Advertisement
This manual applies to Wall Connectors identified by part number 14577681509549-**-*.
Product Specifications
Voltage and Wiring | Nominal 200-240 V AC single-phase |
Current Output Range | 12 – 48 amps |
Terminal Blocks | 12-4 AWG (3.5 - 25 mm 2 ), copper only |
Supported Conduit Sizing | ¾ in (21 mm) default, 1 in (27 mm) optional |
Grounding Scheme | TN/TT |
Frequency | 50/60 Hz |
Cable Length | 7.3 m (24 ft) |
Wall Connector Dimensions | Height: 13.6 in (345 mm) Width: 6.1 in (155 mm) Depth: 4.3 in (110 mm) |
Wire Box Bracket Dimensions | Height: 9.8 in (250 mm) Width: 4.7 in (120 mm) Depth: 2.0 in (50 mm) |
Weight (including wirebox) | 10 lb. (4.5 kg) |
Operating Temperature | -22˚F to 122˚F (-30˚C to 50˚C) |
Storage Temperature | -40˚F to 185˚F (-40˚C to 85˚C) |
Enclosure Rating | Type 3R |
Ventilation | Not required |
Means of Disconnect | External branch circuit breaker |
Ground Fault Circuit Interrupter | Integrated, no additional required (CCID20) |
Wi-Fi | 2.4 GHz, 802.11b/g/n |
Agency Approvals | cULus - E351001 |
Transportation and storage: Ensure that Wall Connector is within storage temperature when moving, transporting, or storing.
Circuit Breaker Rating / Maximum Output
Power Output
For maximum power output, install a standard double pole 60 amp circuit breaker. Wall Connector includes integrated GFCI protection - do not install a GFCI circuit breaker.
Wall Connector incorporates automatic load management, which allows the max output to be customized to an existing power supply. If the electrical supply is unable to support the 60 amp configuration, select a lower amperage configuration.
Circuit breaker (amps) | Max output (amps) | Power output at 240 volts (kW) |
60 | 48 | 11.5 |
50 | 40 | 9.6 |
40 | 32 | 7.6 |
30 | 24 | 5.7 |
20 | 16 | 3.8 |
15 | 12 | 2.8 |
NOTE: External disconnect switches are neither required nor recommended.
NOTE: Circuit breaker size is programmed during the commissioning process. See Commissioning Procedure or details.
NOTE: Some Tesla vehicles may draw less current than the max output. Actual charging rate depends on Wall Connector output and onboard charger in the vehicle.
Branch Circuit Conductors and Ground Wire
Grounding Connections
Wall Connector must have a ground path back to the main equipment earthing point on site. Without a proper ground connection, the Wall Connector will fault during a ground assurance test. Equipmentgrounding conductor must be run with the circuit conductors and connected to the equipment-grounding terminal in the wirebox. Install a ground (PE) wire sized according to local electrical code.
Using Wall Connector
Features
Connectivity
Wall Connector is equipped with Wi-Fi to communicate with local site routers, vehicles, mobile devices, other Wall Connectors, and other Tesla products.
Hosted Access Point
Wall Connector hosts a WPA2 password-secured, 2.4 GHz, 802.11 Wi-Fi access point network to facilitate commissioning and connecting to other devices.
A unique SSID Wi-Fi network name and WPA2 password for connecting to the Wall Connector are printed on a label at the rear of the main unit, as well as on the front cover of the Quickstart Guide included in the box.
Local Network
Connecting Wall Connector to a local Wi-Fi network enables it to receive over-the-air firmware updates, remote diagnostics access, and usage data tracking capability. A Wi-Fi connection is required for sites that utilize authentication, billing, and other property management features.
Wall Connector only supports WPA2/3-secured, 2.4 GHz, 802.11 infrastructure mode networks.
NOTE: Networks that are not password protected are not supported. The Wall Connector will not display non-password protected networks in the options list. Open networks without a password are not supported and will not be recognized by the Wall Connector.
NOTE: WPA enterprise will be supported in a future firmware update.
NOTE: Property management features will be enabled via future firmware updates.
