VIVAX IMPORTANT NOTE Thank you very much for purchasing our product, Before using your unit , please read this manual carefully and keep it for future reference. 1 ...
VIVAX ENG CONTENTS SAFETY CONSIDERATIONS 4 ACCESSORIES 9 Accessories supplied with the unit 9 BEFORE INSTALLATION 9 IMPORTANT INFORMATION FOR THE REFRIGERANT 10 INSTALLATION SITE 11 Selecting a location in cold climates 13 Prevent sunshine 14 INSTALLATION PRECAUTIONS 14 Dimensions 14 Installation requirements 15 Drain hole position 15 Servicing space requirements 16 INSTALLATION THE CONNECTING PIPE 18 Rrfrigerant piping 18 Leakage Detection 19 Heat insulation 19 Connecting method 20 ...
Page 4
VIVAX 8/10/12/14/16 kW 4/6 kW Electric Control System Refrigerant S ystem Please remove the hollow plate after installation. Remove the transportation support 12/14/16 kW 3 ...
VIVAX ENG SAFETY PRECAUTIONS The precautions listed here are divided into the following types.They are quite important, so be sure to follow them carefully. Meanings of DANGER, WARNING, CAUTION and NOTE symbols. INFORMATION Read these instructions carefully before installation. Keep this manual in a handy for future peference. Improper installation of equipment or accessories may result in electric shock, short‐circuit, leakage, fire or other damage to the equipment. Be sure to only use accessories made by the supplier, which are specifically designed for the ...
Page 6
VIVAX CAUTION Indicates a potentially hazardous situation which if not avoided, may result in minor or moderate injury. NOTE Indicates situations that could only result in accidental equipment or property damage. This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an WARNING external ignition source, there is a risk of fire. This symbol shows that the operation manual should be CAUTION read carefully. This symbol shows that a service personnel should be handling this equipment with reference to the installation CAUTION manual. This symbol shows that a service personnel should be CAUTION handling this equipment with reference to the installation manual. This symbol shows that information is available such as the CAUTION operating manual or installation manual. DANGER Before touching electric terminal parts, turn off power switch.
Page 7
VIVAX ENG WARNING Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face danger of death by suffocation. Safely dispose of packing materials such as nails and other metal or wood parts that could cause injuries. Ask your dealer or qualified personnel to perform installation work in accordance with this manual. Do not install the unit yourself. Improper installation could result in water leakage, electric shocks or fire. Be sure to use only specified accessories and parts for installation work. Failure to use specified parts may result in water leakage, electric shocks, fire, or the unit falling from its mount. Install the unit on a foundation that can withstand its weight. Insufficient physical strength may cause the equipment to fall and possible injury. Perform specified installation work with full consideration of strong wind, hurricanes, or earthquakes. Improper installation work may result in accidents due to equipment falling. Make certain that all electrical work is carried out by qualified ersonnel according to the local laws and regulations and this manual using a separate circuit.
Page 8
VIVAX CAUTION Ground the unit. Grounding resistance should be according to local laws and regulations. Do not connect the ground wire to gas or water pipes, lightning conductors or telephone ground wires. Incomplete grounding may cause electric shocks. Gas pipes:Fire or an explosion might occur if the gas leaks. Water pipes:Hard vinyl tubes are not effective grounds. Lightning conductors or telephone ground wires:Electrical threshold may rise abnormally if struck by a lightning bolt. Install the power wire at least 3 feet (1 meter) away from televisions or radios to prevent interference or noise. ...
Page 9
VIVAX ENG CAUTION If the supply cord is damaged, it must be replaced by the manufaturer or its service agent or a similarly qualified person. DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste seperatelly for special treatment is necessary. Do not dispose of electrical appliances as municipal waste, use seperate collection facilities. Contact your local goverment for information regarding the collection systems available. If electrical appliances are disposed of in landfills or dumps, hazardous substance can leak into the groudwater and get into the food chain, damaging your health and well‐being. The wiring must be performed by professional technicians in accordance with national wiring regulation and this circuit diagram. An all‐pole disconnection device which has at least 3mm seperation distance in all pole and a residualcurrent...
VIVAX ACCESSORIES Accessories supplied with the unit Installation Fittings Name Shape Quantity Outdoor unit installation & 1 owners manual (this book) Techinal data manual 1 Water outlet connection 1 pipe assembly Energy label 1 BEFORE INSTALLATION Before installation Be sure to confirm the model name and the serial number of the unit. Handling 9 ...
VIVAX ENG Handle the unit using the sling to the left and the handle to the right. Pull up both sides of the sling at the same time to prevent discinnection of the sling from the unit While handling the unit keep both sides of the sling level. Keep your back straight After mounting the unit,remove the sling from the unit by pulling 1 side of the sling. CAUTION To avoid injury, do not touch the air inlet and aluminum fins of the unit. Do not use the grips in the fan grills to avoid damage. The unit is top heavy! Prevent the unit from falling due to improper inclination during handling. IMPORTANT INFORMATION FOR THE REFRIGERANT Before installation This product has the fluorinated gas, it is forbidden to release to air. Refrigerant type: R32; Volume of GWP: 675. GWP=Global Warming Potential Factory charged refrigerant volume in the unit Model Refrigerant/kg Tonnes CO2 equivalent 4kW 1.50 1.02 6kW 1.50 1.02 8kW 1.65 1.11 10 ...
VIVAX 10kW 1.65 1.11 Factory charged refrigerant volume in the unit Model Refrigerant/kg Tonnes CO2 equivalent 1‐phase 12kW 1.84 1.24 1‐phase 14kW 1.84 1.24 1‐phase 16kW 1.84 1.24 1‐phase 12kW 1.84 1.24 1‐phase 14kW 1.84 1.24 1‐phase 16kW 1.84 1.24 CAUTION Frequency of Refrigerant Leakage Checks Equipment that contains less than 3 kg of fluorinated greenhouse gases or hermetically sealed equipment, which is labelled accordingly and contains less...
Page 13
VIVAX ENG The equipment is not intended for use in a potentially explosive atmosphere. Places where servicing space can be well ensured. Places where the units' piping and wiring lengths come within the allowable ranges. Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe). Places where rain can be avoided as much as possible. Do not install the unit in places often used as a work space. In case of construction work (e.g. grinding etc.) where a lot of dust is created, the unit must be covered. Do not place any object or equipment on top of the unit (top plate) Do not climb, sit or stand on top of the unit. Be sure that sufficient precautions are taken in case of refrigerant leakage according to relevant local laws and regulations. Don’t install the unit near the sea or where there is corrosion gas. When installing the unit in a place exposed to strong wind, pay special attention to the following: Strong winds of 5 m/sec or more blowing against the unit's air outlet causes a short circuit (suction of discharge air), and this may have the following consequences: Deterioration of the operational capacity. Frequent frost acceleration in heating operation. Disruption of operation due to rise of high pressure. Motor burnout. When a strong wind blows continuously on the front of the unit, the fan can start rotating very fast until it breaks. 12 ...
VIVAX In normal condition, refer to the figures below NOTE for installation of the unit If you install the unit on a building wall or obstacle. frame, please install a waterproof plate (field supply) (about 100mm, on the underside of the unit) in Air inlet order to avoid drain water Maintain channel dripping. (See the picture in the right).
VIVAX ENG Prevent Sunshine As the outdoor temperature is measured via the outdoor unit air thermistor, make sure to install the outdoor unit in the shade or a canopy should be constructed to avoild direct sunlight, so that it is not influenced by the sun’s heat, otherwise protection may be possible to the unit. WARNING Uncovered scene, anti‐snow shed must be installed: (1) To prevent rain and snow from ...
VIVAX Installation requirements Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during the operation. In accordance with the foundation drawing in the figure, fix the unit securely by means of foundation bolts. (Prepare four sets each of Φ10 Expansion bolts, nuts and washers which are readily available in the market.) Screw in the foundation bolts until their length is 20 mm from the foundation surface. Φ10 Expansion bolt Rubber shocking proof mat Solid ground or roofing Concrete basement h≥100mm Fig 6‐3 Fig 6‐4 Drain hole position Drain hole Drain hole This drain hole is covered by rubber plug. If the small drain hole can not...
VIVAX ENG Installation space requirements In case of stacked installation 2) In case obstacles exist in front of the 1) In case obstacles exist in front of the air inlet outlet side Fig. 6‐6 A(mm) Unit 4~16kW ≥2000 NOTE It's necessary to install the water outlet connection pipe assembly if the unit is mounted on the top of each other, preventing condensate flow to the heat exchanger. 16 ...
Page 18
VIVAX In case of multiple‐row installation (for roof top use, etc.) 1) In case of installing one unit per row. Fig. 6‐7 Unit A(mm) B1(mm) B2(mm) C(mm) 4~16kW ≥3000 ≥2000 ≥150 ≥600 1) In case of installing multiple units in lateral connection per row. Fig. 6‐8 Unit A(mm) B1(mm) B2(mm) C(mm) 4~16kW ≥3000 ≥2000 ≥300 ≥600 17 ...
