Do you have a question about the Xe-50M and is the answer not in the manual?
Questions and answers
Mark
March 27, 2025
is there a way to test this controller mine is not functioning
Xe-50m
is there a phone to call I'm old and prefer phone calls to emailing
1 comments:
Mr. Anderson
March 27, 2025
To test an Ingersoll-Rand Xe-50M controller that is not functioning, follow these steps using the available information:
1. Check Power Supply: Ensure the controller is receiving power. If not, inspect the voltage transformer and power connections.
2. Verify Motor Rotation: If the controller shows "Ck Motor Rot", check that the motor is rotating correctly. Correct rotation is confirmed when the sump pressure reaches 1 psi or more within 3 seconds of starting (6 seconds for soft starters or if the temperature is below 50°F).
3. Check for Overload: If the display shows "Overload", inspect the motor and fan overload relays. A trip occurs if the relay is open for at least 3 seconds.
4. Remote Stop Issue: If "Rem Stop Fail" appears, confirm that the remote stop/start option is properly configured and the stop button is not stuck in the open position.
5. Inspect Communication Connections: If connecting to a MODBUS network, ensure RS-485 cables are correctly connected to port X04 and properly shielded and routed to avoid electrical interference.
If these checks do not identify the issue, further diagnostics or professional service may be needed.
Page 3
TOPIC PAGE Start Inhibit List Trip History Maintenance Folder Filter Status Maintenance Configuration General Settings Language and Units Selection Time & Date Settings Backlight Settings Serial Port Address Settings Ethernet Settings (ECO Module Only) Integral Sequencing Folder Setup Tuning Priority Rotation Status Folder Analog Inputs...
XE-50M CONTROLLER INTRODUCTION The Xe-50M is standard on 5-15HP fixed speed units and is powered though a stepped down 24 Vac power supply. A stepped down voltage of 110 Vac is fed and switched by internal relays to control the opening and closing of the contactors and solenoid valves.
Page 5
X04-R4 Dryer Run Output (optional) RS485 Communication...
Xe-50M Controller Interface and Operation The standard user interface configuration of the controller consists of the membrane and the LCD display. The membrane consists of three command keys (Start, Stop, and Reset), two navigation keys (Up and Down), and an Edit mode selection key (Enter).
Page 7
To enter the following menus, press the Up and Down arrows simultaneously and enter the corresponding access code using the Up and Down arrows: E06 Operational Menu (Access Code 0009) Item Description Default Unit Value 1.Pu Upper Pressure Setpoint 1.PL Lower Pressure Setpoint 1.Sd Motor Star/Delta Time...
Page 8
Service Due Countdown Timer If the service due countdown timer reaches 0 (Zero) hours the Service and Alarm symbols will flash and the service Alarm (Warning) code will be displayed. The Alarm code can be reset but the service symbol will remain on the display until the service due timer is reset;...
Xe-50M Fault Codes If a Fault condition occurs the Fault triangle symbol will switch ON steady (Warning) or flash (Trip). The user menu display item will show a ‘Fault Code’ dependent on the fault. Fault codes are separated into two categories: Alarm (Warning) Codes - A: Warning symbol illuminated on steady, the compressor will continue to operate.
Shutdown (Trip) Codes - E: Trip symbol will flash, the compressor will stop. Code Description Emergency Stop – 24 Vac in not detected on E:0010 terminal R1C E:0020 Main or blower Motor Overload DI - C2 E:0030 Remote Start Failure DI - C3 E:0040 High Discharge Pressure DI - C4 E:0050...
XE-70M CONTROLLER INTRODUCTION The Xe-70M control system is provides efficient and reliable compressor operation. The controller supports thirty languages, independently configurable units of measure as well as enhanced network and communication capabilities. This microprocessor-based controller uses a finger touch membrane for operation of the compressor and setting control parameters.
COMPONENT REVIEW FU1 - Main Fuse Protection FU1 is the schematic designation of the Main Fuse Protection and is the customer’s responsibility to correctly size and install. FU1 protects the machine should an overcurrent condition occur. These fuses should be time delay fuses, in order to accommodate the inrush current at machine startup.
Page 16
secondary circuits. There are two of these secondary circuits in the control system. The first secondary circuit is rated at 110 Vac, 1 phase, 60Hz and is used to energize solenoid valves and starter coils. The “hot” connection is X1 and the neutral connection, X3, is grounded to the starter chassis.