Ground Fault Circuit Interruption
Integrated ground fault circuit interruption (GFCI) protection automatically detects a current mismatch between power delivery conductors that would indicate that current is flowing through the ground (PE) conductor.
If a ground fault occurs after 10 seconds of charging, Wall Connector will wait 15 minutes before automatically re-attempting to charge. Up to four attempts to charge will be made before user interaction is required.
If a residual current fault occurs within 10 seconds of charging, Wall Connector will lock out and user interaction is required to restore charging functionality.
Recommended interaction includes pressing the button on the charging handle, or removing the charging handle from the vehicle and reinserting it. If this does not resolve the issue, look for a ground fault issue such as water ingress.
Ground Assurance
Wall Connector continuously checks for the presence of a safe ground connection and automatically recovers from faults. Grounded assurance operates by injecting a small amount of current into the ground conductor in order to measure the impedance between line and ground. If high impedance is detected, the Wall Connector will lock out charging and display a fault code of two (2) red blinks. See Fault Codes for a full list of fault codes.
For ground assurance to operate on TN grids, one leg of the distribution transformer must be groundbonded (Neutral). Ground bond should only occur at one location in a site's electrical system.
Wall Connector ground assurance may be adjusted in countries with TT or IT grid configurations and can be disabled in the commissioning procedure.
The Ground Monitor Interrupter feature monitors the Wall Connector ground connection. Select the correct option based on the installation's earthing system and earth impedance.
Depending on country, three options are available:
NOTE: Ground Monitoring is always enabled for installations in North America.
Temporary problems such as ground faults or utility power surges are resolved automatically.
Thermal Monitoring
Wall Connector actively monitors temperatures in multiple locations while charging to ensure stability of the charge session. Temperature sensors are located at the relays, microcontroller, charge handle, and rear of the main unit to monitor the temperature of the terminals in the wirebox.
In warmer conditions, Wall Connector may reduce current and charge speed to protect itself. When this happens, the light bar on the faceplate will continue to display the "streaming green" and a blink code of three red flashes to indicate that charging has been reduced due to high temperatures. If heat continues to rise, Wall Connector will stop charging and display a blink code of three red flashes.
NOTE: See Fault Codes for full list of error codes.
For optimal performance, install Wall Connectors in areas where ambient temperature will remain below 50˚C (122˚F). In rare circumstances, Wall Connector may begin reducing amperage at 35˚C (95˚F) ambient temperatures. Adjustments to amperage are automatic and do not require user input; Wall Connector will return to starting current when temperatures are reduced.
Power Outages
If there is a power outage while Wall Connector is charging a vehicle, charging will automatically resume within 1 to 3 minutes after power restoration. The Wall Connector will display a solid blue light on the faceplate to indicate that it is communicating with the vehicle and waiting to resume charging. Alternatively, pressing the button on the charge handle after power restoration will cause Wall Connector to resume charging immediately.
Firmware Updates
Firmware updates will be automatically applied to the Wall Connector to improve the user experience and introduce new features. Connect Wall Connector to Wi-Fi for access to the most recent firmware update. See Commissioning Procedure Tesla vehicles can provide firmware updates to Wall Connectors.
Wall Connector External Components
"Wall Connector" refers to the product as a whole.
Wall Connector Internal Components
In the Box
NOTE: The hex bit, zip tie, and fasteners are located in a plastic bag inside the wirebox, which comes attached to the main unit of the Wall Connector.
NOTE: Wall plugs are not included. If installing in concrete or other like materials, use 6 mm wall plugs.
Tools
Required Tools
NOTE: Drill bit sizes assume wood mounting surfaces. If installing on concrete or other masonry, consult with an electrician for optimal pilot hole sizes.
Optional Tools
Installation Considerations
Wall Connector may be installed on any flat, vertical surface capable of supporting its weight (e.g. wall, pedestal, etc.). Wall Connector weighs 6.8 kg (15 lb).
Choosing Location
Install Wall Connector in a location that allows the charge cable to reach the vehicle charge port without putting strain on the cable. Recommended installation area for Wall Connectors with cable:
Install Wall Connector in a location with ample clearance on all sides to allow the charge cable to loop around the unit and the charge handle to comfortably land in the side dock.