VIVAX ENG INSTALL THE CONNECTING PIPE Check whether the differance in height between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements: Refrigerant piping Liquid Fig. 7‐1 CAUTION Please pay attention to avoid the components where it is connecting to the connecting pipes.
VIVAX Leakage Detection Use soap water or leakage detector to check every joint whether leak or not (Refer to Fig.7‐2 ). Note: A is high pressure side stop valve B is low pressure side stop valve C and D is connecting pipes interface of indoor and outdoor units Check point of indoor unit Check point of outdoor unit Fig. 7‐2 Heat Insulation Do the heat insulation to the pipes of gas side and liquid side separately. The temperature of the pipes of gas side and liquid side when cooling, for avoiding ...
VIVAX ENG Connecting method Outdoor unit Fig. 7‐4 Indoor unit Max. Difference in height Fig. 7‐5 CAUTION The largest level difference between indoor unit and outdoor unit should not exceed 20m (if the outdoor unit is above) or 15m (if the outdoor unit is below). Additionally: (i) If the outdoor unit is above and the level difference is greater than 20m, it is recommended that an oil return bend with dimensions as specified in Figure 7‐4 is set every 5m in the gas pipe of the main pipe; and (ii) if the outdoor unit is below and the level difference is more than 15m, the liquid pipe of the main pipe should be increased one size. Size of pipes of Gas side and Liquid s ide MODEL ...
VIVAX Connection method Gas side Liquid side 4‐16 kW outdoor unit Flaring Flaring Indoor unit Flaring Flaring MODELS 4‐16 kW Max.piping length (H+L1) 30m Max difference in height (H) 20m Remove Dirt or Water in the Pipes Make sure there is no any dirt or water before connectiong the piping to the outdoor and indoor units. Wash the pipes with high pressure nitrogen, never use refrigerant of outdoor unit. Airtight Testing Charge pressured nitrogen after connecting indoor/outdoor unit pipes to do airtight testing CAUTION Pressured nitrogen [4.3MPa (44kg/cm ) for R32] should be used in the airtight testing. Tighten high/low pressure valves before charging pressured nitrogen. Charge pressure nitrogen from the connector on the pressure valves. ...
VIVAX ENG Refrigerant Amount to be Added Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit connection. If the length of the liquid side pipe is less than 15 meters it is no need to add more refrigerant, so than calculating the added refrigerant the length of the liquid side pipe must subtract 15 meters ...
VIVAX Precautions on electrical wiring work Fix cables so that cables do not make contact with the pipes (especially on the high pressure side). Secure the electrical wiring with cable ties as shown in figure so that it does not come in contact with the piping, particularly on the high‐pressure side. Make sure no external pressure is applied to the terminal connectors. When installing the ground fault circuit interrupter make sure that it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the ground fault circuit interrupter. : NOTE The ground fault circuit interrupter must be a high‐ speed type breaker of 30 mA ...
Page 25
VIVAX ENG Safety device requirment 1. Select the wire diameters ( minimum value) individually for each unit based on the table 8‐1 and table 8‐2, where the rated current in table 9‐1 means MCA in table 9‐2. In case the MCA exceeds 63A, the wire diameters should be selected according to the national wiring regulation. 2. Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection, where MFA is used to select the current circuit breakers and residual current operation breakers: Nominal cross‐sectional area (mm 2 Rated current of ) appliance:(A) Flexible cords Cable for fixed wiring ≤3 0.5 and 0.75 1 and 2.5 >3 and ≤6 0.75 and 1 1 ...
VIVAX ‐ 14kW 3‐PH 380‐415 50 342 456 11 14 16 10.15 0.17 1.50 ‐ 16kW 3‐PH 380‐415 50 342 456 12 14 16 11.15 0.17 1.50 NOTE MCA : Max. Circuit Amps. (A) TOCA : Total Over‐current Amps. (A) MFA : Max. Fuse Amps. (A) MSC : Max. Fuse Amps. (A) FLA : In nominal cooling or heating test condition,the input Amps of compressor where MAX. Hz can operate Rated Load Amps. (A); KW : Rated Motor Output ...
Page 27
VIVAX ENG Stated values are maximum values (see electrical data for exact values). Outdoor Unit Outdoor Unit Power supply Power supply 3‐phase 1‐phase NOTE The ground fault circuit interrupter must be a high‐speed type breaker of 30 mA (<0.1s). Please use 3‐core shielded wire. To finish the outdoor unit installation A Gas pipe B Gas pipe insulation C Finishing tipe D Liquid pipe E Liquid pipe insulation F Interconnection cable 26 ...
VIVAX OVERVIEW OF THE UNIT Disassembling the unit 4/6 kW 8/10/12/14/16 kW Door 1: To access to the compressor and Door 1: To access to the compressor and electrical parts electrical parts WARNING Switch off all power — i.e. unit power supply and backup heater and domestic hot water tank power supply (if applicable) — before removing doors 1. Parts inside the unit may be hot. Push the grill to the left until it stops, then pull its right edge, so you can removed the grill. You can also reverse the procedure. Be careful to avoid hand injury. 27 ...
VIVAX ENG Electronic control box 12/14/16 kW 1‐phase 28 ...
Page 30
VIVAX 12/14/16kW 3‐phase NOTE The picture is for reference only, please refer to the actual product. 4~16kW 1‐phase units 1) PCB A,4‐10 kW Inverter module 29 ...
Page 31
VIVAX ENG Coding Assembly unit Coding Assembly unit 1 Compressor connection port U 6 Reserved(CN302) Port for communication with PCB 2 Compressor connection port V 7 B(CN32) 3 Compressor connection port W 8 Input port N for rectifier bridge(CN502) 4 Output port for +12V/9V(CN20) 9 Input port L for rectifier bridge(CN501) 5 Port for fan(CN19) / / 2) PCB A, 12‐16 kW Inverter module Coding Assembly unit Coding Assembly unit Port for communication with PCB 1 Compressor connection port U 6 B(CN32) 2 Compressor connection port V ...
Page 32
VIVAX 3) PCB B, 4‐16 kW Main Control Board Coding Assembly unit Coding Assembly unit 1 Output port L to PCB A(CN28) 18 Port for low pressure switch (CN14) Port for communication with hydro‐box 2 Reserved(CN22) 19 control board (CN29) 3 Output port N to PCB A(CN27) 20 Reserved(CN20) 4 Reserved(CN3) 21 Reserved(CN38) 5 Port for ground wire(PE2) 22 Reserved(CN37) 6 Digital display(DSP1) 23 Reserved(CN36) Port for communication with PCB 7 24 Port for communication(reserved,CN30) A(CN17) 8 Port for ground wire(PE1) ...
Page 33
VIVAX ENG 14 Port for sunction temp.sensor(CN1) 31 Port for 4‐way valve(CN6) Port for discharge 15 32 Port for SV6 valve(CN5) temp.sensor(CN8) Port for compressor eletric heating tape 16 Port for pressure sensor(CN4) 33 1(CN7) Port for high pressure switch Port for compressor eletric heating tape 17 34 (CN13) 2(CN18) 12~16kW 1‐phase units 1) PCB A, Inverter module Coding Assembly unit Coding Assembly unit 1 Output port for +15V(CN20)) 8 Power Input port L1(CN16) Compressor connection port 2 9 Input port P_in for IPM module(CN1) ...
Page 34
VIVAX Compressor connection port 4 11 PED board(CN22) U(CN17) 5 Power Input port L3(CN15) 12 Port for high pressure switch (CN23) 6 Power Input port L2(CN7) 13 Port for communication with PCB C(CN2) Input port P_out for IPM 7 module(CN5) PCB B, Main Control Board Coding Assembly unit Coding Assembly unit 1 Port for ground wire(CN38) 16 Port for temp.sensor Tp(CN8) Port for outdoor ambient temp. sensor 2 Port for 2‐way valve 6(CN27) 17 and condenser temp.sensor(CN9) 33 ...
Page 35
VIVAX ENG 3 Port for 2‐way valve 5(CN20) 18 Digital display(DSP1) 4 Port for eletric heating tape2(CN7) 19 DIP switch(S5,S6) 5 Port for eletric heating tape1(CN10) 20 Port for low pressure switch(CN31) Port for high pressure switch and quick 6 Reserved(CN11) 21 check(CN29) 7 Port for 4‐way valve(CN18) 22 Rotary dip switch(S3) Port for temp.sensors(TW_out, TW_in, T1, 8 Reserved(CN21) 23 T2,T2B )(CN35)(Reserved) Power supply port from PCB 9 24 Port for communication XYE(CN28) C(CN41) Port for communication with 10 25 Key for force cool&check(S3,S4) Power Meter(CN26) Port for communication with hydro‐ 11 ...
