Page 1
AIR CONDITIONING SYSTEMS MULTI SPLIT UNIT • SERVICE MANUAL MODELS: LV6CI-12WiFiR LV6DI-12WiFiR LV6LI-12WiFiR LV6CI-18WiFiR LV6DI-18WiFiR LV6LI-18WiFiR ENGLISH...
Page 3
Table of Contents §. Safety Precautions Precautions Information servicing §. Model Reference & External Appearance Model Reference External Appearance §. Indoor Unit Indoor Unit - Compact Four-way Cassette Type Indoor Unit - New Four-way Cassette Type Indoor Unit - A6 Duct Type Indoor Unit - Floor Ceiling Type §.
Page 4
Table of Contents §. Troubleshooting Safety Caution General Troubleshooting Information Inquiry Outdoor Unit Point Check Function Error Diagnosis and Troubleshooting Without Error Code Quick Maintenance by Error Code Troubleshooting by Error Code Check Procedures §. Indoor Unit Disassembly Indoor Unit - Compact Four-way Cassette Type Indoor Unit - New Four-way Cassette Type Indoor Unit - A6 Duct Type Indoor Unit - Floor Ceiling Type...
1. Precautions CAUTION To prevent personal injury, or property or unit damage, • • While unpacking be careful of sharp edges around adhere to all precautionary measures and instructions the unit as well as the edges of the fins on the con- denser and evaporator.
Page 8
2. Information servicing(For • Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable flammable materials) hazards or ignition risks. • NO SMOKING signs shall be displayed. Checks to the area Ventilated area •...
• that capacitors are discharged: this shall be done in shall also take into account the effects of aging or a safe manner to avoid possibility of sparking; continual vibration from sources such as compressors or fans. • that there no live electrical components and wiring are exposed while charging, recovering or purging 2.13 Detection of flammable refrigerants the system;...
• The refrigerant charge shall be recovered into the • Before attempting the procedure ensure that: correct recovery cylinders. The system shall be flushed • mechanical handling equipment is available, if with OFN to render the unit safe. This process may required, for handling refrigerant cylinders;...
Page 11
• Empty recovery cylinders are evacuated and, if • The recovered refrigerant shall be returned to the possible, cooled before recovery occurs. refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not • The recovery equipment shall be in good working mix refrigerants in recovery units and especially not in order with a set of instructions concerning the cylinders.
Model Reference Contents Model Reference ....................2 External Appearance .....................3...
Page 13
Refer to the following table to determine the specific indoor and outdoor unit model number of your purchased equipment. Note: Check you are using the right power supply for your model. Power Supply Intake : Outdoor Units Capacity Indoor Unit Model Power Supply (Btu/h) Cassette LV6CI-12WiFiR 1Φ, 220-240V~, Duct LV6DI-12WiFiR 50Hz Console LV6LI-12WiFiR Cassette LV6CI-18WiFiR 1Φ, 220-240V~,...
1. Feature Compact design • The body size is 570×260×570mm, it’s just smaller than the ceiling board, so it’s very easy for installation and will not damage the decoration. The panel size is 647×50×647mm. • The hooks are designed in the four corners of the body, which can save installation space. Fire-proof Controller Box •...
Fresh Air • Fresh air intake function brings you fresh and comfortable air feeling. Wired Controller(Optional) • Compared with infrared remote controller, wired controller can be fixed on the wall and avoid mislaying. It's mainly used for commercial zone and makes air conditioner control more convenient. Louver Position Memory (Standard for ERP models) •...
5. Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to in- stall the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. Name Shape Quantity Installation paper template (some...
-Sound level will vary depending on a range of factors such as the construction -(acoustic absorption coefficient) of particular room in which the equipment is installed. -The operating conditions are assumed to be standard. LV6CI-12WiFiR LV6CI-18WiFiR IDU-Compact Cassette 22...
4×1.0(4x2.5 with auxiliary electric Wiring Strong Electric Signal(mm heater) NOTE: Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A. 11. Electrical Wiring Diagrams IDU Model IDU Wiring Diagram LV6CI-12WiFiR 16022500004023 LV6CI-18WiFiR Abbreviation Paraphrase Yellow-Green Conductor CAP1 Indoor Fan Capacitor...
10.1 Some connectors introduce: A For remote control (ON-OFF) terminal port CN23 and short connector of JR6 1. Remove the short connector of JR6 when you use ON-OFF function; 2. When remote switch off (OPEN) ;the unit would be off; 3.
Page 40
B For ALARM terminal port CN33 1. Provide the terminal port to connect ALARM ,but no voltage of the terminal port , the power from the ALARM system (not from the unit ) 2. Although design voltage can support higher voltage ,but we strongly ask you connect the power less than 24V, current less than 0.5A 3.
Page 41
C. For new fresh motor terminal port CN8 1. Connect the fan motor to the port , no need care L/N of the motor ; 2. The output voltage is the power supply; 3. The fresh motor can not excess 200W or 1A , follow the smaller one ; 4.
Page 42
10.2 Micro-Switch Introduce: A. Micro-switch SW1 is for selection of indoor fan stop temperature (TEL0) when it is in anti-cold wind action in heating mode. Range: 24 C, 15 C, 8 C, According to EEROM setting (reserved for special customizing). B.Micro-switch SW2 is for selection of indoor FAN ACTION if room temperature reaches the setponit and the compressor stops.
Page 43
C.Micro-switch SW3 is for selection of auto-restart function. Range: Active, inactive SWITCH FOR MODE-PRIOR SETTING STATE COOL HEAT MODE HEAT COOL Factory Setting D. Micro-switch SW5 is for setting mode priority of multi connection. Range: Heat, cool. E.Micro-switch SW6 is for selection of temperature compensation in heating mode. This helps to reduce the real temperature difference between ceiling and floor so that the unit could run properly.
Page 44
G.Micro-switch S1 and dial-switch S2 are for address setting when you want to control this unit by a central controller. Range: 00-63 32~35 36~53 54~71 72~90 91~105 106~140 141~160 161~200 H. Dial-switch ENC1: The indoor PCB is universal designed for whole series units from 7K to 68K. This ENC1 setting will tell the main program what size the unit is.
Page 45
Indoor Unit - Duct Contents Feature........................2 Dimensional Drawings ..................4 Part names ......................5 Service Place ......................5 Accessories ......................6 Fan Performance ....................7 Capacity Tables ....................12 Noise Criterion Curves ..................27 Electrical Characteristics ..................29 Electrical Wiring Diagrams ..................29...
1. Feature Eccentric Fan Design New eccentric fan design improves the airflow at the air outlet, resulting better performance. Slim Design The industry lowest height is designed to be fitted into tight roof space. Flexible Air Intake The frame size of air inlet in rear and bottom is the same. It’s very easy to switch to match different applications.
