new value for the damping is 30.0 s. – Go to the next parameter with "E".
  • Page 38: Fieldcare

    Operation Deltapilot S FMB70 with FOUNDATION Fieldbus FieldCare FieldCare is Endress+Hauser's plant asset management tool based on FDT technology. You can use FieldCare to configure all Endress+Hauser devices as well as third-party devices which support the FDT standard. FieldCare supports the following functions: •...
  • Page 39 Deltapilot S FMB70 with FOUNDATION Fieldbus Operation 5.6.1 Copying configuration data ➁ ➀ Zero Display Sensor OUNDATION HW-Version: SW-Version: P01-xxxxxxxx-19-xx-xx-xx-123 ® Electronic insert with optional HistoROM /M-DAT memory module ® Optional HistoROM /M-DAT ® ® To copy configuration data from the HistoROM/...
  • Page 40: Locking/Unlocking Operation

    Operation Deltapilot S FMB70 with FOUNDATION Fieldbus ® Copying configuration data from a HistoROM /M-DAT to a device: Note! Operation must be unlocked. Disconnect the device from the supply voltage. ® Attach the HistoROM /M-DAT to the electronic insert. Configuration data from another ®...
  • Page 41: Simulation

    Deltapilot S FMB70 with FOUNDATION Fieldbus Operation The table provides an overview of the locking functions: Locking via View/ Modify/write via Unlocking via read On-site Remote DIP-Switch On-site Remote parameter display operation display operation DIP-Switch On-site display Remote operation Parameters which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST can still be altered.
  • Page 42: Factory Setting (Reset)

    Operation Deltapilot S FMB70 with FOUNDATION Fieldbus Enter the value and status for the SIMULATION_VALUE and SIMULATION_STATUS elements. During the simulation, the output value and status of the Pressure Transducer Block are replaced by the simulated value and status. The OUT parameter shows the result.
  • Page 43 – The device is restarted. The table uses the group and parameter names as they appear in Field Care. See → ä 30, Section 5.3.8 "Index tables of Endress+Hauser parameters" for the assignment of the FieldCare parameter names and the FF configuration program.
  • Page 44: Commissioning

    Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Warning! • If a pressure that is lower than the minimum permitted pressure is present at the device, messages "E120 sensor low pressure" and "E727 sensor pressure error - overrange" are output in succession.
  • Page 45 Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Configuring the Resource Block Open the Resource Block. If necessary, disable the lock for device operation. See → ä 40, Section 5.7 "Locking/ unlocking operation". Operating is unlocked as standard. If necessary, change the block name. Factory setting: RS_452B481007-xxxxxxxxxxx If necessary, assign a description to the block by means of the TAG_DESC parameter.
  • Page 46: Selecting The Language And Measuring Mode

    Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Specify the alarm priorities by means of the HI_HI_PRI, HI_PRI, LO_LO_PRI and LO_PRI parameters. Reporting to the field host system only takes place with alarms with a priority greater than 2. Set the block mode to Auto using the MODE_BLK parameter, TARGET element. For this purpose, the Resource Block must also be set to the "Auto"...
  • Page 47: Position Adjustment

    Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Position adjustment Due to the orientation of the device, there may be a shift in the measured value, i.e. when the container is empty or partly filled, the measured value parameter does not display zero. There are two options to choose from when performing position adjustment.
  • Page 48: Level Measurement

    Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Level measurement 6.5.1 Information on level measurement Note! • A Quick Setup menu is available for each of the measuring modes Pressure and Level which guides you through the most important basic functions. → For the "Level" Quick Setup menu, see →...
  • Page 49 Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning 6.5.2 Overview of level measurement Measuring task LEVEL Measured variable Description Comment Measured value display SELECTION/ selection LEVEL MODE The measured variable is LEVEL SELECTION: Via the OUTPUT – Calibration with – Incorrect entries are...
  • Page 50 Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus 6.5.3 Quick Setup menu for the Level measuring mode Note! • Some parameters are only displayed if other parameters are appropriately configured. For example, the EMPTY CALIBRATION parameter is only displayed in the following instances: –...
  • Page 51 Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Local operation FieldCare POS. ZERO ADJUST POS. ZERO ADJUST Due to orientation of the device, there may be a shift in Due to orientation of the device, there may be a shift in the measured value.
  • Page 52: Pressure Measurement

    Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Pressure measurement 6.6.1 Information on pressure measurement Note! • A Quick Setup menu is available for each of the measuring modes Pressure and Level which guides you through the most important basic functions. With the setting in the MEASURING MODE parameter, you specify which Quick Setup menu should be displayed.
  • Page 53 Deltapilot S FMB70 with FOUNDATION Fieldbus Commissioning Local operation FieldCare POS. INPUT VALUE POS. INPUT VALUE Due to orientation of the device, there may be a shift in Due to orientation of the device, there may be a shift in the measured value.
  • Page 54: Scaling The Out Parameter

    Commissioning Deltapilot S FMB70 with FOUNDATION Fieldbus Scaling the OUT parameter In the Analog Input Block, the input value or input range can be scaled in accordance with the automation requirements. Example: The measuring range 0 to 500 mbar should be rescaled to 0 to 100 %.
  • Page 55: Maintenance

    Deltapilot S FMB70 with FOUNDATION Fieldbus Maintenance Maintenance ® Keep the pressure compensation and GORE-TEX filter (1) free from contamination. P01-FMB70xxx-17-xx-xx-xx-003 Exterior cleaning Please note the following points when cleaning the device: • The cleaning agents used should not attack the surface and the seals.
  • Page 56: Troubleshooting

    • If the device detects a defect in the onsite display during initialization, special error messages are generated. → For the error messages, → ä 63, Section 8.1.1 "Onsite display error messages". • For support and further information, please contact Endress+Hauser Service. • → See also Section 8.4, Section 8.5 and Section 8.6.
  • Page 57 Deltapilot S FMB70 with FOUNDATION Fieldbus Troubleshooting Code Error Message/ BLOCK Cause Measure Prio type/ Description ERROR ERROR rity NA 64 Value Value 113 (A113) Alarm B>ROM failure in – Main electronics defect. – Replace main electronics. transmitter electronic 115 (E115) Error C>Sensor overpressure...
  • Page 58 Troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Code Error Message/ BLOCK Cause Measure Prio type/ Description ERROR ERROR rity NA 64 Value Value 702 (W702) Warning C>HistoROM data not – Data were not written correctly to – Repeat upload. consistent.
  • Page 59 Deltapilot S FMB70 with FOUNDATION Fieldbus Troubleshooting Code Error Message/ BLOCK Cause Measure Prio type/ Description ERROR ERROR rity NA 64 Value Value 713 (A713) Alarm B>100% POINT – The sensor was replaced. – Carry out calibration again. (LEVEL_100_PERCENT_ VALUE) level out of edit...
  • Page 60 Troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Code Error Message/ BLOCK Cause Measure Prio type/ Description ERROR ERROR rity NA 64 Value Value 723 (A723) Alarm B B>MAX. FLOW – FLOW_TYPE has been changed – Carry out calibration again. (SCALE_OUT, EU_100)
  • Page 61 Deltapilot S FMB70 with FOUNDATION Fieldbus Troubleshooting Code Error Message/ BLOCK Cause Measure Prio type/ Description ERROR ERROR rity NA 64 Value Value – Loose connection at sensor cable. – Wait a short period of time and tighten the connection, or avoid loose connection.
  • Page 62 Troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Code Error Message/ BLOCK Cause Measure Prio type/ Description ERROR ERROR rity NA 64 Value Value 744 (A744) Alarm B>Main electronic PCB – Electromagnetic effects are greater – Restart the device. Perform reset...
  • Page 63 Deltapilot S FMB70 with FOUNDATION Fieldbus Troubleshooting Explanation of XD_ERROR and BLOCK_ERROR Message Code XD_ERROR XD_ERROR Text BLOCK BLOCK_ERROR Text PV Status type VALUE ERROR Value Alarm General Error Other Bad Sensor Failure 707, 711, 713, 721, Calibration Error Input Failure...
  • Page 64: Response Of Outputs To Errors

    Troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Response of outputs to errors The device makes a distinction between the message types "Alarm", "Warning" and "Error". → See the following table and → ä 56, Section 8.1 "Messages". Output A (Alarm)
  • Page 65: Confirming Messages

    FieldCare: Menu path for ALARM DISPL. TIME and ACK. ALARM MODE: OPERATING MENU → DIAGNOSTICS → MESSAGES Repair The Endress+Hauser repairs concept provides for measuring devices to have a modular design and also that the customer may carry out repairs (see Section 8.6 "Spare Parts" on → ä 66). Note! •...
  • Page 66: Spare Parts