Page 36
VIVAX PCB C 3‐phase 12/14/16kW, Filter Board Coding Assembly unit Coding Assembly unit Port for communication with PCB B 1 Power supply L2(CN201) 9 (CN8) 2 Power supply L3(CN200) 10 Power filtering L3(L3’) 3 Power supply N(CN203) 11 Power filtering L2(L2’) Power supply port of 4 12 Power filtering L1(L1’) 310VDC(CN212) 35 ...
VIVAX ENG Power supply port for main control 5 Reserved(CN211) 13 board(CN30) 6 Port for FAN Reactor(CN213) 14 Port for ground wire(PE2) Power supply port for Inverter 7 15 Port for ground wire(PE1) module(CN214) 8 Ground wire(PE3) 16 Power supply L1(L1) TEST RUNNING Operate according to "key points for test running" on the electric control box cover. CAUTION Test running can not start until the outdoor unit has been connected to the power for 12 hours. Test running can not start until all the valves are affirmed open. PRECAUTIONS ON REFRIGERANT LEAKAGE When the refrigerant charge in appliance is more than 1.842kg, following requirments should be complied with. Requirments for charge limits in unventilated areas: The maximum refrigerant charge in appliance shall be in accordance with the following: 1/2 = 2.5 x (LFL) x 1.8 x (A) or the required minium floor area Amin to install an appliance with refrigerant charge mc shall be in accordance with following: ...
Page 38
VIVAX ● Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate. Outdoor Unit Indoor Unit Room is filled of leakage refrigerant (All refrigerant has leaked out.) 4/6kW Fig 11‐1 Outdoor Unit Indoor Unit Room is filled of leakage refrigerant (All refrigerant has leaked out.) Fig 11‐2 8/10/12/14/16 kW 37 ...
VIVAX ENG Indoor unit A. Ventilation peristome B. Leak alarm related to mechanical ventilator Leak hunting siren should be installed in places easily keep refrigerant) Fig 11‐3 TURN OVER TO CUSTOMER The owner's manual of indoor unit and owner's manual of outdoor unit must be turned over to the customer. Explain the contents in the owner’s manual to the customers in details. 38 ...
Page 40
VIVAX WARNING Ask your dealer for installation of Do not dispose this the heat pump. Incomplete product as unsorted installation performed by yourself municipal waste. may result in a water leakage, Collection of such waste electric shock, and fire. separately ...
Page 41
VIVAX ENG CAUTION If damaged, the unit may fall and Do not use the heat pump for other result in injury. purposes. To avoid oxygen deficiency, In order to avoid any quality ventilate the room sufficiently if deterioration, do not use the unit for equipment with burner is used cooling precision instruments, food, together with the heat pump. ...
VIVAX ● Strong wind is Continuously or deformation of the unit due to the blowing to the air outlet of the heat. outdoor unit. Do not install the heat pump at any Heating Operation place where flammable gas may leak ● Too much rubbish adhere to the out. filter in the water system If the gas leaks out and stays around ● The air outlet of indoor unit is the heat pump, a fire may break out. ...
VIVAX ENG In some extreme cold upland that buy During operation, the fan motor in the indoor unit equipped with the outdoor unit may stop running electrical heater will obtain better under high temperature. performance.( Refer to indoor unit owner’s manual for details) Defrost in the heating operation During heating operation, outdoor NOTE ...
VIVAX Error codes When a safety device is activated, an error code will be displayed on the user interface. A list of all errors and corrective actions can be found in the table below. Reset the safety by turning the unit OFF and back ON. In case this procedure for resetting the safety is not successful, contact your local dealer. MALFUNCTION OR FAILURE CAUSE ERROR CODE PROTECTION AND CORRECTIVE ACTION Phase loss or neutral 1. Check the power supply cables should be wire and live wire are conneted stable,aviod phase loss. connected 2. Check whether the sequence of neutral wire reversely(only for three and live wire are connected reversely. phase unit). 1. The T3 sensor connector is loosen. Reconnect it. The condenser outlet 2. The T3 sensor connector is wet or there is water refrigerant temperature in. remove the water, make the connector dry. sensor (T3)error. Add waterproof adhesive 3. The T3 sensor failure, change a new sensor. 1. The T4 sensor connector is loosen. Reconnect it. The ambient 2. The T4 sensor connector is wet or there is water ...
Page 45
VIVAX ENG 1. wire doesn’t connect between main control board PCB B and main control board of hydraulic module. connect the wire. Communication fault 2. Communication wire sequence is not right. between indoor unit and Reconnect the wire in the right sequence. outdoor unit 3. Whether there is a high magnetic field or high power interfere, such as lifts, large power transformers, etc.. To add a barrier to protect the unit or to move the unit to the other place. 1. Whether there is power connected to the PCB and driven board. Check the PCB indicator light is on or off. If Light is off, reconnect the power Communication error supply wire. 2. if light is on, check the wire connection between inverter module PCB A and main between the main PCB and driven PCB, if the control board PCB B wire loosen or broken, reconnect the wire or change a new wire. 3. Replace a new main PCB and driven board in turn. The sum of the number of times L0 and L1 Three times P6 protect appear in an hour equals three.See L0 and L1 for fault handling methods ...
Page 46
VIVAX 1. The EEprom parameter is error, rewrite the EEprom data. The main control board 2. EEprom chip part is broken, change a new PCB B EEprom failure EEprom chip part. 3. Main PCB is broken, change a new PCB. H6 displayed 10 times in Refer to H6 2 hours Low pressure protection Pe<0.6) occured 3 Refer to P0 times in an hour 1. System is lack of refrigerant volume. Charge the refrigerant in right volume. 2. When at heating mode or DHW mode, the outdoor heating exchanger is dirty or something is block on the surface. Clean the outdoor heating exchanger or remove the obstruction. ...
Page 47
VIVAX ENG 1. The same reason to P1. Compressor overcurrent 2. Power supply voltage of the unit is low, increase protection the power voltage to the required range 1. The same reason to P1. High discharge 2. TW_out temp.sensor is loosen Reconnect it. temperature protection 3. T1 temp.sensor is loosen. Reconnect it. 4. T5 temp.sensor is loosen. Reconnect it DC fan motor protect Contact your local dealer 1. Heat exchanger cover is not removed. Remove it. High temperature 2. Heat exchanger is dirty or something is block on protection of refrigerant the surface. Clean the heat exchanger or outlet temp of remove the obstruction. condenser 3. There is no enough space around the unit for heat exchanging. ...
Page 48
VIVAX 1. Check the power supply. 2. If the power supply is OK,and check if LED light is OK, check the voltage PN, if it is 380V, the problem usually comes from the main board. And if the light is OFF, disconnect the power, check the IGBT, check those dioxides, if the voltage ...
Page 49
VIVAX ENG MALFUNCTION OR FAILURE CAUSE ERROR CODE PROTECTION AND CORRECTIVE ACTION Module protection DC generatrix low voltage protection DC generatrix high voltage protection 1. Check the Heat pump system pressure; 2. Check the phase resistance of compressor; MCE malfunction 3. Check the U、V、W power line connection sequence between the inventer board and the compressor; Zero speed protection 4. Check the L1、L2、L3 power line connection between the inventer board and the Filter board Speed difference >15Hz ; protection between the front and the back 5. Check the inventer board. clock Speed difference >15Hz ...
VIVAX TECHNICAL SPECIFICATIONS Model (Capacity 4 kW 6 kW 8 kW 10 kW mark) Power supply 220‐240V~ 50Hz Rated power input 2200W 2600W 3300W 3600W Rated current 10.5A 12.0A 14.5A 16.0A Norminal capacity Refer to the technical data Dimensions 1008*712*426 1118*865*523 (W×H×D)[mm] Packing 1065*810*485 1190*970*560 (W×H×D)[mm] Fan motor DC motor / Horizontal Compressor DC inverter dual rotary Heat exchanger Fin‐coil Refrigerant Type R32 ...
Page 51
VIVAX ENG Model (Capacity 12 kW 14 kW 16 kW 12 kW 14 kW 16 kW mark) 3‐phase 3‐phase 3‐phase Power supply 220‐240V~ 50Hz 380‐415V 3N~ 50Hz 5400 5700 Rated power input 6100W 5400W 5700W 6100W W W Rated current 14.5A 25.0A 26.0A 9.0A 10.0A 11.0A Norminal capacity Refer to the technical data Dimensions 1118*865*523 1118*865*523 (W×H×D)[mm] Packing ...
VIVAX INFORMATION SERVICING Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minmised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. Work procedure Works shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed. General work area All mintenance staff and others working in the local area shall be instructed on the nature of work being carried out. work in confined sapces shall be avoided. The area around the work space shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
Page 53
VIVAX ENG Checks to the refrigeration equipment Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: The charge size is in accordance with the room size within which the refrigerant containing parts are installed; The ventilation machinery and outlets are operating adequately and are not obstructed; If an indirect refrigerating circuit is being used, the secondary circuits shall be checked for the presence of refrigerant; marking to the equipment continues to be...