NOTE: If constrained by space, a cable organizer can be installed near the Wall Connector (sold separately).
Choosing Height
Maximizing Wi-Fi Signal Reception
Wall Connectors should be connected to a local Wi-Fi network for optimal functionality. For maximum signal reception, avoid installing Wall Connector on opposite sides of concrete, masonry, metal studs, and other physical obstructions that could impede Wi-Fi signal reception.
NOTE: If a mobile device is able to connect to local Wi-Fi at a given location, it is a good indication that Wall Connector will also be able to connect.
Wire Entry Options
Wall Connector's wirebox has multiple wire entry options. Choose one entry path and follow installation instructions based on chosen entry path.
For additional installation considerations on sites that will have multiple Wall Connectors, see Considerations for Power Sharing.
The default conduit size is 3/4 in (21 mm). 1 in (27 mm) conduit is acceptable if needed.
Based on fittings and conduit size, prepare the wirebox.
Top Entry | Bottom Entry | Rear Left Entry | Rear Right Entry |
![]() | ![]() | ![]() 1-1/8 in (29 mm) | ![]() 1-1/8 in (29 mm) |
Top Entry | Bottom Entry | Rear Left Entry | Rear Right Entry |
Do not expand. | ![]() 1-3/8 in (35 mm) | ![]() 1-3/8 in (35 mm) | ![]() 1-3/8 in (35 mm) |
NOTE: For 1 in (27 mm) rear and bottom entry options, drill with 1-3/8 in (35 mm) step bit to prepare wirebox for fittings.
Top Entry | Bottom Entry | Rear Left Entry | Rear Right Entry |
![]() | ![]() | ![]() | ![]() |
Top Entry | Bottom Entry | Bottom Left Entry | Bottom Right Entry |
![]() | ![]() | ![]() | ![]() |
NOTE: Type 3R rating is only possible when washers have sealing gaskets. If mounting to alternate surface (such as a prefabricated pedestal), use alternate fasteners with sealing washers.
NOTE: The wood fastener screws are designed to support the weight of the entire Wall Connector, cable, and charging handle.
Top Entry | Bottom Entry | Rear Left Entry | Rear Right Entry |
![]() | ![]() | ![]() | ![]() |
The commissioning process for Wall Connector enables easy configuration of circuit breaker size, Wi-Fi connectivity, and power sharing options.
NOTE: To have the Wall Connector broadcast the SSID again, hold the button on the charge handle for 5 seconds or turn the circuit breaker off, then on again.
Setting Up Access Control
The Charging Access Control feature provides full control over which vehicles are allowed to charge with your Wall Connector and excludes vehicles without access based on user specifications.
Power Sharing Overview
The firmware-based power sharing feature enables up to 6 Wall Connectors installed at the same site to intelligently share the site's total available power via unit-to-unit Wi-Fi. This minimizes the need for many residential and commercial applications to have specific electrical upgrades for concurrent multi-vehicle charging.
During the commissioning process,
NOTE: For instructions to commission Wall Connectors in a power sharing network, see Gen 3 Wall Connector Power Sharing.
Total current output of Wall Connectors that share power will never exceed the site's total allocated power.
Breaker and Branch Circuit Setup
Power sharing circuits may be installed in an electrical panel that supports other loads. If space is limited or the main power supply is far from the Wall Connectors, installing a dedicated load center may be prudent.
See below for examples of Wall Connector power sharing diagrams (one with sub-panel and one without). Each individual Wall Connector in below examples is capable of providing 48 amps when it is the only one in use. As more Wall Connectors begin plugging into vehicles, the system will automatically distribute power based on the total power allocated to the site.
Power Sharing Setup with Sub-Panel
Power Sharing Setup Without Sub-Panel
Considerations for Power Sharing
Wall Connector power sharing is achieved wirelessly.
For optimal performance, Wall Connectors within a power sharing network should be installed within view of each other whenever possible.
NOTE: Line of sight is recommended but not required. Wireless communication is capable of reaching around concrete corners but network range may degrade as a result.
Avoid placing Wall Connectors on opposite sides of concrete, masonry, metal studs, and other physical obstructions that would impede Wi-Fi signal strength.