Page 47
Built-in Drain Pump(Optional) The built-in drain pump can lift condensing water up to 750mm. Easy Clean You can pull out the filter from left, right, or from the bottom for easy cleaning. IDU-A6 Duct 3 ...
3. Part names Air inlet Electric control box Air lter(on some models) Drain hose Air outlet Refrigerant connecting pipe 4. Service Place Air outlet (30cm) 11.8 (20cm) Air inlet 23.6 x23.6 (60cmx60cm) checking orifice IDU-A6 Duct 5 ...
5. Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to in- stall the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. Name Shape Quantity Soundproof / insulation sheath...
8. Noise Criterion Curves Indoor Unit Notes: -Sound measured at 1.5m away from the center of the unit. -Data is valid at free field condition -Data is valid at nominal operation condition -Reference acoustic pressure OdB = 20µPa -Sound level will vary depending on a range of factors such as the construction -(acoustic absorption coefficient) of particular room in which the equipment is installed.
9. Electrical Characteristics Capacity (Btu/h) 12K~18k Phase 1-phase Frequency and 220-240V, 50Hz Voltage OUDOOR UNIT POWER Power Wiring 3×1.5 Circuit Breaker/ 25/20 Fuse (A) Weak Electric Signal)(mm Indoor/Outdoor Connecting 4×1.0(4x2.5 with Strong Electric Wiring auxiliary electric Signal(mm heater) NOTE: Electric auxiliary heating type circuit breaker/fuse need to add more than 10 A. 10.
10.1 Some connectors introduce: A. For new fresh motor terminal port (also for Anion generator) CN43: 1. Connect the fan motor to the port, no need care L/N of the motor; 2. The output voltage is the power supply; 3. The fresh motor can not excess 200W or 1A, follow the smaller one; 4.
Page 63
B For ALARM terminal port CN33 1. Provide the terminal port to connect ALARM, but no voltage of the terminal port, the power from the ALARM system (not from the unit); 2. Although design voltage can support higher voltage, but we strongly ask you connect the power less than 24V, current less than 0.5A;...
Page 64
C. For remote control (ON-OFF) terminal port CN23 and short connector of J7 1. Remove the short connector of J7 when you use ON-OFF function; 2. When remote switch off (OPEN); the unit would be off; 3. When remote switch on (CLOSE); the unit would be on; 4.
Page 65
10.2 Micro-Switch Introduce: FOR ANTI-COLD WIND EEPROM TEL0 DEFAULT FACTORY SETTING A. Micro-switch SW1 is for selection of indoor fan stop temperature (TEL0) when it is in anti-cold wind action in heating mode. Range: 24°C, 15°C, 8°C, according to EEROM setting (reserved for special customizing). FOR SETTING FAN MOTOR CONTROL WHEN THERE IS NO DEMAND MO DE...
Page 66
FOR TEMP. COMPENSATION(HEATING) EEPROM CODE DEFAULT FACTORY SETTING D. Micro-switch SW6 is for selection of temperature compensation in heating mode. This helps to reduce the real temperature difference between ceiling and floor so that the unit could run properly. If the height of installation is lower, smaller value could be chosen.
Page 67
Indoor Unit-Console Contents Feature........................2 Dimensional Drawings ..................4 Part names ......................5 Service Place ......................5 Accessories ......................6 Air Velocity and Temperature Distributions ............8 Capacity Tables ....................10 Noise Criterion Curves ..................16 Electrical Characteristics ..................17 Electrical Wiring Diagrams ..................17...
1. Feature An Elegant And Compact Design • The look of newly-upgraded console unit features flowing lines that is aesthetic enough. • Its unobtrusive design can easily fit into most interiors with different decorating-schemes. • The width of the machine has been reduced by 10mm, taking less space. A Perfect Choice For New Buildings And Renovation Projects •...
• Wide Airflow & Constant Comfort-Dual air outlets satisfy both cooling and heating needs in different seasons and allows a quick comfort of the room. *Compared to last generation console unit Air Quality We care your indoor air quality from many perspectives •...
3. Part names Air flow louver (at air outlet) Display panel Air inlet (with air filter in it) Refrigerant connecting pipe Air flow louver (at air outlet) Drain hose 4. Service Place ≥100mm ≥1000mm IDU-New Console 5 ...
5. Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to in- stall the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. Name Shape Quantity Remote controller...
Page 73
Transfer connector(Φ12.7-Φ15.9)/(Φ0.5in-Φ0.63in)(Packed with the indoor unit) NOTE: Pipe size may differ from appliance to appliance. To meet different pipe size requirements, sometimes (on some models) the pipe connections need a transfer connector installed on the outdoor unit . Transfer connector(Φ6.35-Φ9.52)/(Φ0.25in-Φ0.37in)(Packed with the indoor unit) NOTE: Pipe size may differ from appliance to appliance.
8. Noise Criterion Curves Notes: -Sound measured at 1.5m away from the noisiest location of the unit. -Data is valid at free field condition -Data is valid at nominal operation condition -Reference acoustic pressure OdB = 20µPa -Sound level will vary depending on a range of factors such as the construction -(acoustic absorption coefficient) of particular room in which the equipment is installed.
9. Electrical Characteristics Capacity (Btu/h) Phase 1-phase 1-phase Frequency and Voltage 220-240V, 50Hz 220-240V, 50Hz Oudoor Unit Power Power Wiring (mm 3×1.5 3×2.5 Circuit Breaker/ Fuse (A) 20/16 20/16 Weak Electric Signal)(mm Indoor/Outdoor 4×1.0(4x2.5 with auxiliary 4×1.0(4x2.5 with auxiliary Connecting Wiring Strong Electric Signal(mm electric heater) electric heater)
1. Installation Overview Indoor Unit Indoor Unit Install the indoor unit Install the outdoor unit Install the drainpipe Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Install the panel Perform a test run (only for cassette type) ...
2. Location selection 2.1 Unit location selection can refer to installation manual. 2.2 DO NOT install the unit in the following locations: • Where oil drilling or fracking is taking place. • Coastal areas with high salt content in the air. •...
3. Indoor Unit Installation(Compact Cassette Type 3.1 Service space for indoor unit Suspension bolt pitch dimensions Body dimensions Decoration panel dimensions Refrigerant piping Suspension bolt (×4) Ceiling opening dimensions Hanger bracket Ceiling board 2. Drill 4 holes 5cm (2”) deep at the ceiling hook positions in the internal ceiling.
Page 89
3.3.1 Remove the front grille unit and the four sides of false ceiling are even. The 1. Slide the 2 grille hooks toward the middle of the bottom of the unit should be 24mm / 0.9in higher than decoration panel. ceiling board.
Page 90
3.3.6 Close the front grille, and close the two grille 3.3.3 Mount the grille hooks. Ensure that the buckles at the back of the grille be properly seated in the groove of the panel. 3.3.4 Connect the two wires of the panel to the main board of the unit.