Page 17
110 Vac Circuit - Transformer (T1) to Xe-70M The Xe-70M controller receives 110 Vac from T1. Depending on operating conditions, the controller sends the voltage onward to specific areas at specific times. Examples: energizing a starter coil at start-up or energizing a solenoid valve when the compressor loads.
Page 18
SB1 - Emergency Stop Button SB1 (sometimes referred to as ES) is located next to the Xe-70M controller in the starter panel and is intended to stop the compressor in an emergency. The switch has two sets of normally closed contacts that open when the red E-Stop button is pressed.
Page 19
X01 - X13 Quick Connect Terminal Plug Strips A group of different sized terminal plugs is used to connect control and instrument wires to the Xe-70M controller. These connectors are female Phoenix type (5.08mm spacing) and plug into matching male receptacles on the Xe-70M controller.
Page 20
X02 Digital Inputs Terminal plug strip X02 is dedicated to digital inputs that provide remote control and feedback from various switches installed on the package. DI2 - Main Motor Overload Relay (FA1 R-Series Only) Connected to the bottom of KM1, the main motor overload relay provides protection in the event of an overcurrent condition in the motor windings.
Page 21
A continuous voltage is applied to the strain gauge assembly. As the strain gauge bends due to the changing pressure on the diaphragm, the resistance value through the strain gauge changes a corresponding amount; the result is a variable output signal that ranges from 0.5-4.5 volts.
Page 22
4APT - Package Discharge Pressure Connected to X03-3 & 4, 4APT has a range of 0 to 232 psi. Power is provided to the transducer at X03-3 and return signal at X03-4. The output signal is 4mA at 0 psi and 20mA at 232 psi.
Page 23
at X03-6. The output resistance is 10kOhms at 77°F and 413.9Ohms at 239°F. Should 2ATT observe the temperature rise exceeding 228°F (109°C), the controller shuts the compressor down on a Trip. The display will show the word Tripped and the Trip Log will display High Airend Discharge Temperature.
Page 24
CTO - Common Trip Outputs N.O. output connected to X07-3 & 4 X08, X09 Triac Outputs Terminal plug strips X08 and X09 are dedicated outputs that provide control of solenoid valves and starter contactors. These outputs are powered by 110 Vac located at X09-CR.
Page 25
R2 - Main Motor Start Contact Connected to X09-3, the controller provides power to KM3 main motor starter coil. Auxiliary contact KM2-1 provides full control of the Star/Wye Delta starting circuit.
Page 26
R3 - Fan Motor Start Contacts (KM4) R-Series Only Connected to X9-4, the controller provides power to KM4 fan motor starter coil. KM4 provides control of the cooling fan motor starting circuit.
Page 27
R4 - NC Load Solenoid Valve (1SV) Connected to X08-2, the controller provides power to the 1SV load solenoid valve. When energized, 1SV opens and applies pressure to the inlet valve to allow the compressor to load. R4 - NO Blowdown Solenoid Valve (3SV UP6S/RS Only) Connected to X08-2, in parallel with 1SV, the controller provides power to the 3SV solenoid valve.
Page 28
R5 - Dryer/Blower Drive Relay (KA1 TAS Option Only) Connected to X08-4, the controller provides power to the KA1 (sometimes referred to as K1) dryer/blower drive control relay. KA1 provides control of the integrated dryer or blower drive relay circuit (optional components). X10, X11 Current Transformer Analog Inputs Current transformers (CTs), if equipped, provide real-time motor current input to the controller for motor protection.
Page 29
Xe-70M Controller I/O Summary Digital Inputs X02-2 Emergency Stop ES-2 X02-3 Fan Motor Protection FMP-1 X02-4 Remote Load Enable RLE X02-5 Remote Load/Unload RLU X02-6 Remote Start RST X02-7 Remote Stop RSP X02-8 Dryer High Temperature Trip (TAS Option) X02-9 Dryer High Pressure Trip (TAS Option) Analog Inputs X03-1 &...
Page 30
Xe-70M Controller Interface and Operation The standard user interface configuration of the controller consists of the membrane and the LCD display. The membrane consists of five command keys (Start, Stop, Load, Unload, and Reset), four navigation keys (Up, Right, Left and Down), and an Edit mode selection key (Enter). These keys, in conjunction with the graphics display and LED icons, make up the user interface to the compressor.