Page 54
VIVAX NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Instrinsically safe components do not have to be isolated prior to working on them. 11) Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinscially safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak. 12) Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. 13) Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. 14) Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect...
Page 55
VIVAX ENG Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no ...
Page 56
VIVAX In case analysis is required prior to re‐use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced. Become familiar with the equipment and its operation. Isolate system electrically Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protetive equipment is available and being used correctly; The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders conform to the appropriate standards. Pump down refrigerant system, if possible. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. Make sure that cylinder is situated on the scales before recovery takes place. Start the recovery machine and operate in accordance with manufacturer s instructions. Do not overfill cylinders. (No more than 80% volume liquid charge). Do not exceed the maximum working pressure of the cylinder, even temporarily. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. Labelling Equipment shall be labelled stating that it has been de‐commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery When removing refrigerant from a system, either for service or decommissioning, it is recommended good practice that all refrigerants are removed safely. When tranferring refrigerant into cylinders, ensure that only appropriate ...
Page 57
VIVAX ENG The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak‐free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to retruning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely. Transportation, marking and storage for units Transport of equipment containing flammable refrigerants Compliance with the transport regulations Marking of equipment using signs Compliance with local regulations Disposal of equipment using flammable refrigerants Compliance with national regulations Storage of equipment/appliances The storage of equipment should be in accordance with the manufacturer’s instructions. Storage of packed (unsold) equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations. 56 ...
Page 61
VIVAX ENG The automatic setting curve The automatic setting curve is the ninth curve,this is the calculation: State:In the setting the wired controller, if T4H2<T4H1, then exchange their value; if T1SETH1<T1SETH2, then exchange their value. Table3 The environment temperature curve of the low temperature setting for cooling T4 ‐10 ≤ T4 <15 15 ≤ T4 <22 22 ≤ T4 <30 30 ≤ T4 <46 1 ‐ T1S 18 11 8 5 T4 ‐10 ≤ T4 <15 15 ≤ T4 <22 22 ≤ T4 <30 30 ≤ T4 <46 2 ‐ T1S 17 12 9 6 T4 ...
Page 65
VIVAX ENG CONTENTS GENERAL SAFETY PRECAUTIONS 3 About the documentation 3 For the user 3 A GLANCE OF THE USER INTERFACE 4 The appearance of the wired controller 4 Status icons 4 USING HOME PAGES 5 MAIN STRUCTURE 8 About the menu structure 8 To go to the menu structure 8 To navigate in the menu structure 8 BASIC USAGE 8 Screen Unlock 9 Turning ON/OFF controls 9 Adjusting the temperature 12 Adjusting space operation mode 12 OPERATION 13 Operation Mode 13 Preset Temperature ...
VIVAX GENERAL SAFETY PRECAUTIONS About the documentation. DANGER WARNING Indicates a situation that results in Indicates a situation that could result death or serious injury. in death or serious injury. DANGER DANGER: RISK OF ELECTROCUTION RISK OF BURNING Indicates a situation that results in Indicates a situation that could result ...
VIVAX ENG A GLANCE OF THE USER INTERFACE The appearance of the wired controller Turn on or off the Enter the menu space operation structure from mode or DHW the home page mode turn on or off the function in the menu structure Navigate cursor on the display/navigate in the menu ...
Page 68
VIVAX USING HOME PAGES When you turn on the wired controller, the system will enter the language selection page, You can choose your preferred language, then press OK to enter the home pages. If you don't press OK in 60 seconds, the system will enter in the currently selected language. You can use the home pages to read out and change settings that are meant for daily usage. What you can see and do on the home pages is described where applicable. Depending on the system layout, the following home pages may be possible: Room desired temperature (ROOM ) Water flow desired temperature (MAIN) DHW tank actual temperature (TANK) DHW=domestic hot water.
Page 69
VIVAX ENG Home Page 2 If the WATER FLOW TEMP. is set NON and ROOM TEMP. is set YES (See ''FOR SERVICEMAN'' > ''TEMP. TYPE SETTING'' on ''Installation and owner's manual (M‐ thermal split indoor unit)''). The system has the function including floor heating and domestic hot water, home page 2 will appear: The System layout 2 Room desired temperature NOTE The wired controller should be installed in the floor heating room to check the room temperature. Home Page 3 ...
Page 70
VIVAX Home Page 4 If the ROOM THERMOSTAT is set DOUBLE ZONE or DOUBLE ZONE is set YES. There will be main page and addition page. The system has the function including floor cooling, space cooling for fan coil and domestic hot water, home page 4 will appear: Main page The System layout 4 RT= Room thermostat Zone 1 water flow DHW tank real temp. desired temperature Additional page ...
VIVAX ENG MENU STRUCTURE About the menu structure You can use the menu structure to read out and configure settings that are NOT meant for daily usage. What you can see and do in the menu structure is described where applicable. For an overview of the menu structure, see " 7 Menu structure: Overview" To go to the menu structure From a home page, press ''MENU''. Result: The menu structure appear To go to the menu structure Use''▼''、 ''▲'' to scroll. BASIC USAGE Screen Unlock If the icon ...
VIVAX The interface will be locked if there is no handing for a long time(about 120 seconds:it can be set by the interface, see ''SERVICE INFORMATION''.) If the inerface is unlocked, long press "unlock", the interface will be locked. Turning ON/OFF controls Use the interface to turn on or off the unit for space heating or cooling. The ON/OFF of the unit can be controlled by the interface if the ROOM THERMOSTAT is NON. (see ''ROOM THERMOSTAT SETTING'' in ''Installation and owner's manual (M‐...
Page 73
VIVAX ENG Use the room thermostat to turn on or off the unit for space heating or cooling. ① The room thermostat is not SET NON (see ''ROOM THERMOSTAT SETTING'' in ''Installation and owner's manual (M‐ thermal split indoor unit)''). The unit for space heating or cooling is turned on or off by the room thermostat,...
Page 74
VIVAX If the space operation mode is OFF, then following pages will display: Use the interface to turn on or off the unit for DHW. Press ''►''、''▼''on home page, the black cursor will appear: ...
VIVAX ENG Adjusting the temperature Press ''◄ ''、 ''▲'' on home page, the black cursor will appear: If the cursor is on the temperature, use the ''◄''、 ''►'' to select and use ''▼''、 ''▲'' to adjust the temperature.: Adjusting space operation mode Adjusting space operation mode by interface Go to ''MENU'' > ''OPERATION MODE'' . ...
VIVAX OPERATION Operation Mode See "Adjusting space operation mode": Preset Temperature The operation mode can not be changed PRESET TEMPERATUER has PRESET TEMP.\ WEATHER TEMP. SET\ECO MODE 3 items. Select Then the space operation mode is… PRESET TEMP . PRESET TEMP. function is used to set Always heating mode different temperature on different time when the heat mode or cool mode is on. Always cooling mode PRESET TEMP. = PRESET TEMPERATRE The PRESET TEMP. function will be off in Automatically changed by the software these conditions. ...
Page 77
VIVAX ENG For example: Now time is 8:00 and temperature is 30°C. We set the PRESET TEMP as following table. The following page will appear: When double zone is activated,The PRESET TEMP. function only works for zone 1. use ''◄''、''► ''、 ''▼''、 ''▲'' to scroll and use ''▼''、 ''▲'' to adjust the time and the temperature. When the cursor is on ''■'', as the following page: INFORMATION When the space operation mode is changed, the PRESET TEMP. is off automatically. You press ''OK'', and the ''■'' becomes '' ''. The PRESET TEMP. function can be The timer 1 is selected. used in the heat mode or cool You press ''OK'' again, and the '' ...
Page 78
VIVAX Water Temperature Set It only have the curve of the low WEATHER TEMP. SET = WEATHER temperature setting for cooling, if the TEMPERATURE SET low temperature is set for cooling. WEATHER TEMP.SET function is used to See ''FOR SERVICEMAN''> ''COOL preset the desired water flow temperature ...
Page 79
VIVAX ENG If the weather TEMP.SET is actived,the Press ''ON/OFF''. The following page will desired temperature can not be adjusted on appear: the interface.Press the ''▼'' , ''▲'' to adjust the temperature on home page. The following page will appear: Use '◄ '', ''►''to scroll. Press ''OK'' to select. The following page will appear: Move to “NO”,press “OK” to come back to home page,move to “YES”, press “OK” to ...
VIVAX INFORMATION ECO MODE SET have two kinds of curves: 1. the curve of the high temperature setting for heating, 2. the curve of the low temperature setting for heating, It only have the curve of the high temperature setting for heating, if the high temperature is set for heating. See ''FOR SERVICEMAN''>''HEAT MODE SETTING'' in "Installation and owner's manual (M‐thermal split indoor unit)".