Page 91
3. Indoor Unit Installation(Duct) 5. Drill 4 holes 10cm (4”) deep at the ceiling hook positions in the internal ceiling. Be sure to hold the drill at 3.1 Service space for indoor unit a 90° angle to the ceiling. 6. Secure the bolt using the included washers and nuts. >...
Page 92
NOTE: 1. Do not put the connecting duct weight on the 3. When installing the filter mesh, fit it into the flange as indoor unit. illustrated in the following figure. 2. When connecting the duct, use an nonflammable canvas tie-in to prevent vibrating. 3.
3.6 Horizontal Installation Remove the cover 3.6.1 With External pump (9K, 12K models) Cut both ends of the rubber hose into a straight one, use it to connect the drain Connector A and the external Unplug the “PUMP” pin pump and safety it with clamps on both ends. Then Short connect the “CN5”...
3. Indoor Unit Installation NOTE: It is recommended to fx it on the wall according to the hanging hole indicated by the arrow on the mounting (Console) plate. Mounting plate must be installed horizontally. 3.1 Service space for indoor unit Mounting plate ≥100mm Tapping...
open the piping cover plate. Two buckles Refrigerant pipe Drain-pipe Power cord NOTE: In order to drain smoothly, the position of the drain pipe must refer to the above figure when discharging the right pipe. • Installation with skirting line 2.
4. Outdoor unit installation 4.3 Install Outdoor Unit Fix the outdoor unit with anchor bolts(M10) 4.1 Service space for outdoor unit >60cm / 23.6” Fix with bolts Caution Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
For Vertical drainage pipe (The following table is for 5. Drainage Pipe Installation reference) Install the drainage pipe as shown below and take Reference measures against condensation. Improperly installation Allowable value of inner could lead to leakage and eventually wet furniture and maximum water Remark pipe...
Page 99
• The air outlet shall face down to prevent dirt enter- ing pipe. • Each indoor unit of the system should be installed it. • The installation should be considering the conve- nience for future cleaning. • The correct installation will not cause converse water flow and the slope of the branch pipes can be adjusted freely •...
6. Refrigerant Pipe Installation Indoor unit/ Outdoor unit 6.1 Maximum length and drop height Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in the following table.
4. Rain water might penetrate into pipeline during 8. Additional Refrigerant Charge construction. • After the vacuum drying process is carried out, the additional refrigerant charge process need to be performed. Procedures of special vacuum drying are as follows: • The outdoor unit is factory charged with refrigerant.
9 . Engineering of Insulation insulation and cause easy aging of the material. 9.2 Insulation of drainage pipe 9.1 Insulation of refrigerant pipe 1. Operational procedure of refrigerant pipe 1. Operational procedure of refrigerant pipe insulation insulation Select the suitable pipe → insulation (except joint section) Cut the suitable pipe →...
Engineering of Electrical Wring 11. Test Operation 1. Highlights of electrical wiring installation 1. The test operation must be carried out after the entire installation has been • All field wiring construction should be finished by qualified electrician. completed. • Air conditioning equipment should be grounded ac- 2.
4. Drainage Test a. Ensure the drainpipe flow smoothly. New buildings should perform this test before finishing the ceiling. b. Remove the test cover. Add 2000ml of water to the tank through the attached tube. c. Turn on the main power switch and run the air conditioner in COOL mode.
Maintenance Contents First Time Installation Check .................2 Refrigerant Recharge ....................4 Re-Installation .......................5 Indoor Unit ....................5 Outdoor Unit ....................7...
1. First Time Installation Check Air and moisture trapped in the refrigerant system affects To prevent air and moisture from affecting the air the performance of the air conditioner by: conditioner’s performance, the indoor unit, as well as the pipes between the indoor and outdoor unit, must be be •...
Page 108
Procedure: • If the pressure successfully reaches -0.1 MPa Tighten the flare nuts of the indoor and outdoor (14.5 Psi), fully close the Handle Lo valve, then units, and confirm that both the 2- and 3-way valves cease vacuum pump operations. are closed.
2. Refrigerant Recharge mA A Procedure: Close both 2- and 3-way valves. 3-way valves. Slightly connect the Handle Lo charge hose to the Operate the air conditioner in cooling mode to charge 3-way service port. the system with liquid refrigerant. Connect the charge hose to the valve at the bottom When the electronic scale displays the correct of the cylinder.
3. Re-Installation Indoor Unit Collecting the refrigerant into the outdoor unit Procedure: Confirm that the 2- and 3-way valves are opened. Close the 3-way valve so that the gauge rests between 0.3 MPa (43.5 Psi) and 0.5 MPa (72.5 Psi). Connect the charge hose with the push pin of Handle Lo to the 3-way valve’s gas service port.
Page 111
Air purging with vacuum pump Procedure: • If the pressure successfully reaches -0.1 MPa Tighten the flare nuts of the indoor and outdoor (14.5 Psi), fully close the Handle Lo valve, then units, and confirm that both the 2- and 3-way valves cease vacuum pump operations.
Outdoor Unit Evacuation for the whole system Procedure: Wait for 5 minutes then check whether the gauge Confirm that the 2- and 3-way valves are opened. needle moves after turning off the vacuum pump. If Connect the vacuum pump to the 3-way valve’s the gauge needle moves backward, check whether service port.
Refrigerant charging mA A Procedure: Close both 2- and 3-way valves. Fully open the Handle Lo manifold valve, 2- and 3-way valves. Slightly connect the Handle Lo charge hose to the 3-way service port. Operate the air conditioner in cooling mode to charge the system with liquid refrigerant.
Page 114
Product Features Contents Display Function ....................2 Safety Features ......................5 Basic Functions .......................6 Table ......................6 Abbreviation ....................7 Fan Mode ......................7 Cooling Mode ....................7 Heating Mode(Heat Pump Units) ..............8 Auto-mode ....................9 Drying Mode ....................10 Forced Operation Function ................10 Timer Function ....................10 3.10 Sleep Function .....................10 3.11 Auto-Restart Function ..................10 Optional Functions ....................11 Remote Controller Functions ................12...
1. Display Function Duct Type Compact Cassette Type Console Type Display Function ECO function (available on select units only) When Wireless Control feature is activated (some units) Temperature value Temperature Timer ON is set. (3s) Activation of Swing, Boost, Silence or UV-C lamp Timer OFF is set.
2. Safety Features Compressor three-minute delay at restart Compressor functions are delayed for up to ten seconds upon the first startup of the unit, and are delayed for up to three minutes upon subsequent unit restarts. Automatic shutoff based on discharge temperature If the compressor discharge temperature exceeds a certain level for nine seconds, the compressor ceases operation.