Page 33
LED Status Icons Three LED icons are used to indicate the current status of the control system from a distance and are located on the upper left side of the user interface. Icon Name Function Green Indicator, Illuminates when no Warnings or Trips are sensed, (can be in a Ready or Not Ready state).
Page 34
Command Keys These keys command the controller to perform actions as specified in the following table. When any of these keys are pressed the action below will be initiated and logged in the event log. Icon Name Function Places the compressor into the selected mode of Load operation.
Page 35
Navigation Keys There are four navigation keys (UP, RIGHT, DOWN and LEFT) that move a cursor throughout the folders and pages in the display. While the ENTER key is not considered a navigation key, it is used in conjunction with the navigation keys to make or confirm a selection.
Display Layout Xe-70M Display Layout Folder Bar: Uses tabs to graphically identify each folder. Title Bar: Identifies current folder and page. Page Content: Content of the current page. Dashboard: Displays system status. Folder Navigation & Icons To move among the tabbed folders shown on the LCD display, press the RIGHT and LEFT keys.
Page 37
Folder Icon Description Name System events log. Events Details on the most Trip History recent trips. Status and notification Maintenance setup for compressor maintenance items. General settings such as General Language, Time, and Settings Units of Measure. Page Navigation Once the desired folder is selected, press the DOWN key to move to the page selection area and then use the RIGHT and LEFT keys to select the desired page.
Page 38
The cursor rolls over, so once the last parameter is selected, pressing the DOWN key will navigate the cursor to the Folder Bar. If the first parameter is selected, pressing the UP key will move the cursor to the page selection area.
Page 39
Dashboard Icons The dashboard is intended to be a quick at-a-glance view of system status. The following table lists standard dashboard icons and their definition. Name Icon Description Integral Sequencing Remote communication status and Control configuration. Notification that one or Service more maintenance items Required...
Page 40
Running Loaded - The compressor is operating and producing air. The inlet valve is open and the blowdown valve is closed. Running Unloaded - The compressor is operating, but not producing air. The inlet valve is closed to the unloaded position and the blowdown valve is open.
Home Folder Page 1: System Overview This is the factory default display after powering up the system. Online Pressure Setpoint - indicated in the black box and arrow, which is always left of center on the gauge. The compressor will load when package discharge pressure falls below this value.
Page 42
Airend Discharge Temperature - indicated by the numbers in the lower right of the display. This is the temperature of the air/oil mixture at the discharge of the compression module. Temperature Unit of Measure - indicated to the right of the Airend Discharge Temperature.
Page 2: Counters Hour Meters - Indicates the hours that: the controller has been powered up, the compressor motor has been running, and the compressor has running loaded. Starts - Indicates the number of times a start is attempted on the compressor.
Page 44
Pages 3 & 4: Analog Inputs and Compressor Information Any sensor that is not installed or is reporting a failure will show a [ - - ] symbol. NOTE: All information on these pages is read only. The following analog inputs are displayed in this section.
Page 45
Package Discharge Pressure - The pressure the compressor is delivering to the plant Sump Pressure - The compressor’s internal pressure at the sump tank. Airend Discharge Temperature - The temperature of the air/oil mixture at the discharge of the compression module.
Operator Settings Folder Pages 1 & 2: Operator Settings The below values are all setpoints: Online Pressure - The compressor will load when the package discharge pressure falls below this value Range (in PSI): 65 to Offline Pressure - 10...
Page 47
Offline Pressure - The compressor will unload when package discharge pressure rises above this value. Range (in PSI): 75 to Rated Pressure + 10 Lead/Lag - When this box is checked the compressor is operating as a lead machine. Unchecking the box causes the machine to run as a lag machine.
Page 48
Mod/ACS - The compressor will initially start out in online offline mode. If the compressor goes through 3 load/unload cycles within 3 minutes, it will switch over into Modulation mode. It will remain in modulation until the stop button is pressed or 3 minutes pass between an unload and load command.
Page 50
The below values are all setpoints: Enable Auto-Restart - Enabling this will allow the compressor to stop if it has been running unloaded for a period of time, and the motor has exceeded its minimum running time (10 minute in most cases). Auto-Restart Time - The time period the compressor must run unloaded before stopping in auto-restart.