Page 81
VIVAX ENG Fast DHW Also, even if the heat pump system fails, TANK HEATER can be used to heat water in The FAST DHW function is used to force the tank. system to operate in DHW mode. Go to ''MENU'' > ''DOMESTIC HOT WATER'' The heat pump and the booster heater or > ''TANK''. addition heater will operate for DHW mode together, ...
VIVAX DHW Pump Set as follows: The DHW PUMP function is used to return water of the water net. Go to ''MENU'' > ''DOMESTIC HOT WATER'' > ''DHW PUMP''. Press ''OK''. The following page will appear: The PUMP will run as follows: SCHEDULE SCHEDULE menu contents as follows: The following page will appear: 1) TIMER 2) WEEKLY SCHEDULE 3) SCHEDULE CHECK 4) CANCEL TIMER Move to “■”, press ''OK'' to select or unselect.
VIVAX ENG The operation of the controller at the following time: The operatin of the TIME controller 1:00 DHW mode is turned ON 3:00 DHW mode is turned OFF 7:00 HEAT MODE is turned ON 9:00 HEAT MODE is turned OFF 11:30 COOL MODE is turned ON Use ''◄'', ''►'', ''▼'', ''▲'' to scroll and use 13:00 COOL MODE is turned OFF ''▼'', ''▲'' to adjust the temperature. 14:00 HEAT MODE is turned ON Move to “■”, press ''OK'' to select or unselect.
Page 84
VIVAX Schedule check INFORMATION Schedule check can only check the weekly We must set two days at least when we schedule. want to enable WEEKLY SCHEDULE Go to ''MENU'' > ''SCHEDULE'' >''SCHEDULE' function. CHECK''. Press ''OK''. The following page will appear Use ''◄'' or ''►'' to SET, press "ENTER". The Monday to Friday are selected to be scheduled and they have the same schedule. ...
VIVAX ENG INFORMATION TIMER and WEEKLY SCHEDULE are on the same priority. The later setting function is valid. The PRESET TEMP. becomes invalid when TIMER or WEEKLY SCHEDULE is valid. The WEATHER TEMP. SET is not affected by the setting of TIMER or WEEKLY SCHEDULE. If TIMER or WEEKLY SCHEDULE is canceled, ...
Page 86
VIVAX Go to the home page to check if silent mode If the silent TIMER is selected, Press “OK” to is activated. If the silent mode is activated,'' enter, the following page will appear. '' will display on the home page. Go to ''MENU'' > ''OPTIONS'' > ''SILENT MODE''. Press ''OK'' . The following page will appear: There are two timers for setting. Move to “■”, press '' OK '' to select or unselect. If the two time are both unselected,the silent mode will operate in all time.
Page 87
VIVAX ENG INFORMATION Usage example: You go away during the winter. Disinfecting the unit on 23:00 of the last day The current date is 2018‐01‐31, two days if disinfect is ON. later is 2018‐02‐02, it is the beginning date When in holiday away mode, the climate of the holiday. related curves previously set is invalid, and If you are in the following situation: the curves will automatically take effect after the holiday away mode is ends. In 2 days, you go away for 2 weeks during The preset temperature is invalid when in ...
VIVAX Use ''ON/OFF'' to select ''OFF'' or ''ON''. Use ''ON/OFF'' to select ''OFF'' or ''ON'' and use ''◄ '', ''► '', ''▼'', ''▲'' to scroll and adjust. INFORMATION If the CURRENT STATE is OFF, the HOLIDAY If the operation mode is auto mode in space HOME is OFF. heating or cooling side, the buckup heater If the CURRENT STATE is ON, the HOLIDAY function can not be selected. HOME is ON. The BACKUP HEATER function is invalid ...
VIVAX ENG The Cool/Heat mode can't turn ON or OFF SERVICE INFORMATION when the COOL/HEAT MODE ON/OFF is locked. If you want to turn on or off the Cool/Heat mode when COOL/HEAT MODE ON/OFF is About service information locked, the following page will appear: Service information menu contents as following: 1) SERVICE CALL 2) ERROR CODE 3) PARAMETER 4) DISPLAY How to go to service information menu ...
VIVAX Press OK the page will appear: The DISPLAY function is used to set the interface: Press OK to show the mean of the error code: Use ''OK'' to enter and use ''◄ '', ''► '', ''▼ INFORMATION '', ''▲'' to scroll. A total of eight fault codes can be recorded. The parameter function is used to display the Operation Parameter main parameter, there are two pages to show the parameter: This menu is for installer or service engineer reviewing the operation parameter. At home page, go to ''MENU'' > ...
VIVAX ENG INFORMATION The power consumption parameter is optional. if some parameter not be activated in the system, the parameter will show "‐‐" The heat pump capacity is for reference only, not used to judge the ability of the unit. The accuracy of sensor is ±1℃. The ...
VIVAX Activate the WLAN by interface. How To Exit For SERVICEMAN Go to "MENU"> "WLAN SETTING"> "AP If you have set all the parameter. MODE". Press ''BACK'', the following page will appear: Press "OK", the following page will appear: Select ''YES'' and press ''OK'' to exit the FOR Use ''◄'',''►'' to move to "YES", press SERVICEMAN. "OK" to select AP mode. After exiting the FOR SERVICEMAN, the unit Select ...
Page 93
VIVAX ENG Mobile Device Setting Add Home Appliances: AP Mode is available for wireless distribution 1. Choose the wired controller model, then on mobile device side. go to add the device. AP Mode connecting WLAN: Install APP 1. Scan the following QR code to install the Smart Home APP. 2. Operate the wired controller according to APP prompts 1. Please research "Msmartlife" in APP STORE or GOOGLE PLAY to install the APP. Sign in/Sign up Click the "+" button on the right side of the home page , register account according to the...
Page 94
VIVAX 4. After the appliance is successfully connected, the LCD icon“ ” of the wired controller is constantly On, and the air conditioner can be controlled through the APP. 5. If the network distribution process fails, or the mobile connection demands reconnection and replacement, operate “WLAN Factory Reset” on the wired controller, ...
Page 97
VIVAX ENG Table 1: The environment temperature curve of the low temperature setting for heating Table 2: The environment temperature curve of the high temperature setting for heating 34 ...
Page 98
VIVAX The automatic setting curve The automatic setting curve is the ninth curve,this is the calculation: State:In the setting the wired controller, if T4H2<T4H1, then exchange their value; if T1SETH1<T1SETH2, then exchange their value. Table 3: The environment temperature curve of the low temperature setting for cooling ...
Page 99
VIVAX ENG Table 4: The environment temperature curve of the high temperature setting for cooling The automatic setting curve The automatic setting curve is the ninth curve,this is the calculation State: In the setting the wired controller, if T4C2<T4C1, then exchange their value; if T1SETC1<T1SETC2, then exchange their value. 36 ...
VIVAX DISPOSAL OF ELECTRICAL AND ELECTRONIC EQUIPMENT To protect our environment and to recycle the raw materials used as completely as possible, the consumer is asked to return unserviceable equipment to the public collection system for electrical and electronic. The symbol of the crossed indicates that this product must be returned to the collection point for electronic waste to feed it by recycling the best possible raw ...
Jamstvo vrijedi ako su montaža ili servis VIVAX klima uređaja obavljeni od strane ovlaštenog servisa kojeg je ovlastio zastupnik M SAN Grupa d.o.o. VIVAX klima uređaj kao cjelinu čine jedna ili više unutarnjih jedinica, instalacija i vanjska jedinica koje su pravilno odabrani i koji si međusobno odgovaraju po modelu i snazi. U slučaju kvara na proizvodu koji je predmet ovog jamstva, obvezujemo se da ćemo isti popraviti u najkraćem ...
Page 103
Naziv tvrtke davatelja jamstva: M SAN GRUPA d.o.o., Buzinski prilaz 10,10010 Zagreb‐Buzin, tei: 01/3654‐961 CENTRALNI SERVIS: MR servis d.o.o, Dugoselska cesta 5,10370 Rugvlca Tel: +385 1 640 1111 Fax: +385 1 365 4982 E‐mail za opće upite: info@mrservis.hr, E‐mail za prodajne upite: prodaja@mrservis.hr, Web: www.mrservis.hr DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA Ugradnja DATUM UGRADNJE OVLAŠTENI SERVIS I POTPIS Servisni periodični pregled i održavanje: Servisni pregled 1 Ovlašteni servis: Datum: Vrijedi do: Servisni pregled 2 Ovlašteni servis: Datum: Vrijedi do: Servisni pregled 3 Ovlašteni servis: Datum: Vrijedi do: Servisni pregled 4* Ovlašteni servis: Datum: Vrijedi do: * Servisni pregled 4 vrijedi samo za modele s osnovnim jamstvom od 12 mjeseci ...