NOTE: If a mobile device is able to connect to the Leader Wall Connector Wi-Fi, it is a good indication that the Follower Wall Connector will also be able to connect.
Calculating Power Sharing Requirements for Existing Systems
To calculate power supply requirements per number of Wall Connectors for existing electrical systems, use the following equation:
NOTE: Maximum number of Wall Connectors for power sharing is 6.
NOTE: When calculating maximum amperage per Wall Connector, 100% utilization must be greater than 6 amps for power sharing operation. If maximum amperage is greater than 48 amps, power sharing is not necessary.
For large scale sites, consider expected parking time in relation to a 100% utilization rate.
Expected Park Time (hours) | Examples | Recommended Amperage per wall Connector at 100% Utilization |
6+ (long term) | Long term parking, overnight parking | 12+ amps |
3-5 (medium term) | Workplace, hospitality | 24+ amps |
1-2 (short term) | Shopping and dining | 32+ amps |
NOTE: 100% utilization represents the worst case scenario for charging speeds, where the least amount of power would be available for each individual vehicle. In most situations, not all Wall Connectors would be actively charging a vehicle, which enables faster charging for the remaining vehicles.
Power Sharing Commissioning Procedure
Light Codes
Startup
Once energized at the circuit breaker, every LED (seven total) on the faceplate will illuminate for up to five seconds.
After Startup
After Wall Connector is energized at the circuit breaker, certain green LEDs (depending on the circuit breaker size) will illuminate for 10 seconds. See table below for exact light codes.
![]() | ![]() | ![]() | ![]() | ![]() | ![]() | |
Circuit breaker | 60 A | 50 A | 40 A | 30 A | 20 A | 15 A |
Maximum output | 48 A | 40 A | 32 A | 24 A | 16 A | 12 A |
NOTE: To re-display the green LEDs after the initial 10 seconds, press and hold the charging handle button.
When multiple Wall Connectors are linked for power sharing, the center blue LED will illuminate during the 10-second startup window.
Other
Standby, waiting to plug in | Charging in progress | SSID broadcasting, ready to commission | Waiting to charge, communicating with vehicle |
Top green solid![]() | Every green streaming![]() | Green pulsing![]() | Blue solid![]() |
All red blink codes pause for one second, and then repeat. | ||
Light Bar | What It Means | Details |
No Lights | Power supply issue, charging disabled | Verify that the power supply is turned on. If the issue persists, have an electrician remove the Wall Connector from the wirebox and confirm that voltage is present at the terminal block using a multimeter. Record the voltage readings for the following: L1 to L2/N, L1 to Ground, L2/N to Ground. |
Solid red | Internal, charging disabled | Turn the circuit breaker off, wait 5 seconds, and turn it back on. If solid red light remains, document part number and serial number, then contact Tesla Energy. |
One (1) red blink | Ground fault circuit interruption due to unsafe current path, charging disabled | Inspect the handle, cable, Wall Connector, and vehicle charge port for damage or signs of water ingress. Have an electrician check that ground is not directly connected to a conductor wire in the branch circuit. |
Two (2) red blinks | Ground assurance fault, high ground resistance detected, charging disabled | Verify that the Wall Connector is properly grounded. The ground connection must be bonded in the upstream power supply for proper operation. Check all physical connections, including the wirebox terminals, electrical panel(s), and junction boxes. In residential power supplies, check the bond between ground and neutral at the main panel. If connected to a transformer, contact the transformer's manufacturer for direction on how to bond the ground connection. |
Three (3) red blinks | High temperature detected; charging limited or disabled | Verify that Wall Connector is connected to Wi-Fi and updated with the latest available firmware for optimal temperature sensing functionality. Check the faceplate and cable handle for excessive warmth. Have an electrician remove the Wall Connector from the wirebox and verify that the conductors used are sized correctly and that the terminal block is torqued to specification. |
Four (4) red blinks | Internet connection lost, online features disabled | Check for objects that could interfere with the area's Wi-Fi signal strength. Confirm that the local Wi-Fi router is operational. If the Wi-Fi password was changed recently, follow the commissioning process on your mobile device to update the Wi-Fi settings. |
Five (5) red blinks | Power-sharing communication issue, charging reduced | Check for objects that could interfere with the area's Wi-Fi signal strength. Follow the commissioning process on your mobile device to re-link the Wall Connectors for power-sharing. |
Six (6) red blinks | Overvoltage or poor grid quality detected, charging disabled | Verify that the power supply is nominal 200-240 volts. If the issue persists, have an electrician remove the Wall Connector from the wirebox and confirm that voltage readings are as expected at the terminal block using a multimeter. Record the voltage readings for the following: L1 to L2/N, L1 to Ground, L2/N to Ground. |
Seven (7) red blinks | Vehicle overcurrent detected | Reduce the vehicle's charge current setting. If the issue persists and the attached vehicle is manufactured by Tesla, record the vehicle's VIN and approximate time of the fault and contact Tesla. If the vehicle is not manufactured by Tesla, contact the vehicle's manufacturer. |
Additional Assistance for Red LED Faults
A Wall Connector's alerts are visible in the browser commissioning wizard (for instructions on how to connect to the commissioning wizard, see Commissioning Procedure).