3. Basic Functions Table Cooling Mode&Heating mode Heating Mode Functions Anti-cold Air Outdoor Fan Control Defrosting Mode Function Case 1: Cases Compressor Case 2:T4 Case 1 Case 2 Case 1 Case 2 Frequency and T4 Model Functions Auto mode Cases Case 1 Case 2 Case 3...
Abbreviation 120 minutes. • If the following conditions are satisfied, the Unit element abbreviations compressor ceases operation. • Calculated frequency(fb) is less than minimum limit Abbreviation Element frequency(FminC). Indoor room temperature • Compressor runs at FminC more than 10 minutes. Coil temperature of evaporator •...
Case 2: • If one of the following conditions is satisfied, not judge protective time. • The outdoor unit will be run at different fan speed • Compressor running frequency is more than test according to T4. frequency. • For different outdoor units, the fan speeds are •...
to 60%(Medium); Case 1: • When T1-Tsc is higher than 0.5°C, fan speed • T3 is lower than 3°C(37.4°F) and compressor reduces to 40%(Low); running time is more than 120 minutes, at this • When T1-Tsc is higher than 1°C, fan speed reduces time, if T3 is lower than TCDI1+4°C(39.2°F) for 3 to 20%(Low);.
• Low Room Temperature Protection ∆T Running mode If the room temperature is lower than 10°C, the ∆T>2°C(3.6°F) Cooling compressor ceases operations and does not resume until -3℃(-5.4°F)≤∆T≤2°C(3.6°F) Fan-only room temperature exceeds 12°C. ∆T<-3°C(-5.4°F) Heating* Forced operation function Heating*: In auto mode, cooling only models run the fan Press the AUTO/COOL button, the AC will run as below •...
• When cooling, the temperature rises 1°C (to not higher than 30°C/86°F) every hour. After 2 hours, the temperature stops rising and the indoor fan is fixed at low speed. • When heating, the temperature decreases 1°C(to not lower than 16°C/60.8°F) every hour. After 2 hours, the temperature stops decreasing and the indoor fan is fixed at low speed.
4. Optional Functions Electrical energy consumption control function (Optional) 8°C Heating Press the “Gear” button on remote controller to enter the In heating mode, the temperature can be set to as low energy efficient mode in a sequence of following: as 8°C, preventing the indoor area from freezing if unoccupied during severe cold weather.
5. LCD Wired Remote Controller Infrared Wireless Remote Controller (Standard for some units) 5.1.1 RG10A(B2S)/BGEF Remote Controller Specifications Model RG10A(B2S)/BGEF Rated Voltage 3.0V (Dry batteries R03/LR03×2) Reaching Distance Environment Temperature Range -5°C~60°C(23°F~140°F) Buttons and Functions Product Features ...
Page 125
Remote LCD Screen Indicators Note: All indicators shown in the figure are for the purpose of clear presentation. But during the actual operation, only the relative function signs are shown on the display window. Product Features ...
Page 126
5.2.1 LCD Wired Remote Controller KJR-120X/TFBG-E(Optional) The KJR-120X/TFBG-E wired remote controller is optional for some types. i) ) Buttons and Functions 1. . POWER butt 6. . TIMER butt Turn on of turn off the unit. To set timer on and timer off time of one day 7. FAN SPEED button MODE button Used to select the fan speed.
Page 127
ii) i) LCD Screen 1 Operation mode indication 8 Room temperature indication 2 Fan speed indication 9 Rotating indication 3 Temperature display 10 Follow Me function indication 4 Lock indication 11 Left-right swing indication 5 °C / °F indication (some models) 6 Main unit and secondary unit 12 Clock display indication...
Page 128
iii) Installation • Dimensions 20mm 120mm 46mm 60mm 3) Connection • Wire with the indoor unit: 60mm Wiring hole HA HB • 1: Indoor Unit. • 2: Notch the part for the wiring to pass through with a nipper tool. •...
Page 129
For some models: The wired controller connects to terminal board, terminal board connects to main control board. Main control board Terminal board CN40 ENC1 HA HB HA HB Wired controller 4) Address setting Unit2 Unit16 Unit1 HA HB HA HB HA HB HA HB Wired controller...
5.3 Centralized Controller 1) Connection For Light commercial air conditioner with XYE port, it can be directly connected to Centralized Controller (CCM03, CCM09). 2) Address setting When setting the address, please make sure the unit is powered off. The address can be set from 0 to 63 by the switch. Turn on the unit, then the address will be effective.
5.4 Using the wire controller to set • If there is no change after airflow adjustment in the ventilation paths, be sure to reset automatic airflow external static pressure adjustment. • You can use the unit’s automatic airflow adjustment • If there is no change to ventilation paths after airflow function to set external static pressure.
Troubleshooting Contents Safety Caution .......................3 General Troubleshooting ..................4 Information Inquiry ....................7 Outdoor Unit Point Check Function ..............14 Error Diagnosis and Troubleshooting Without Error Code .......16 Remote maintenance ...................16 Field maintenance ..................17 Quick Maintenance by Error Code ..............22 Troubleshooting by Error Code ................23 EH 00/EH 0A / EC 51 (EEPROM parameter error Diagnosis and Solution) ..23 EL 01 (Indoor and outdoor unit communication error Diagnosis and Solution) 24 EH 03 / EC 07 (Fan speed is operating outside of the normal range )/EC 71(Over...
Page 133
Troubleshooting Contents 7.11 EC 0d (Outdoor unit malfunction Diagnosis and Solution) ......37 7.12 PC 40(Communication error between outdoor main PCB and IPM board diagnosis and solution) ................38 7.13 PC 08(Current overload protection)/PC 44(Outdoor unit zero speed protection)/ PC 46(Compressor speed has been out of control)/PC 49(Compressor overcurrent failure) diagnosis and solution ...........39 7.14 PC 0F(PFC module protection diagnosis and solution) ........41 7.15 EC 72 (Lack phase failure of outdoor DC fan motor diagnosis and solution) .42...
1. Safety Caution WARNING Be sure to turn off all power supplies or disconnect all wires to avoid electric shock. While checking indoor/outdoor PCB, please equip oneself with antistatic gloves or wrist strap to avoid damage to the board. WARNING Electricity remains in capacitors even when the power supply is off.
2. General Troubleshooting Error Display (Indoor Unit) When the indoor unit encounters a recognized error, the operation lamp will flash in a corresponding series, the timer lamp may turn on or begin flashing, and an error code will be displayed. These error codes are described in the following table: Operation Timer...
Page 136
TS46/ 7 times FLASH High pressure protection or low pressure protection (for some models) PC 03 TS35 14 times Outdoor unit malfunction(for some models) TS37 ec 0 2 times Communication error between master and slave unit (for twins system) TS50 EL 11 2 times Another indoor unit malfunction (for twins system)
Outdoor compressor lack phase protection TS43 PC 43 PC 44 Outdoor unit zero speed protection TS39 Outdoor unit IR chip drive failure TS44 PC 45 Compressor speed has been out of control TS39 PC 46 PC 49 Compressor overcurrent failure TS39 High pressure protection TS46...