Page 104
POPIS SERVISNIH MJESTA Grad Servis Adresa Telefon Bjelovar Koda d.o.o. Vladimira Nazora 14 043/225 245 Bjelovar Begić d.o.o. Male Sredice 47 b 095/903‐0860 Buje‐Oprtalj Elektro servis Šorgo Šorgi 6 091/424‐2958 Cavtat Šturica‐obrt za Gornji Obod 31 098/345‐026 Cerna Elektroinst, i klimatizacija Sabo Josipa Kozarca 70 097/704‐6424 Čavle‐Rijeka Termo servis Čargonja d.o.o. Buzdohanj 36 098/366‐499 Čavle‐Rijeka Optimare d.o.o. Zastenice 52 095/2222‐312 Čazma Vl. Tihomir Vreš Serv. Kuć. ap. ČA F.Vidović 35 043/771‐924 Daruvar Stilios d.o.o. Trg dr.Franje Tuđmana 3 099/3719‐084 ...
Page 106
Vinkovci Obrt Corect vl.Davor Turalija Ante Starčevića 54 098/358‐458 Virovitica Fruk d.o.o. Strossmayerova 9 098/403‐631 Viškovo‐Rijeka Kjukar d.o.o. Gornji Sroki 141 098/327‐146 Vukovar Servis Jagetić , Elektromeh. obrt Radnička 63 091/560‐0474 Zadar I‐Klima Domovinskog rata 8 091/508‐0960 Zadar Arija‐Nova d.o.o. Ulica braće Miroslava i Janka 023/316‐060 Zadar T.O. Optima Kneza Novaka Krbavskog 42 023/241‐801 Zadar Štefančić‐inst. Klima uređ i centr. Splitska 42 a 097/679‐0769 Zadar Montis trg. instalaterski obrt Put Vukića 1 023/384‐138 Zadar Vedran Company d.o.o. Nikole Tesle 18 095/123‐0000 Zadvarje ...
Page 107
POŠTOVANI! Zahvaljujemo Vam na kupovini Vivax proizvoda i nadamo se da ćete biti zadovoljni izborom. MOLIMO VAS DA PRE UPOTREBE PROIZVODA PAŽLJIVO PROČITATE TEHNIČKU DOKUMENTACIJU I DA SE PRILIKOM UPOTREBE PRIDRŽAVATE PRILOŽENIH UPUTSTAVA GARANTNI LIST 24+36=60 MESECI OSNOVNI PODACI O PROIZVODU (Popunjava trgovac) MODEL UREĐAJA SERIJSKI BROJ DATUM PRODAJE BROJ RAČUNA / FISKALNOG ISEČKA POTPIS I PEČAT TRGOVCA U skladu sa članom 49 Zakona o zaštiti potrošača roba je saobrazna ako: • odgovara opisu koji je dao prodavac i ako ima svojstva robe koju je prodavac pokazao potrošaču kao uzorak ili model, • ima svojstva potrebna za naročitu upotrebu za koju je potrošač nabavlja, a koja je bila poznata prodavcu ili mu je morala biti poznata u vreme zaključenja ugovora, • ako ima svojstva potrebna za redovnu upotrebu robe iste vrste, • po kvalitetu i funkcionisanju odgovara onome što je uobičajeno kod robe iste vrste i što potrošač može osnovano da očekuje s obzirom na prirodu robe i javna obećanja o posebnim svojstvima robe data od strane prodavca, proizvođača ili njihovih predstavnika, naročito ako je obećanje učinjeno putem oglasa ili na ambalaži robe. ...
Page 108
Da je klima uređaj montiran u kućnim i kancelarijskim uslovima po uputstvu i predviđenim standardima od strane ovlašćenog servisa VIVAX klima uređaja; Da se klima uređaj koristi u skladu sa korisničkim uputstvom; Da se vrši redovan godišnji servis klima uređaja na kraju druge, treće i četvrte godine od datuma kupovine klima uređaja. Redovan servis mora obaviti ovlašćeni serviser za VIVAX klima uređaje. Troškove redovnog godišnjeg servisa snosi korisnik uređaja. Potrošač je u obavezi da instalaciju/ servis poveri isključivo ovlašćenom serviseru za VIVAX klima uređaje, kao i da ne ošteti kontrolnu nalepnicu. Petogodišnja garancija nije prenosiva na druge VIVAX proizvode, već se odnosi isključivo na registrovane (prijavljene) klima uređaje. Garantni rok počinje istekom roka saobraznosti od 2 godine u skladu sa Zakonom o zaštiti potrošača i traje 36 meseci pod gore navedenim uslovima. POSTUPAK OSTVARIVANJA PRAVA IZ GARANCIJE Prava iz garancije ostvarujete kontaktiranjem ovlašćenog servisa za Vivax klima uređaje i prilaganjem overenog i popunjenog garantnog lista, dokaza o kupovini, dokaza o ugradnji klima uređaja od strane ovlašćenog servisa kao i dokaza o obavljenom redovnom servisu klime na kraju druge, treće i četvrte godine. Kupac gubi pravo na garanciju: ako se kvar izazove nepridržavanjem datih uputstava za upotrebu, ako su kvarovi na proizvodu nastali kao posledica neodržavanja uređaja ili usled mehaničkog oštećenja ako su na proizvodu vršene bilo kakve popravke od strane neovlašćenih lica, ako instalacija nije urađena u skladu sa propisanim tehničkim uslovima, ako je korisnik nestručno, neadekvatno koristi i nemarno se ophodi prema klima uređaju, ako je proizvod pretrpeo strujni udar ili udar groma, ako nije ispunjen bilo koji od gore navedenih USLOVA GARANCIJE ...
Page 109
VAŽNE NAPOMENE Pre uključivanja aparata pročitajte uputstvo koje je priloženo uz svaki aparat. Pre nego što se obratite za tehničku pomoć nekom od naših ovlašćenih servisa, molimo Vas da proverite da li su obezbeđeni svi potrebni uslovi za normalan rad aparata. U slučaju opravke, garantni rok će se produžiti onoliko koliko je kupac bio lišen upotrebe stvari. Sve popravke aparata obavljaju se isključivo u ovlašćenim servisima. Spisak se nalazi na kraju ovog dokumenta DATUM PRIJEMA UREĐAJA NA SERVIS DATUM POPRAVKE DATUM PRIJEMA UREĐAJA NA SERVIS DATUM POPRAVKE DATUM PRIJEMA UREĐAJA NA SERVIS DATUM POPRAVKA Ugradnja DATUM UGRADNJE OVLAŠĆENI SERVIS I POTPIS Servisni periodični pregled i održavanje: Servisni pregled 1 Ovlašćeni servis: Datum: Vrijedi do: Servisni pregled 2 Ovlašćeni servis: ...
Page 110
POPIS SERVISNIH MESTA Centralni servis: KIM‐TEC d.o.o., Viline vode bb, Slob. zona Bg, Beograd Tel: 011/33 13 568 E‐mail: servis@kimtec.rs Mesto Servis Adresa Telefon Ada ELEKTROSERVIS UNIEL Branka Radičevića 51/C 063/547‐939 037/751‐338 Aleksandrovac AZA KOM 29 Novenbar 17 063/692‐082 018/805‐577 Aleksinac SKY Knjaza Miloša 86/4 063/402‐936 Alibunar MONT EL ALIBUNAR Žarka Zrenjanina 6/4 063/325‐838 Apatin KRNJAIĆ TIM Lađarska 87 064/2382‐817 034/701‐235 Aranđelovac MB ELECTRONIC Kralja Petra I bb 062/701‐235 Aranđelovac MIRKO ANIČIĆ PR PEGAS Orašački put 291 065/2003‐180 034/6712‐902 Aranđelovac ...
Page 111
021/872‐858 Beočin SOFTEL Dositeja Obradovića 15 063/527‐174 011/2578‐281 Beograd ACRO KLIMA d.o.o. Lole Ribara 2 061/1607‐416 Beograd ACS SHOP SERVICE Zrenjaninski put 5 011/2717‐181 011/8035‐096 Beograd AS FRIGO Nikole Tesle 11, Leštane 064/1170‐432 011/7179‐046 Beograd ASTRA FRIGO Gandijeva 60/55 063/283 290 011/2169‐304 Beograd BUILCON TIM Marka Čelebonovića 48 063/8060‐587 Bulevar kralja Aleksandra488a Beograd BULEVAR 063/835‐125 lokal30 060/7517‐707 Beograd COOL4YOU Marka Cara 16 064/0307‐006 Beograd COOL SHOP ...