Page 51
pressure rises above the offline setpoint. Both this time period and the minimum motor run timer (10 minutes) must be satisfied before the compressor will stop in auto restart. Range (in seconds) 120 - 3600 Auto-Restart Delay - The time period after the package discharge pressure has fallen below the online setpoint before the compressor can automatically restart.
Page 52
day, hour, and minute of the scheduled start setpoints. Scheduled Start/Stop is an option and the option module must be purchased and installed before this feature can be turned on. Scheduled Start Hour - Hour of the day for which a scheduled start will be performed.
* The low ambient temperature is only adjustable if the low ambient factory set point is on. ** A value of 0 will disable the lead/lag cycle time feature. Page 7: Sensor Calibration Sensor calibration can only take place when the machine is stopped and there is no pressure on the sensor.
Page 54
Note: If a sensor is currently reading a value that is +/- 10% of its range from zero, the sensor will not be able to be calibrated and a warning will be logged in the event log. Always make sure the sensor is exposed to atmosphere before attempting calibration.
Events Folder Pages 1 to a Max of 50: Event History The pages in the Events folder document up to the last 250 events that the controller has experienced, with the time and date of the occurrence. The events are recorded in sequence, with number one being the newest and 250 being the oldest.
Page 56
The following items will generate an event. Power On Power Off Press the Start Key Press the Stop Key Press the Load Key Press the Unload Key Starting the compressor remotely Stopping the compressor remotely ...
Active Start Inhibits will be listed in the Event log, but not have an icon present. The display will indicate the compressor is not ready to start if a start inhibit is active. Warning Events List Sensor Failure - Xe-70M On-Screen Text: 7ATT Failure This will occur whenever sensor 7ATT is recognized as missing or broken.
Page 58
warning would occur if the sump pressure goes above 125 psi in this example. This condition must exist for 3 seconds before the warning is issued. Service Service warnings occur when the unit has operated a certain number of hours, based on the total hours. Service warnings can have multiple levels, depending on the service level selection.
Page 59
complete factory set point. Once the service complete factory set point is set, indicating the service is completed, the time for the next “SERVICE REQUIRED” warning will be calculated by adding the service time period to the total hours value, with the “100 HOURS TO SERVICE”...
Page 60
The contact must be open for at least 3 seconds before the warning will occur. However, this switch is a locking switch. The dryer high pressure switch must be reset (contact closed) before this warning can be reset. If this warning is reset while the conditions for running the dryer exist, the dryer can restart.
Trip Events List Low Sump Pressure - Xe-70M On-Screen Text: Low Sump Press Will occur if the unit is running unloaded or loaded and 3APT is less than 13 psi for 15 seconds. High Airend Discharge Temperature - Xe-70M On- Screen Text: High A/E Disch T This will occur if 2ATT is greater than 228°F and the unit is running.
Page 62
checked after each start until correct motor rotation is established. Correct motor rotation is established when the controller reads a sump pressure of 1 psi or more within 3 seconds of starting. Overload - Xe-70M On-Screen Text: Overload This will occur if the fan or motor overload relays opens. The contact must be open for at least 3 seconds before the trip will occur.
High Sump Pressure - Xe-70M On-Screen Text: High Sump Pres This will occur if the compressor is running loaded for at least 8 seconds, and any one of the 3 following conditions exist. (1) The sump pressure is above the rated pressure by 35 psi.
Trip History Pages 1 to a Max of 3: Trip History The pages in the Trips History folder document up to the last 15 trips that the controller has experienced and time stamps each. The trips are recorded in sequence, with number one being the newest and 15 being the oldest.
While the dialog box is active, press the left and right keys in order to scroll through the displayed data. The name of the trip will always be shown in the title bar of the dialog box. Press enter when finished viewing the data to return to the trip history screen.
This page displays the status of the filters. The filter status will either be “OK” or “Change” depending on the compressor’s diagnostic readings. If a filter reaches the “change’ status, a warning will be issued and the service indicator will light up to notify the user. Note that the compressor must be in a “Running Loaded”...
Note: After changing the Service Interval a Reset must be performed to set the Hours Until Service to the proper value. General Settings Folder Page 1: Language and Units Selection Language is selectable from the following 30 selections: English (default) Finnish Latvian Slovak...