If additional assistance is required, have the following information prepared before contacting Tesla:
Visit tesla.com/support/contact or scan the QR code below to request support.
Optionally, for owner support and issue troubleshooting: (888) 765-2489
For North America Electrician and Installer support: (650) 963-5655
Read all instructions before using this product. Save these instructions. Wall Connector features built-in Type B RCD.
This manual contains important instructions for the Tesla J1772 Wall Connector that shall be followed during installation, operation, and maintenance. Please review all warnings and cautions before installing and using the Wall Connector.
When using electric products, basic precautions should always be followed, including the following.
INSTRUCTIONS RELATING TO RISK OF FIRE OR ELECTRIC SHOCK
Do not install or use the Wall Connector near flammable, explosive, harsh, or combustible materials, chemicals, or vapors.
Turn off power at the circuit breaker before installing or cleaning the Wall Connector.
This product can expose you to one or more chemicals that are known to the state of California to cause cancer.
This device should be supervised when used around children.
The Wall Connector must be grounded through a permanent wiring system or an equipment-grounded conductor.
Use the Wall Connector only within the specified operating parameters.
Never spray water or any other liquid directly at the wall mounted control box. Never spray any liquid onto the charge handle or submerge the charge handle in liquid. Store the charge handle in the dock to prevent unnecessary exposure to contamination or moisture.
Do not use the Wall Connector if it is defective, appears cracked, frayed, broken, or otherwise damaged, or fails to operate.
Do not use the Wall Connector if the flexible power cord or cable is frayed, broken, or otherwise damaged, or fails to operate.
Do not attempt to disassemble, repair, tamper with, or modify the Wall Connector. The Wall Connector is not user serviceable. Contact Tesla for any repairs or modification.
When transporting the Wall Connector, handle with care. Do not subject it to strong force or impact or pull, twist, tangle, drag, or step on the Wall Connector, to prevent damage to it or any components.
Do not touch the Wall Connector's end terminals with fingers or sharp metallic objects, such as wire, tools, or needles.
Do not insert fingers or foreign objects into any part of the Wall Connector.
Do not forcefully fold or apply pressure to any part of the Wall Connector or damage it with sharp objects.
Use of the Wall Connector may affect or impair the operation of any medical or implantable electronic devices, such as an implantable cardiac pacemaker or an implantable cardioverter defibrillator. Check with your electronic device manufacturer concerning the effects that charging may have on such electronic devices before using the Wall Connector.
Do not use private power generators as a power source for charging.
Incorrect installation and testing of the Wall Connector could potentially damage the vehicle's battery, components, and/or the Wall Connector itself. Any resulting damage is excluded from the New Vehicle Limited Warranty and the Charging Equipment Limited Warranty.
Do not operate the Wall Connector in temperatures outside its operating range of -22˚ F to 122˚ F (-30˚ C to 50˚ C).
Wall Connector should only be installed by personnel who are trained and qualified to work on electrical systems.
Ensure that Wall Connector is within storage temperature when moving, transporting, or storing.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the J1772 and is the answer not in the manual?
Questions and answers