3. Information Inquiry Duct type &Floor ceiling Type: • To enter information inquiry status, complete the following procedure within ten seconds: • Press LED(or DO NOT DISTURB) 3 times. • Press SWING(or AIR DIRECTION) 3 times. • Finish 1 and 2 within 10 seconds, you will hear beeps for two seconds, which means the unit goes into parameter checking mode.
Page 139
Displayed Displayed code Explanation Meaning Additional Notes value Room temperature 1. All displayed temperatures use actual values. Indoor coil temperature 2. All temperatures are -1F,-1E,-1d,-1c,- -25,-24,-23,-22, displayed in °C regardless Outdoor coil 1b,-1A -21,-20 of remote used. temperature -19—99 -19—99 3.
Page 140
Displayed Displayed code Explanation Meaning Additional Notes value 0-FF Reserved 0-63 0-FF Troubleshooting 9 ...
Page 141
Compact Cassette Type: • To enter information inquiry status, complete the following procedure within ten seconds: • Press LED(or DO NOT DISTURB) 3 times. • Press SWING(or AIR DIRECTION) 3 times. • Finish 1 and 2 within 10 seconds, you will hear beeps for two seconds, which means the unit goes into parameter checking mode.
Console Type: • To enter engineer mode, in power-on or standby mode, and in non-locked state, press the key combination “ON/OFF + Air Speed” for 7s • After entering the engineer mode, the remote control will display icons of “Auto, Cool, Dry, Heat”, and the Battery icon;...
Page 143
Error code of engineer mode Display Error Information EH 00/EH 0A Indoor unit EEPROM parameter error Indoor / outdoor unit communication error EL 01 Communication error between indoor unit and indoor external fan module EH A EH 30 Parameters error of indoor external fan Upper indoor fan speed is operating outside of the normal range(for new console type) EH 31 Lower indoor fan speed is operating outside of the normal range(for new console type)
Page 144
IPM malfunction or IGBT over-strong current protection PC 00 Over low voltage protection PC 10 Over voltage protection PC 11 DC voltage protection PC 12 Top temperature protection of compressor or High temperature protection of IPM module pc 02 Communication error between outdoor main chip and compressor driven chip PC 40 Current Input detection protection Pc 41...
4. Outdoor Unit Point Check Function(for some models) • A check switch is included on the outdoor PCB. • Push SW1 to check the unit’s status while running. The digital display shows the following codes each time the SW1 is pushed. Number of Display Remark...
Page 146
Frequency limit caused by The display value is a Bit7 IGBT radiator hexidecimal number. Bit6 Frequency limit caused by PFC For example, the Frequency limit caused by digital display show Bit5 high temperature of T2. 2A, then Bit5=1, Frequency limit caused by low Bit3=1, and Bit1=1.
5. Error Diagnosis and Troubleshooting Without Error Code WARNING Be sure to turn off unit before any maintenance to prevent damage or injury. Remote maintenance SUGGESTION: When troubles occur, please check the following points with customers before field maintenance. Problem Solution Unit will not start TS18 - TS19...
Field maintenance Problem Solution Unit will not start TS20 - TS21 Compressor will not start but fans run TS20 - TS21 Compressor and condenser (outdoor) fan will not start TS20 - TS21 Evaporator (indoor) fan will not start TS20 - TS21 Condenser (Outdoor) fan will not start TS20 - TS21 Unit runs, but shortly stops...
Page 149
1.Remote Maintenance Electrical Circuit Refrigerant Circuit Possible causes of trouble Unit will not start ☆ ☆ ☆ ☆ The power switch is on but fans will not start ☆ ☆ ☆ The temperature on the display board cannot be set ☆...
Page 150
1.Remote Maintenance Others Possible causes of trouble Unit will not start The power switch is on but fans will not start ☆ The temperature on the display board cannot be set Unit is on but the wind is not cold(hot) Unit runs, but shortly stops The unit starts up and stops frequently ☆...
Page 151
2.Field Maintenance Refrigerant Circuit Others Possible causes of trouble Unit will not start Compressor will not start but fans run ☆ Compressor and condenser (outdoor) fan will not start Evaporator (indoor) fan will not start Condenser (Outdoor) fan will not start Unit runs, but shortly stops ☆...
Page 152
2.Field Maintenance Electrical Circuit Possible causes of trouble Unit will not start ☆ ☆ ☆ ☆ ☆ ☆ Compressor will not start but fans run ☆ ☆ ☆ ☆ ☆ Compressor and condenser (outdoor) fan will not start ☆ ☆ ☆...
6. Quick Maintenance by Error Code If you do not have the time to test which specific parts are faulty, you can directly change the required parts according the error code. You can find the parts to replace by error code in the following table. Error Code Part requiring replacement...
7. Troubleshooting by Error Code EH 00/ EH 0A / EC 51 (EEPROM Parameter Error Diagnosis and Solution) Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip. Recommended parts to prepare: • Indoor PCB • Outdoor PCB Troubleshooting and repair: Shut off the power supply and turn it on 2 minutes later.
EL 01 (Indoor and Outdoor Unit Communication Error Diagnosis and Solution) Description: Indoor unit can not communicate with outdoor unit Recommended parts to prepare: • Indoor PCB • Outdoor PCB • Reactor Troubleshooting and repair: Power off, then restart the unit after 2 minutes.
Page 156
Remarks: • Use a multimeter to test the DC voltage between 2 port(or S or L2 port) and 3 port(or N or S port) of outdoor unit. The red pin of multimeter connects with 2 port(or S or L2 port) while the black pin is for 3 port(or N or S port) . •...
EH 03 / EC 07 (Fan Speed Is Operating Outside of Normal Range)/EC 71(Over Current Failure of Outdoor DC Fan Motor) Diagnosis and Solution Description: When indoor / outdoor fan speed keeps too low or too high for a certain time, the unit ceases operation and the LED displays the failure.
Page 158
Index: 1. Indoor or Outdoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced. Color Signal Voltage...
Page 159
Port Description Parameter Remark CON1 Power input for the PCB 230V/AC Communication with main PCB Test port 5V/DC For debugging board CN23 UVW output for DC fan motor CON2 Ports for reactor CN1 Communication with main PCB Signal Voltage +15V 0~6V 0~15V 3.
Page 160
CON1 Drive Chip EEPROM FAN1 FAN2 IPM for DC Rectifier Part Description Parameter Remark CON1 Power input for the PCB 192-380V/DC Communication with main PCB Test port 5V/DC For debugging board FAN1 UVW output for DC fan motor FAN2 UVW output for DC fan motor CN1 Communication with main PCB Signal Voltage...