The controller will display all screens in the selected language and only one language can be selected at a time. Each language appears in its native translation. Temperature is selectable between °F and °C. Pressure is selectable between psi, kpa, bar, kg/cm Page 2: Time &...
The controller will continue to display any changes, even when the selections have not been confirmed and the user exits the page, then returns. Cycling of the power returns all selections to their current settings. Note: The controller does not support Daylight Savings Time.
Page 4: Serial Port Address Settings This page allows the user to set up the network addresses for the RS-485 networks the controller is capable of communicating with. RS485 Protocol - Allows the serial port to be configured to Airbus (used for X-Series system controllers and integral sequencing) or Modbus protocols MODBUS Address - Sets the modbus node ID for the controller to communicate with a Modbus capable device,...
Pages 5 - 7: Ethernet Settings (ECO Module Only) IP Address Setting - When DHCP is not enabled, this setpoint sets the IP address of the controller. IP Address Actual - This will match the IP address setting when DHCP is not enabled. If DHCP is enabled this will display the address assigned to the controller by the DHCP server.
Enable DHCP - Allow the controller to automatically receive an IP address from the Local Area Network (LAN) Apply - After editing the desired setpoint navigate to the accept setting and press enter in order for the values in the setting variables to be confirmed by the controller.
Page 73
another compressor is based on the pressure reading from the compressor assigned as the integral sequencing master. Lastly, note that the Active Protocol on the general settings tab must be set to Airbus485 for integral sequencing to operate properly. Certain functions may interfere with compressors loading and unloading: ...
Page 1: Setup Integral Sequencing - Enabling Integral Sequencing chooses this compressor to be the sequence Master. The master’s package discharge pressure sensor will be the pressure signal used for the system. The default is disabled. Make sure all compressors are set up for integral sequencing before enabling this function.
unload pressure should always be set lower than the local offline setpoint of compressors in the system. The system unload pressure should always be set lower than the local offline setpoint of compressors in the system. Note that when under system control, the compressor will ignore the local pressure setpoints except for protective functions.
Tolerance - The pressure control “Tolerance” setting, which is used to tell the system how to respond to changes in pressure above and below the load/ unload pressures. The default is 3.0 psi and should not normally be changed. Number of Compressors - Defines how many compressors are in the system.
Page 4: Rotation Sequence - Displays the current load/unload order of the system. Each compressor in the system is assigned a letter. The letter indicates whether the machine with the assigned Airbus address is a lead machine (loads first, unloads last) or one of the trim machines. Letter A is assigned to the lead machine, B to the next machine to load, C to the third machine to load, and D to the final machine to load.
Rotation Interval - Determines the time period between sequence rotations. Time Left - Counts down the time until the sequence rotation will occur. System Pressure - Shows the current pressure reading that the system is using for control. This will only be shown on the sequence Master controller.
Airend Discharge Temperature - The temperature of the air/oil mixture at the discharge of the compression module. Aftercooler Discharge Temperature - The temperature of the air after passing through the Aftercooler. Note that this will only be shown if the Low Ambient option has been purchased and installed.
Running Hours - The number of hours the compressor’s motor has been running Loaded Hours - The number of hours the compressor has been producing air Real Time Clock - Current time of day Pages 3 & 4: Digital Inputs...
Each digital input will have an indication showing whether the input is in an “OPEN” or “CLOSED” state. This is the physical state of the input and may not necessarily line up with the logical condition. The normal state is shown in the table below.
Page 82
Each digital output will have an indication showing whether the output is in an “OPEN” or “CLOSED” state. This is the physical state of the input and may not necessarily line up with the logical condition. The normal state is shown in the list below: ...
Page 7: Analog Outputs The value for the analog outputs will be in mA: VSD Blower Output - Current speed of the VSD blower (if installed) Page 8: CT Inputs...
Displays the mA value of the current transformers installed on each leg of the motor incoming power: CT1 CT2 CT3 Factory Settings Folder This folder is for IR factory and service personnel. The password “2010” must be entered on page one in order to adjust values in this folder.
valid password has not been entered or it has timed out. This is read only. Password timeout enable - Checking this box will enable the password time feature. Password timeout - This timeout along with the password timeout enable allows the user to set an adjustable amount of time to require a valid password to be re- entered.