    Troubleshooting Deltapilot S FMB70 with FOUNDATION Fieldbus Spare Parts An overview of the spare parts for your device is available in the internet at www.endress.com. To obtain information on the spare parts, proceed as follows: Go to "www.endress.com" and select your country.
  • Page 67: Returning The Device

    Please enclose the following when returning the device: • The duly completed and signed "Declaration of Hazardous Material and Decontamination". Only then can Endress+Hauser inspect or repair the returned device. • The chemical and physical properties of the fluid. • A description of the application.
  • Page 68: Technical Data

    Menu Note! • The entire menu of Endress+Hauser parameters is depicted on the following pages. Some Endress+Hauser parameters correspond to FF standard parameters. All other FF parameters can only be configured by means of an FF configuration program (see Operating Instructions BA303 "Cerabar S / Deltabar S / Deltapilot S, Description of Device Functions")
  • Page 69 Deltapilot S FMB70 with FOUNDATION Fieldbus Appendix Measured value GROUP SELECTION MANUFACTURER VIEW LANGUAGE MEASURING MODE QUICK SETUP Level measuring LEVEL SELECTION mode only OPERATING MENU SETTINGS POSITION ADJUSTMENT MEASURING MODE Deltabar S only Pressure Level Flow POS. ZERO ADJUST POS.
  • Page 70 Appendix Deltapilot S FMB70 with FOUNDATION Fieldbus Service BASIC SETUP MEASURING MODE Pressure Level Flow PRESS. ENG. UNIT LEVEL SELECTION PRESS. ENG. UNIT CUSTOMER UNIT P CUSTOMER UNIT P Level Easy Pressure Level Easy Height Level Standard CUST. UNIT FACT. P CUST.
  • Page 71 Deltapilot S FMB70 with FOUNDATION Fieldbus Appendix Continuation BASIC SETUP "Level", Height Volume Mass see also the previous page LEVEL SELECTION = HEIGHT UNIT UNIT VOLUME MASS UNIT Level Standard CUSTOMER UNIT V CUSTOMER UNIT M CUTOMER UNIT H PRESS. ENG. UNIT CUST.
  • Page 72 Appendix Deltapilot S FMB70 with FOUNDATION Fieldbus EXTENDED SETUP LINEARISATION LINEARISATION TOTALIZER SETUP Level measuring Level measuring Flow measuring mode only mode only mode only (Deltabar S only) Display via on-site Display via FieldCare display only only Pressure Level Flow TEMP.
  • Page 73 Deltapilot S FMB70 with FOUNDATION Fieldbus Appendix DISPLAY TRANSMITTER INFO FF data TRANSMITTER DATA PROCESS CONNECTION SENSOR DATA MENU DESCRIPTOR DEVICE ID DEVICE SERIAL No Pmax PROC. CONN. SENSOR SER. NO. MAIN DATA FORMAT DEVICE REVISION ELECTR. SERIAL No PROC. CONN. TYPE PRESS.
  • Page 74 Appendix Deltapilot S FMB70 with FOUNDATION Fieldbus PROCESS INFO OPERATION PROCESS VALUE FUNCTION BLOCKS PEAK HOLD INDICATOR Deltabar S only Level Flow Pressure MEASURED VALUE MEASURED VALUE MEASURED VALUE COUNTER:P > Pmax AI1 OUT VALUE ENTER RESET CODE PRESSURE PRESSURE...
  • Page 75 Deltapilot S FMB70 with FOUNDATION Fieldbus Appendix DIAGNOSTICS SIMULATION MESSAGES USER LIMITS SIMULATION MODE ALARM STATUS Pmin ALARM WINDOW LAST DIAG. CODE Pmax ALARM WINDOW ACK. ALARM MODE Tmin ALARM WINDOW ACK. ALARM Tmax ALARM WINDOW RESET ALL ALARMS Display via FieldCare only ERROR NO.
  • Page 76: Intellectual Property Rights

    Appendix Deltapilot S FMB70 with FOUNDATION Fieldbus 10.2 Intellectual property rights This product is protected by at least one of the following patents. Further patents are pending. • US 6,427,129 B1 i EP 0 892 249 B1 • US 6,703,943 A1 •...
  • Page 77: Index

    Deltapilot S FMB70 with FOUNDATION Fieldbus Index Index Alarm messages....... . . 56 Onsite display .
  • Page 78 Deltapilot S FMB70 with FOUNDATION Fieldbus Index Endress+Hauser...
  • Page 79 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 80 www.endress.com/worldwide BA372P/00/EN/06.09 71095403 CCS/FM+SGML6.0 71095403...