EH 60/EH 61/EC 53/EC 52/EC 54/EC 55/EC 56/EC 50 (Open Circuit or Short Circuit of Temperature Sensor Diagnosis and Solution) Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure. Recommended parts to prepare: •...
EL 0C (Refrigerant Leakage Detection Diagnosis and Solution) Description: Judging the abnormality of the refrigeration system according to the number of compressor stops and the changes in operating parameters caused by excessive exhaust temperature. Recommended parts to prepare: • Indoor PCB •...
EH 0E(Water-Level Alarm Malfunction Diagnosis and Solution) Description: If the sampling voltage is not 5V, the LED displays the failure code. Recommended parts to prepare: • Connection wires • Water-level switch • Water pump • Indoor PCB Shut off the power supply and Shut off the power supply and turn it on 2 minutes later.
PC 00(IPM malfunction or IGBT over-strong current protection)/PC 04(Inverter compressor drive error) Diagnosis and Solution Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the display LED shows “PC 00” and the AC turn off. Or an abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.
PC 01(Over voltage or too low voltage protection)/PC 10(Outdoor unit low AC voltage protection)/PC 11(Outdoor unit main control board DC bus high voltage protection)/PC 12(Outdoor unit main control board DC bus high voltage protection /341 MCE error) Diagnosis and Solution Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
PC 03/PC 31(Low Pressure Protection Diagnosis and Solution) Description: If the sampling voltage is not 5V, the LED displays a failure code. Recommended parts to prepare: • Connection wires • Low pressure protector • Indoor fan assembly • Outdoor PCB Troubleshooting and repair: Low pressure protection Low pressure protection...
7.10 PC 02(Top temperature protection of compressor or High temperature protection of IPM module diagnosis and solution) Description: For some models with overload protection, If the sampling voltage is not 5V, the LED will display the failure. If the temperature of IPM module is higher than a certain value, the LED displays the failure code. Recommended parts to prepare: •...
Check the fastening screws on the PCB and IPM radiator. Replace the outdoor Are they fixed tightly? control PCB. Tighten the screws and apply silicon grease. 7.11 EC 0d(Outdoor unit malfunction Diagnosis and Solution) Description: The indoor unit detect the outdoor unit is error. Recommended parts to prepare: •...
7.12 PC 40(Communication error between outdoor main PCB and IPM board diagnosis and solution) Description: The main PCB cannot detect the IPM board. Recommended parts to prepare: • Connection wires • IPM board • Outdoor main PCB • Electric control box Troubleshooting and repair: Is there at least one LED in Is there at least one LED in...
7.13 PC 08(Current overload protection)/PC 44(Outdoor unit zero speed protection)/ PC 46(Compressor speed has been out of control)/PC 49(Compressor overcurrent failure) diagnosis and solution Description: An abnormal current rise is detected by checking the specified current detection circuit. Recommended parts to prepare: •...
Page 171
Was the protection activated Was the protection activated in standby? in standby? Restart the unit when the power supply Restart the unit when the power supply Is the power voltage is normal? Is the power voltage is normal? returns to normal returns to normal Is outdoor terminal voltage Is the power wiring...
7.14 PC 0F PFC module protection diagnosis and solution) Description: When the voltage signal that IPM send to compressor drive chip is abnormal, the LED displays the failure code and the AC turns off. Recommended parts to prepare: • Connection wires •...
7.15 EC 72 (Lack phase failure of outdoor DC fan motor diagnosis and solution) Description: When the three-phase sampling current of the DC motor is abnormal, especially when the current of one or more phases is always small and almost 0, the LED displays the failure code. Recommended parts to prepare: •...
7.16 PC 43 (Outdoor compressor lack phase protection diagnosis and solution) Description: When the three-phase sampling current of the compressor is abnormal, especially when the current of one or more phases is always small and almost 0, the LED displays the failure code Recommended parts to prepare: •...
7.17 PC 45 (Outdoor unit IR chip drive failure diagnosis and solution) Description: When the IR chip detects its own parameter error, the LED displays the failure code when power on. Recommended parts to prepare: • Inverter module PCB. Troubleshooting and repair: Power off,then restart the unit 2 minutes later.
7.20 PC 30 (High pressure protection diagnosis and solution) Description: Outdoor pressure switch cut off the system because high pressure is higher than 4.4 MPa Recommended parts to prepare: • Connection wires • Pressure switch • Outdoor fan • Outdoor main PCB Troubleshooting and repair: ...
Page 177
High pressure protection High pressure protection Are the high pressure switch Are the high pressure switch Connect high pressure switch and Connect high pressure switch and and main control boar wired and main control boar wired mian control board mian control board correctly? correctly? Is the high pressure...
7.21 PC 0A (High temperature protection of condenser diagnosis and solution) Description: When the outdoor pipe temperature is more than 65°C, the unit stops. It starts again only when the outdoor pipe temperature is less than 52°C. Recommended parts to prepare: •...
7.22 PC 06 (Discharge temperature protection of compressor diagnosis and solution) Description: If the compressor discharge temperature exceeds a certain level for nine seconds, the compressor ceases operation, the LED displays the failure code Recommended parts to prepare: • Connection wires •...
7.23 EL11 (Communication error between master and slave unit (for twins system) Diagnosis and Solution) Description: When set in twins system, master unit and slave unit cannot be recognized normally. Recommended parts to prepare: • Connection wires • Indoor PCB Check the dial switch Check the dial switch Correct the settings...
7.25 EH b3 (Communication error between wired controller and indoor unit Diagnosis and Solution Description: If Indoor PCB does not receive feedback from wired controller, the error displays on the wired controller Recommended parts to prepare: • Connection wires • Indoor PCB •...
7.26 EH bA(Communication malfunction between external fan module and indoor unit)/ EH 3A(External fan DC bus voltage is too low protection)/ EH 3b(External fan DC bus voltage is too high fault) diagnosis and solution Description: Indoor unit does not receive the feedback from external fan module during 150 seconds. or Indoor unit receives abnormal increases or decreases in voltage from external fan module.
8. Check Procedures 8.1 Temperature Sensor Check WARNING Be sure to turn off all power supplies or disconnect all wires to avoid electric shock. Operate after compressor and coil have returned to normal temperature in case of injury. 1. Disconnect the temperature sensor from PCB (Refer to Chapter 5&6. Indoor&Outdoor Unit Disassembly). 2.