Page 86
Rated Pressure (psi - 100, 115, 135, 190) - This is the nominal pressure that the compressor can provide.
Page 87
Starter Type (Star-delta, Remote Starter, Soft Starter) - Choose the starter type installed in the compressor. If this is not set correctly, the compressor may not start. Service Level (0, 1, or 2) - Set the service level reminders for the compressor. ...
Page 88
Enable PAC (On/Off) - Enables Progressive Adaptive Control - this will reduce operating pressure in the case of a Change HE Filter warning or High Sump Pressure warning in order to protect the compressor. Enable Dryer (On/Off) - Enables dryer control from the controller.
Power On Hours (Read Only) Pages 7 - 8: Software Version These pages are used for displaying software information for the controller. All items are read only.
Connection to the MODBUS Network The Xe-70M controller is designed to interface to any MODBUS RTU master capable device using Belden 9841 or equivalent RS-485 cable. In order to connect to the network, the cable must be connected to port X04 on the controller as shown below: RS-485 Network RS-485 data communications and other low voltage...
attach the RS-485 or signal cable on the outside of an earthed cable tray such that the cable tray forms an earthed electrical interference shield. 3. Where possible, never route an RS-485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications...
The MODBUS address for each compressor is set on the General Settings Tab, Page 4. The controller’s default MODBUS Address setting is 1. Additionally, the active protocol must be set to MODBUS Slave. MODBUS Master Settings In order to communicate properly with the Xe-70M controller, the MODBUS master must be set to communicate with the following configuration: Baud Rate - 9600...
Wiring Schematics The following wiring schematics are provided for reference and example purposes only. Some terminations may not be shown or may be incorrect for your application. Always refer to the wiring schematics and drawings specific to your compressor for the most accurate information. List of Schematics and Drawings: UP6S 15-30HP / UP5S 11-22KW Xe-70M Fixed Speed - Star Delta (48775233 Rev E)
X-Series System Controls Connection The Xe-70M controller is designed to interface to an Ingersoll Rand X-Series System Controller using Belden 9841 or equivalent RS-485 cable. In order to connect to the network, the cable must be connected to port X04 on the controller as shown in the diagrams below.
Page 106
attach the RS-485 or signal cable on the outside of an earthed cable tray such that the cable tray forms an earthed electrical interference shield. Where possible, never route an RS-485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).
RS-485 Address Selection Each compressor connected to the network will have a unique assigned address, starting at compressor 1 increasing sequentially to the number of compressors connected to the network. The RS-485 address for each compressor is set on the General Settings Tab, Page 4.
Page 108
Additionally, for fixed speed machines, make sure that the Enable Auto-Restart setpoint is enabled (checkbox is filled in) or the compressor will continue to run when unloaded by the system controller. After the address and COM control have been set, be sure that Integral Sequencing is disabled by navigating to Integral Sequencing, page 1 and verifying that the Integral sequencing setpoint is disabled (checkbox not filled in) as...
Page 109
Once these setpoints are correctly set and the machine is started locally, the system controller should see status information from the compressor and be able to take control.
Page 110
Change Log April 2018: Initial Release...
Need help?
Do you have a question about the Xe-50M and is the answer not in the manual?
Questions and answers
is there a way to test this controller mine is not functioning Xe-50m is there a phone to call I'm old and prefer phone calls to emailing
To test an Ingersoll-Rand Xe-50M controller that is not functioning, follow these steps using the available information:
1. Check Power Supply: Ensure the controller is receiving power. If not, inspect the voltage transformer and power connections.
2. Verify Motor Rotation: If the controller shows "Ck Motor Rot", check that the motor is rotating correctly. Correct rotation is confirmed when the sump pressure reaches 1 psi or more within 3 seconds of starting (6 seconds for soft starters or if the temperature is below 50°F).
3. Check for Overload: If the display shows "Overload", inspect the motor and fan overload relays. A trip occurs if the relay is open for at least 3 seconds.
4. Remote Stop Issue: If "Rem Stop Fail" appears, confirm that the remote stop/start option is properly configured and the stop button is not stuck in the open position.
5. Inspect Communication Connections: If connecting to a MODBUS network, ensure RS-485 cables are correctly connected to port X04 and properly shielded and routed to avoid electrical interference.
If these checks do not identify the issue, further diagnostics or professional service may be needed.
This answer is automatically generated