Download Print this page

Merrytek MSA001S 1 User Manual

Microwave sensor
Hide thumbs Also See for MSA001S 1:

Advertisement

Quick Links

Model: MSA001S 1
Microwave Sensor User's Manual

Advertisement

loading
Need help?

Need help?

Do you have a question about the MSA001S 1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Merrytek MSA001S 1

  • Page 1 Model: MSA001S 1 Microwave Sensor User’s Manual...
  • Page 2 ATTENTION The product shall be installed by a professional electrician. Please disconnect the power before installation and wiring. Before the product is powered on, please confirm that the input voltage range meets the requirements of the manual. Please read the relevant contents in this manual carefully before using the product.
  • Page 3 Switches and routers, and installation interval should be at least 2 meters to avoid radio interference. Product Introduction This product uses Merrytek 5.8GHz patent low impedance microwave sensing technology and detects human body, cars at low speed and other moving signals. It is not influenced by the changing of temperature and suitable for...
  • Page 4 Parameters Operating Voltage 220-240Vac, 50/60Hz Operating Mode ON/OFF Resistive load (Incandescent lamp, ventilator Rated Load etc): 800W Max., Capacitive load (Ballast, (Note 1) energy-saving lamps etc): 400W Max., LED: 400W Max. Max. Surge Capacity 30A (50% Ipeak, twidth=500uS, (Note 1) 230Vac full load, cold start) Stand-by Power 0.5W Max.
  • Page 5 Note: When the sensor is connected to the load, the cold start surge current of the electrical appliances in the loop cannot exceed this limit, otherwise the sensor will be damaged. It is recommended that this product be connected to a maximum of 4 loads, and the total power of the load and the surge current generated at the moment when the load input is powered on cannot exceed the rated requirements...
  • Page 6 1. Dimension (mm) 2. Structure Motion Sensor Adjustable Daylight Detection Area Sensor Hold-time...
  • Page 7 3. Wiring Single Unit: load 220-240Vac...
  • Page 8 Multiple Unit: load load 220-240Vac Note: 1. It is recommended that this product be connected to a maximum of 4 loads, and the total power of the load and the surge current generated at the moment when the load input is powered on cannot exceed the rated requirements of the sensor.
  • Page 9 4.Function ON/OFF Function 1 (daylight sensor is set to “disable”) 1. Sensor turns on 2. Sensor makes 3. Sensor turns off lights when people lights remain on lights after hold enter detecting when people is time ends when area. moving during people leave hold time.
  • Page 10 ON/OFF Function 2 (daylight sensor is set to “5lux, 30lux or 50lux”) 1. If environment illuminance 2. If environment illuminance is higher than the preset is lower than the preset daylight threshold, sensor daylight threshold, sensor does not turn on lights when turns on lights when people people enter detecting area.
  • Page 11 5. Installation Instruction 1) Flush mounting 1. Cut a hole of 55mm on the ceiling. 2. Remove the crimping cover using a flat-head screwdriver. 3. Connect input wire to wiring terminals 4. Assemble the wire cover and press the wire. 5.
  • Page 12 6. Toggle DIP switches and set parameters. 7. Cover surface cover and make it be fastened to main body. 8. The spring clamp is bent backwards to push through a hole in the ceiling. 9. Ensure installation stable. 2) Surface mounting...
  • Page 13 1. Cut off thin wiring housing of ceiling mounting seat with a tool. 2. Use the matching screws to fix the product to the mounting surface. 3. Connect input wire to wiring terminals. Assemble cover and press wire tightly. 4. Remove the surface cover with a flat-head screwdriver. 5.
  • Page 14 6. Instructions 1) Initialization: After power on, the indicator light flashes for 20 seconds and then turns off. During initialization, the sensor does not detect external movement signals. After the initialization is completed, it enters the normal working state. 2) Block Time: The sensor blocking time is 2s once the sensor is turned off after the “Hold time”...
  • Page 15 4) Parameter settings: Detection Area The higher the detection area, the larger the detection radius. Detection Detection Radius Motion Detection Coverage Area I ON ON 100% Around 3 meters Approx.36m² (6x6m room) II - ON Around 2.5 meters Approx.25m² (5x5m room) III ON - Around 2 meters Approx.16m²...
  • Page 16 Hold Time When no one is detected, power will turn off after the time elapses. 1min 5min 10min Daylight Sensor When someone enters the detection area, the relay does not close; when the surrounding environment illuminance is higher than the preset daylight threshold, the relay closes when it is lower than the preset and lights turn on automatically.
  • Page 17 Daylight sensor Illuminance 5Lux Dark 25Lux Twilight 50Lux Slightly bright No “daylight sensor” Disable function 5. DIP Switch Setting Indication: (The following figure) Toggle up the DIP Switch to "ON", downwards to " " For example, when setting detection area to 100%, hold time to 5s and daylight to disable, DIP Switch Setting will be like the right picture:...
  • Page 19 After-sales and Warranty Free maintenance service is provided for failures caused by the product during the warranty period. Damages that are not caused by our company's actions such as handling, dropping, installation, use, maintenance, and improper storage by the user are not covered by the warranty.
  • Page 20 Damage caused by using without following instruction or due to force majeure factors, such as, fire, earthquake, etc., is not covered by the warranty. Any exterior decoration and accessories of the body are not warranted, such as connecting cables, cabinets, panels, cabinet accessories, etc.
  • Page 21 The Model No., parameters and performance of the product in this manual are subject to change without further notice. Shenzhen Merrytek Technology Co., LTD No.17th Building, Dianda Guyuan Industrial Park, Mashantou, Matian, Guangming District, Shenzhen, China, 518106...