Page 184
Resistance KSN98D64UFZ3 KSN140D21UFZ KTM240D43UKT KTM240D57UMT Value Blue-Red Blue-Black 2.7Ω 1.28Ω 1.03Ω 0.62Ω Red-Black Resistance KTF250D22UMT KTF310D43UMT KTQ420D1UMU KSN140D58UFZ Value ATF235D22TMT ATF310D43TMT ATQ420D1SN5A1 Blue-Red Blue-Black 0.75Ω 1.86Ω 0.65Ω 0.37Ω Red-Black Resistance Value ATM150D23TFZ ATH307CDRC8DUL Blue-Red Blue-Black 1.72Ω 1.09Ω Red-Black Note: The picture and the value are only for reference, actual condition and specific value may vary. Troubleshooting ...
8.3 IPM Continuity Check WARNING Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before troubleshooting. 1. Turn off outdoor unit and disconnect power supply. 2. Discharge electrolytic capacitors and ensure all energy-storage unit has been discharged. 3.
Page 186
Indoor Unit Disassembly-Compact Cassette Contents Indoor Unit Disassembly ..................1 Front Panel and Display Board................2 Electrical Parts ....................5 Fan Motor and Fan ..................7 Water Pump ....................9 Evaporator ....................11...
1. Indoor Unit Disassembly Front Panel and Display Board Procedure Illustration 1) Release 2 hooks and open the panel. CJ_MCA_001 ) (see CJ_MCA_001 2) Remove two screws of wire line. (see CJ_MCA_002 ) CJ_MCA_002 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 188
Procedure Illustration 3) Release the hook then pull up the filter(see CJ_MCA_003 ) CJ_MCA_003 4) Remove 4 screws of cover and remove CJ_MCA_004 ) the display board(see CJ_MCA_004 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 189
Procedure Illustration 5) Remove 2 screws of display board and remove PCB.(see CJ_MCA_005 ) CJ_MCA_005 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 4 ...
Page 190
Electrical Parts(Antistatic gloves must be worn.) Note: Remove the front panel (refer to 1.1 Front Panel and display) before disassembling electrical parts. Procedure Illustration 1) Remove 4 screws of the panel and pull up the panel. (see CJ_ MCA_006) CJ_MCA_006 2) Remove 3 screws of electrical cover.
Page 191
Procedure Illustration 3) Disconnect the connectors of PCB. CJ_MCA_008 ) (see CJ_MCA_008 4) Remove 2 screws of main control board and remove PCB.(see MCA_009 ) CJ_MCA_009 5) Remove 2 screws of electronic control box and remove electronic CJ_MCA_010 ) control box.(see CJ_MCA_010 Note: This section is for reference only.
Fan motor and fan Note: Remove the front panel and electrical parts (refer to 1.1 &1.2 ) before disassembling fan motor. Procedure Illustration 1) Remove 4 screws of water collector then remove it.(see CJ_MCA_011 ) CJ_MCA_011 2) Remove the nut of the fan and then CJ_MCA_012 ) pull up the fan.(see CJ_MCA_012...
Page 193
Procedure Illustration 3) Remove the nuts and remove the fan motor(see CJ_MCA_013 ) CJ_MCA_013 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 8 ...
Water Pump Note: Remove the front panel, electrical parts and water collector (refer to 1.1,1.2 &1.3) before disassembling water pump. Procedure Illustration 1) Take off the fasten belt of the water pump. (see CJ_MCA_014) CJ_MCA_014 2) Pinch the metal wire in the direction shown in the figure to release it.
Page 195
Procedure Illustration 3) Remove 3 screws and then remove the water pump. (see CJ_MCA_016) CJ_MCA_016 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 10 ...
Evaporator Note: Remove the front panel, electrical parts and fan(refer to 1.1,1.2 &1.3) before disassembling evaporator. Procedure Illustration 1) Remove 3 screws of pipe clamp board assembly then remove it.(see CJ_MCA_017 ) CJ_MCA_017 2) Remove 4 screws of evaporator fixing board then remove it.(see MCA_018 ) CJ_MCA_018 Note: This section is for reference only.
Page 197
Procedure Illustration 3) Remove 1 screw of evaporator fixing CJ_MCA_019 ) hook and remove it. (see CJ_MCA_019 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 12 ...
Page 198
Indoor Unit Disassembly-New 4-way Cassette Contents Indoor Unit Disassembly ..................1 Front Panel ....................2 Electrical Parts ....................5 Display Board ....................6 Water Pump ....................8 Water Collector & Water Level Switch ............9 Fan Motor and Fan ..................11 Evaporator ....................12...
1. Indoor Unit Disassembly Front Panel Procedure Illustration 1) Push one side of the grille clamp. (see CJ_MCD1_001 ) CJ_MCD1_001 2) Remove one screw then push two grille clamps to remove the air inlet CJ_MCD1_002 ) grille assembly.(see CJ_MCD1_002 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 200
Procedure Illustration 3) Turn over the air inlet grille assembly then pull up the filter. (see MCD1_003 ) CJ_MCD1_003 4) Remove 2 screws and remove the cover of electronic control box. (see CJ_MCD1_004 ) CJ_MCD1_004 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 201
Procedure Illustration 5) Disconnect the connectors of display board and stepper motor and release CJ_MCD1_005 ) the panel. (see CJ_MCD1_005 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 4 ...
Page 202
Electrical Parts (Antistatic gloves must be worn.) Procedure Illustration 1) Remove 3 screws of electronic control box and 1 screw of earth CJ_MCD1_006 ) wire.(see 2) Disconnect the connectors of temperature sensor, pump, motor Earth wire and water level switch. (see MCD1_006 ) 3) Remove the electronic control box CJ_MCD1_006 )
Display Board Procedure Illustration 1) Open the install cover assembly(with display board) (see CJ_MCD1_008) CJ_MCD1_008 2) Remove 1 screw of display window board. (see CJ_MCD1_009) CJ_MCD1_009 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 6 ...
Page 204
Procedure Illustration 3) Turn over the display board, push the swtich to remove the display board. (see CJ_MCD1_010) CJ_MCD1_010 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 7 ...
Water Pump Procedure Illustration 1) Remove 5 screws fixing external water pump box assembly.(see CJ_ MCD1_011) CJ_MCD1_011 2) Remove the water pump box assembly. (see CJ_MCD1_012) CJ_MCD1_012 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 8 ...
Page 206
Water Collector and Water Level Switch Procedure Illustration 1) Remove the 2 screws of the ventilation ring. (see CJ_MCD1_013) CJ_MCD1_013 2) Remove the 2 screws fixing the water collector. (see CJ_MCD1_014) CJ_MCD1_014 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 207
Procedure Illustration 3) Remove the 5 screws of the water collector subassembly. (see CJ_ MCD1_015) CJ_MCD1_015 4) Turn over the water collector subassembly and remove the water level switch. (see CJ_MCD1_016) CJ_MCD1_016 Note: This section is for reference only. Actual unit appearance may vary. ...
