Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
Zoneworks, HIVE (HV/HVG) and DATA Monitored Options
Fittings with part numbers
-ZW, -HV, -HVG, -DATA
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
Option
State
ZW, HV, HVG,
Commissioned
DATA
ZW, DATA
Un-commissioned
Un-commissioned
HV, HVG
With network connectivity
Un-commissioned
HV, HVG
Without network connectivity
ZW, DATA
Emergency Light Test In Progress
HV, HVG
Emergency Light Test In Progress
In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Luminaires with part numbers having -D2 are fitted with DALI modules (nodes) that facilitate connection
and integration to 3rd Party Lighting Control Systems. Before installing the -D2 fitting please confirm that
the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -D2 fitting will
be addressed and configured into the control system by the Lighting Control System Commissioning
Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
"IDENTIFY COMMAND"
Lamp and Status LED Flash for 30 seconds
A 2-way "figure 8" cable and terminal block facilitates the connection to the DALI network OR a 5/6way
"structured wiring system" lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da
Microwave Sensor Option
Refer to the supplementary operation guide supplied with the Product.
– Clevertronics Stallion Driver, Sensor Adjust.
Instruction Sheet Template - V1.4 – Updated 09/03/2022
are fitted with Zoneworks communications modules
LED Operation
LED on Solid (Green)
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: yellow 250mS, green
250mS, yellow 250mS, green 250mS,
green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
LED flashes at yellow 5s , 0ff 1s
LED flashes at yellow 1s , 0ff 1s
LP™ IP65 CIRCLITE LED Luminaire
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the
requirements of AS2293.3: 2018 and AS/NZS
CISPR15: 2017
NOTE: Standard product codes with this symbol
enabled with Clevertest Plus capability. Please refer to
the operation guide supplied with the product for details
Models:
ARGOCIRC-xx-LP-yy-zz
Options:
Testing:
Without Sensor
xx = blank
Manual Test
Microwave Sensor xx = SEN
DALI-2
Zoneworks HIVE
Spare Parts:
1550231
Replacement Battery
8051465
Replacement LED Board
805-00003
Replacement LED Board (-SEN)
AUM02370720001
Replacement Emergency Driver
1330105
Replacement 240V Driver
1330104
Replacement 240V Driver (-SEN)
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before
installation, ensure that the electricity supply has been switched off and isolated. Installation must be
carried out in accordance with the relevant Australian and International Standards.
Victoria (Head Office & Manufacturing)
Website:
www.clevertronics.com.au
Email:
info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9207 0000
Fax: +61 8 9207 0088
are
New Zealand
Phone: +64 800 548 448
Colour:
yy = Blank
Black
zz = BLK
yy = D2
White
zz = WHT
yy = HV/HVG
1940007
V1.1
29 October 2024
Need help?
Do you have a question about the ARGOCIRC LP Series and is the answer not in the manual?
Questions and answers