Page 112
Beograd TERMOCOOL Ljubomira Milića 10,1 sprat 063/622‐151 Beograd VELEMAJSTOR Bul.Kralja aleksandra 064/1110‐046 Beograd Z.R.ALSTEDO Put za Ovču 20g 011/3329‐719 ELEKTROSERVIS 015/7413‐501 Bogatić Pavla Orlovića 105a SRDANOVIĆ 060/7413‐501 015/7786‐434 Bogatić ENERGY SZTKR Mike Vitomirovića 14 060/558‐67‐44; 064/258‐67‐44 030/427‐031 Bor ELEKTRON SC Treći Oktobar 39b 061/7154‐178 030/423‐360 Bor SERVIS TERZIĆ DEJAN Njegoševa 46 063‐11 79 031 PR ZANATSKA RADNJA Borča Put za Ovču 20/G 063‐773‐9041 ALSTEDO 025/731‐167 Crvenka ...
Page 113
0230/402‐740 Kikinda BUS COMPUTERS DOO Nemanjina 36 062/224‐432 Kikinda FRIGO TERMO MAX Оslobođenja 9 060/5507‐055 Kikinda XEON DOO KIKINDA Svetosavska 68 065/2437‐935 019/807‐104 Kladovo ELEKTRO LUKS Ritska 18 062/406‐156 Knjaževac AB KLIMAELEKTRO Knjaza Miloša 92 019/736‐336 Knjaževac SZR ,,GAGISERVIS'' Trgovište bb 063‐8089‐332 Kovin DR FRIGO Cara Lazara 87 063/8315‐625 013/745‐207 Kovin Termofrigo Ive Lole Ribara 4 065/8332‐176 034/314‐400 Kragujevac FOKUS Ljubiše Bogdanovića 14 065/3144‐004 Kragujevac ...
Page 114
HOME CENTAR VERA Leskovac Stanoja Glavaša 9 016/3441‐144 D.O.O. Leskovac KATALOG DOO Stepe Stepanovića 3 016/213‐312 016/250‐778 Leskovac SERVIS EL Cara Lazara 27/17 064/1749‐509 015/892‐002 Loznica PLEROMA PLUS Vladislava Bronjevskog 13 065/6787‐678 015/873‐692 Loznica S.Z.R. UNIVERZAL Vojvode putnika 7 9521 064/8568‐ 206 Loznica SERVIS MARJANOVIĆ SZTR Vojvode Putnika 11 015/877‐865 ‐ 032/819‐298 Lučani TOP WOOD Jugoslovenske armije 2 065/3607‐790 Ljig CENTAR SERVIS Kolubarska 1 014/3443‐953 Mačvanska DRAGAN ZABLACANSKI PR Brace Andonovic 18 ...
Page 115
FRIGO‐MILAN SZR MILAN Novi sad Ljubena Karavelova 17 064/1143‐903 LUŽAIĆ PR 021/6398‐350 Novi sad MISTER COOL Pavleka Miškina 31 063/344‐667 021/453‐869 Novi sad PROSPERO d.o.o. Narodnog fronta 30 063/512‐671 021/503‐218 Novi sad SILER Stanoja Glavaša 114 066/333‐109 011/7872‐228 Obrenovac FRIGO NIDŽA Kralja Petra I 15 064/3675‐742 Obrenovac MICROHARD Miloša Obrenovića 140 063/308‐114 Obrenovac ŠAINOVIĆ I SINOVI Belopoljska 1 011/8725‐799 Odžaci BAGZI TIM Јurija Gagarina 24 069/2644‐787 Odžaci ŠPAKI ELEKTRO Hajduk Veljka 13 063/8122‐890 ...
Page 116
Ratkovo FRIGO MIKOVIĆ Ratka Pavlovića 37 063/8418‐229 Ruma COOL WATT Vrdnicka 78 060/5005‐200 RADOVAN STOJADINOVIĆ Ruma PR ZANATSKA RADNJA SBT Vladimira Nazora 4 060/4713‐120 RAŠA 022/471‐584 Ruma T.C.SISTEM Prvomjska 46 064/9842‐064 Sefkerin FRIGOMANEX Jna 47 066/5511‐536 OMEGA ELEKTRO SERVIS I 024/815‐565 Senta Madrač Imrea9/A PREVOZNIK 064/0812‐720 Smederevo ANTARTIK Partizanska 75 062/362‐481 Smederevo ELEKTRO DIPOL Oslobođenja 66 064/3676‐765 Smederevo FRIGOSISITEM‐SD Crvene armije 55 064/1205‐661 ...
Page 117
Ruzmarina 2 ; PJ Frankopanska 024/523‐764 Subotica WM servis 36 063/519‐505 Surdulica PTMR COLESOFT Srpskih Vladara 51 064‐6339‐915 015/304‐445 Šabac AXEL SERVICE d.o.o. Vladike Joanikija Neškovića 4 063/326‐303 015/319‐530 Šabac CENTRAL SERVICE d.o.o. Prote Smiljanića 52 063/346‐222 015/304‐246 Šabac HARMONIKA Marička 23 063/362‐218 SERVIS I TRGOVINA Šabac Prote Smiljanica 2 064/4088‐015 MIJAILOVIC Šabac ZTR OBRADOVIĆ Kralja Milana 47a 015/344‐997 022/731‐634 Šid FRIGOMONT Vojvođanska 104 c 063/8186‐751 Solunskih dobrovoljaca 62, 022/718‐230 ...
Page 118
Zabrđe kod FREON Zabrđe BB 063/388‐750 petrovca 019/463‐047 Zaječar MILENKOVIĆ SERVIS OBOD 2 Kursulina 20 063‐485‐875 063/8468‐504 Zaječar SZR KLIMA ZAJEČAR Nikole Pašića 224 063/8141‐396 023/530‐877 Zrenjanin ART COOL Ivana Aćina 35 063/7763‐259 Zrenjanin KLEM S.Mokranjca12 060/0525‐901 Zrenjanin KLIMA CENTAR Valjevska 25 060‐5114‐949 RADIVOJ GAGIĆ PR SERVIS Zrenjanin Rade Trnića 31 064/2674‐400 GAGIĆ ZDRAVKO PETROVIĆ PR Zrenjanin Bačka 130 063/515‐562 SERVIS BELE TEHNIKE DEJAN ŠARIN PR D&S Žabalj Petra Kočića ...
Page 119
ACP‐xxxxCFxxxxx, ACP‐xxxxFSxxxxx za koje se garancija može produljivati četiri puta, što u ukupnom trajanju može iznositi maksimalno 60 mjeseci 5. Garantni servisni pregled naplaćuje ovlašteni servis po cjenovniku zastupnika KimTec d.o.o. i/ili Kim Tec servis d.o.o. i ovjerava garantni list što dokazuje produženje i valjanost garancije 6. Garancija vrijedi ako su montaža ili servis Vivax cool klima uređaja obavljeni od strane ovlaštenog servisa kojeg je ovlastio zastupnik Kimtec d.o.o.. 7. Vivax cool klima uređaj kao cjelinu čine unutarnja jedinica, instalacija i vanjska jedinica koji su pravilno odabrani i koji međusobno odgovaraju po modelu i snazi. 8. U slučaju kvara na Vivax cool klima uređaju obvezujemo se da ćemo isti popraviti u najkraćem mogućem roku, a najkasnije u roku 45 dana, ako se Vivax cool klima uređaj ne može popraviti ili se ne popravi u roku od 45 dana, biće zamijenjen novim. Ako popravak Vivax cool klima uređaja traje duže od 10 dana, garancija će sa produžiti za vrijeme trajanja popravka. 9. Garancija se priznaje samo uz račun o kupovini, te uz ovaj garantni list koji mora bili ispravno popunjen i ovjeren od strane prodavca, ovlaštenog montažera ili servisera. 10. Davaoc garancije osigurava servis i rezervne dijelova 7 godina od datuma kupnje Vivax cool klima uređaj ...
Page 120
Kim Tec d.o.o., Poslovni centar 96‐2, 72250 Vitez, Naziv firme davatelja garancije: Tel: 030 718 800, FAX: 033 755 897, e‐mail: vivax@kimtec.ba DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA Ugradnja DATUM UGRADNJE OVLAŠTENI SERVIS I POTPIS ...
Page 121
POPIS SERVISNIH MJESTA Grad Servis Adresa Telefon Vitez Kim Tec‐Servis d.o.o. Poslovni centar 96‐2 030718844 Servis rashladne op. i bijele 119 Muslimanske brdske Banovići 061 287 708 teh. Klimatronic brigade 051 280 500, Banja Luka Servis Preradović Oplenačka br.2. 051 280 505, Banja Luka MCT Elektronik d.o.o. Obilićeva 4 Trn 051 508 080 065 523 658, Banja Luka Sloboda SOD Milice Stojadinović S.6 051 438 908 Banja Luka Kod Ivice szr rtv servis Voždovačka 7 051‐301‐449 Banja Luka East Code d.o.o. Bulevar Desanke M. 10 051 435 595 Banja Luka Frigomatik d.o.o. Petra Preradovića 13 051 315 950 ...