Fan Motor and Fan Procedure Illustration 1) Remove the nut of the fan and then pull up the fan. (see CJ_MCD1_017) CJ_MCD1_017 2) Remove 2 screws of fixing board and 3 nuts of fan motor. (see CJ_ MCD1_018) CJ_MCD1_018 Note: This section is for reference only. Actual unit appearance may vary. ...
Evaporator Procedure Illustration 1) Remove 2 screws of pipe clamp board. (see CJ_MCD1_019) CJ_MCD1_019 2) Remove 4 screws of the evaporator fixing bracket and then remove it. (see CJ_MCD1_020) CJ_MCD1_020 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 210
Indoor Unit Disassembly - DUCT Contents Indoor Unit Disassembly ..................1 Electrical Parts ....................2 Fan Motor and Fan ..................5 Evaporator .....................7...
Page 211
1. Indoor Unit Disassembly Electrical Parts (Antistatic gloves must be worn.) Procedure Illustration 1) Remove 5 screws of the cover of electronic control box and then remove the cover. (see CJ_A6_001) CJ_A6_001 2) Remove 2 screws of the electronic control box. Then release 2 hooks of the main control board.
Page 212
Procedure Illustration 3) Disconnect the connectors and then remove the front main control board. (see CJ_A6_003) 4) Turn over the electronic control box. CJ_A6_003 Disconnect the connectors and remove 2 screws of rear main control board. (see CJ_A6_004) CJ_A6_004 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 213
Procedure Illustration 5) Remove 2 screws of reactor and remove the reactor. (see CJ_A6_005) CJ_A6_005 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 4 ...
Page 214
Fan motor and fan Procedure Illustration 1) Remove 10 screws of the top cover and then remove the top cover. (see CJ_A6_006) CJ_A6_006 2) Release 3 hooks of volute shell. (see CJ_A6_007) CJ_A6_007 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 215
Procedure Illustration 3) Remove the fiing screws of fan (2 screws). (see CJ_A6_008) CJ_A6_008 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 6 ...
Page 216
Evaporator Procedure Illustration 1) Remove 9 Screws of the water collecter and remove the water collecter. (see CJ_A6_009) CJ_A6_009 2) Remove the screws of the pipe clamp board and the left side board (3 for the pipe clamp and 9 for left side board). (see CJ_A6_010) CJ_A6_010 Note: Remove the front panel (refer to 1.
Page 217
Procedure Illustration 3) Remove 2 screws of the evaporator support and then pull up the temperature sensor. (see CJ_A6_011) CJ_A6_011 4) Remove the screw of the evaporator and then remove it. (see CJ_A6_012) CJ_A6_012 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 218
Indoor Unit Disassembly-Console Contents Indoor Unit Disassembly ..................1 Filter ......................2 Display Board ....................4 Panel Frame Subassembly ................5 Upper air outlet frame assembly ..............6 Lower air outlet frame assembly ..............8 Evaporator .....................9 Fan Motor and Fan ..................10 Electrical Parts .....................11...
1. Indoor Unit Disassembly Filter Procedure Illustration 1) Hold the both sides of front panel and open the front panel. (see CJ_ CONSOLE2_001) CJ_CONSOLE2_001 2) Remove the string from the hook. (see CJ_CONSOLE2_002) CJ_CONSOLE2_002 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 220
Procedure Illustration 3) Pull out the filter (see CJ_ CONSOLE2_003) CJ_CONSOLE2_003 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 3 ...
Display Board Note: Remove the front panel (refer to 1.1. filter) before disassembling display board. Procedure Illustration 1) Remove 1 screw and remove the display box subassembly(see CJ_ CONSOLE2_004) CJ_CONSOLE2_004 Display board 2) Pry open the display light box.(see CJ_ CONSOLE2_005) 3) Remove the display board and the humidity sensor module.
Panel Frame Subassembly Note: Remove the front panel (refer to 1.1. filter) before disassembling panel frame subassembly. Procedure Illustration 1) Remove 7 screws and remove the panel frame subassembly(see CJ_ CONSOLE2_006) CJ_CONSOLE2_006 Note: This section is for reference only. Actual unit appearance may vary. ...
Upper Air Outlet Frame Assembly Note: Remove the front panel and panel frame subassembly (refer to 1.1. Filter&1.3 Panel frame subassembly) before disassembling upper air outlet frame assembly. Procedure Illustration 1) Remove 3 screws and remove the upper air outlet frame assembly.(see CJ_CONSOLE2_007) CJ_CONSOLE2_007 2) Remove 2 screws and remove the...
Page 224
Procedure Illustration 3) Take out the positive and negative ion generator upward, and pull out the positive and negative ion emitter(see CJ_CONSOLE2_009)(for some units) CJ_CONSOLE2_009 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 7 ...
Lower Air Outlet Frame Assembly Note: Remove the front panel and panel frame subassembly (refer to 1.1. Filter&1.3 Panel frame subassembly) before disassembling lower air outlet frame assembly. Procedure Illustration 1) Remove 3 screws and remove the lower air outlet frame assembly.(see CJ_CONSOLE2_010) CJ_CONSOLE2_010 2) Remove 2 screws and remove the...
Evaporator Note: Remove the front panel, panel frame subassembly,upper air outlet frame assembly and lower air outlet frame assembly (refer to 1.1,1.3,1.4&1.5 ) before disassembling evaporator. Procedure Illustration 1) Remove 1 screw and remove auxiliary water pan.(see CJ_CONSOLE2_012) Remove one screw used for the ground connection(see CJ_CONSOLE2_012) pull out the coil temperature sensor (T2) (see CJ_CONSOLE2_012)
Fan and Fan Motor Note: Remove the evaporator subassembly (refer to 1.1, 1.3, 1.4, 1.5 and 1.6) before disassembling fan. Procedure Illustration 1) Remove 1 screw and 1 hook,and remove the motor cover(there are two motor cover). (see CJ_CONSOLE2_014) 2) Pull out the fan motor and fan assembly from the side.
Page 228
Electrical Parts (Antistatic gloves must be worn.) Note: Remove the front panel& panel frame subassembly (refer to 1.1&1.3 ) before disassembling electrical parts. Procedure Illustration 1) Remove 1 screw and remove the cover of electronic control box. (see CJ_ CONSOLE2_016) CJ_CONSOLE2_016 2) Pull out the electrical main board.
Page 229
Appendix Contents Temperature Sensor Resistance Value Table for T1, T2, T3, and T4 (°C – K) ..2 Temperature Sensor Resistance Value Table for TP (for some units)(°C --K) ..3 iii) Pressure On Service Port ..................4...
Page 230
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517 11.5 2.19073 0.59386 96.3423 10.9731...
Page 231
ii) Temperature Sensor Resistance Value Table for TP(for some units) (°C --K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm...
Need help?
Do you have a question about the LV6CI-12WiFiR and is the answer not in the manual?
Questions and answers