Page 122
Derventa Audio Video Cen. Danijel s.p. N. Pašića 44 065 076 788 Doboj Gama a&a sztur Celjska 41 053 226 966 Doboj EM‐elektronik Kralja Aleksandra 211 066 804 663 Goražde Tehnika d.o.o. Mravinjac bb 061 156 046 Gračanica Dinnet d.o.o. Kamenica bb 062 346 289 061 103 900, Gradačac Elektroservis Hido H.K. Gradaščevića 110 061 178 431 065 525 637, Gradiška Koming d.o.o. Vindovdanska 21 051 814 755 Gradiška zr Frigoelektro 5. Kozarske brigade 11 066 488 479 Istočno Sarajevo Frigo‐elektro s.p. Draže Mihajlovića 64 065 142 473 Istočno Sarajevo Klima shop s.p. Spasovdanska br.6. ...
Page 124
5. Гарантниот сервисен преглед го наплатува овластениот сервис согласно ценовникот на застапникот Паком Компани дооел и го заверува гарантниот лист со што се докажува продолжувањето и важноста на гаранцијата. 6. Гаранцијата важи ако монтажата и сервисните услуги на клима уредот Vivax cool се извршени од страна на овластен сервис од страна на застапникот Паком Компани. 7. Vivax cool клима уредите се составени од внатрешна единица, инсталација и надворешна единица кои се ...
Page 125
Име на фирмата‐давател на гаранција: Паком Компани ДООЕЛ ул. Јадранска Магистрала 12, 1000 Скопје, тел.02 3202‐800 Контакт 2000‐Скопје Паком Компани дооел Централен сервис: , ул.10 бр.10 Аеродром, Скопје Jадранска магистрала бр.12, Скопје Тел. 02 246‐0000 Тел. 02/ 3202 800, факс 02/3202 892 ДАТУМ НА ПРИЕМ НА УРЕДОТ ВО СЕРВИС ДАТУМ НА ПОПРАВАЊЕ ДАТУМ НА ПРИЕМ НА УРЕДОТ ВО СЕРВИС ДАТУМ НА ПОПРАВАЊЕ ...
Page 126
СЕРВИСНИ МЕСТА Град Сервис Адреса Телефон Битола Фригомонт Трифун Пановски 28 070 269 313 Битола Г Монт Дебарска 125б 075 694 058 Велес Електрон Маршал Тито 108 043 231 381 Гевгелија Хот Контрол Солунска 5 075 650 888 Гевгелија Еко Фриго Терм Иво Лола Рибар 43 034 216 948 Гостивар Сервис Фриго Никола Парапунов 72 070 215 420 Демир Хисар Алианса Клима Контрола 2‐ри Септември бр.2 075 387 522 Дојран АБА Пеливанов с. Фурка 071 471 583 Кавадарци ...
Page 127
POŠTOVANI Zahvaljujemo na kupovini Vivax uređaja i nadamo se da ćete biti zadovoljni izborom. Ako u periodu u kojem imate pravo na reklamaciju bude potreban popravak proizvoda, molim savetujte se sa ovlašćenim prodavačem koji Vam je proizvod prodao il/i nas kontaktirajte na dolje navedene brojeve i adrese. MOLIMO VAS DA PRIJE UPOTREBE PROIZVODA PAŽLJIVO PROČITATE TE HNIČKU DOKUMENTACIJU I UPUTSTVA KOJI SU PRILOŽENI UZ PROIZVOD! IZJAVA O SAOBRAZNOSTI MODEL UREĐAJA SERIJSKI BROJ DATUM PRODAJE BROJ RAČUNA PRODAVCA POTPIS I PEČAT PRODAVCA 1. Ovom izjavom o saobraznosti proizvođač proizvoda, preko KIM TEC CG d.o.o., kao uvoznika i davaoca prava u Crnoj Gori osigurava besplatan popravak istog u skladu s vazečim propisima i u skladu s uslovima opisanim u ovoj izjavi o saobraznosti. 2. Ovom izjavom o saobraznosti ističemo da će predmet ovog prava raditi bez greške uzrokovane eventualnom lošom ...
Page 128
DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA DATUM SERVISNE INTERVENCIJE DATUM POPRAVKA Ugradnja DATUM UGRADNJE OVLAŠĆENI SERVIS I POTPIS Servisni periodični pregled i održavanje: Servisni pregled 1 Ovlašćeni servis: Datum: Vrijedi do: Servisni pregled 2 Ovlašćeni servis: Datum: Vrijedi do: Servisni pregled 3 Ovlašćeni servis: Datum: Vrijedi do: Kim Tec CG d.o.o. Ćemovsko polje bb, 81000 Podgorica, Crna Cora, Tel: 020/608‐251, E‐mail: servisi@kimtec‐ca.com ...
Page 129
POPIS SERVISNIH MJESTA Grad Servisi Adresa Telefon 068‐501‐209 Podgorica D‐MK ŠĆEPANOVIĆ doo Dalmatinska bb 067‐501‐209 Podgorica KLIMA M doo Miladina Popovića 155 067‐261‐535 Podgorica TmušićTermo Tehnika Pavla Mijovića bb 067‐181‐482 069‐312‐312 Bar FRIGO TIM doo Bulevar DJ.K.Skenderbega 030‐411‐999 Bar NS ELEKTRONIX doo Bjeliši bb 069‐527‐638 Budva NS ELEKTRONIX doo Bjeliši bb 069‐527‐638 Herceg novi MILMONT doo V Crnogorske brigade br.5 067‐584‐922 Herceg novi KOMPRESOR doo Njegoševa 150 031 ‐323‐503 Herceg novi KOROVLJEVIĆ doo ...
Page 130
TË NDERUAR BLERËS Faleminderit për bleijen tuaj dhe shpresoj se ju do të jenë të kënaqur me përzgjedhjen. Nëse periudha e garandonit është e nevojshme për të riparuar produktin, ju lutem konsultohuni me shitësin Apo me me personin i cili jua shet produktin tone JU LUTEM LEXONI ME KUJDES PARA PËRDORIMIT PRODUKTIT DOKUMENTET TEKNIKE DHE MANUALET CILAT JANË VENDOSUR NË KUTI LETGARANCIONI EMRI PRODUKTIT LLOJI DHE MODELI PRODHUESI EMËRTIMI APO EMRI 1 SHITËSIT NUMRI SERIAL DATA SHITJES VU LA: ...
Page 131
DATA PRANIMIT PAISJES SERVIS DATA RIPARIMIT DATA PRANIMIT PAISJES SERVIS DATA RIPARIMIT DATA PRANIMIT PAISJES SERVIS DATA RIPARIMIT Instalimi DATA E INSTALIMIT SHËRBIMI DHE FINSHKRIMI I AUTORIZUAR Inspektimi dhe mirëmbajtja periodike e shërbimit: Inspektimi i shërbimit 1 Data: Skadon: Inspektimi i shërbimit 2 Data: Skadon Inspektimi i shërbimit 3 Data: Skadon Inspektimi i shërbimit 4* Data: Skadon * Shërbimi i Inspektimit 4 është i vlefshëm vetëm për modelet me një garanci bazë 12‐mujore. Ask Tec d.o.o., Tahir Zajmi (Kosova tex), 10000 Prishtina ...
Page 132
SERVISET E AUTORIZUARA City Company Adress Phone Prishtine‐Fush Kosove‐Lipjan Eko Electronics Vëllezërit Fazliu Nr. 74 045553800 Prishtine‐Fush Kosove‐Lipjan Unique Rr.Isa Kastrati p.n Kompleksi ARKOS 049111499 Ferizaj Termo Ylli 044677077 Gjilan‐Viti Toni‐Impex 28 Nentori nr 60 044 490 939 Mitrovice Kulla Ahmet Maloku 60 049307307 Peje Uraniku Vitomerice 049178749 Peje CTA Sahit Bakalli nr. 24 049506447 Gjakove Lila Tech Rr. Skenderbeu 048116811 Prizren‐Suharek‐Malisheve ...
Garancijo je mogoče skupaj podaljšati trikrat, razen za model ACP‐xxxxCCxxxxx, ACP‐xxxxCTxxxxx, ACP‐xxxxDTxxxxx, ACP‐xxxxCFxxxxx, ACP‐xxxxFSxxxxx, za katero se garancija lahko podaljša za največ štirikratno obdobje (največ 60 mesecev). Garancijski in servisni pregled zaračunava pooblaščeni serviser po ceniku zastopnika podjetja. Ob servisu naprave, pooblaščeni serviser potrdi garancijski list in s tem podaljša veljavnost garancije. Garancija velja v primeru, ko je vgradnja ali servis Vivax klimatskih naprav opravljena s strani pooblaščenega serviserja, katerega je pooblastil zastopnik, podjetje SCArA‐Tec d.o.o., Gozdna ulica 2C, Spodnje Hoče, 2311 Hoče Vivax klimatsko napravo, kot celoto, sestavljajo notranja(e) enota(e), instalacija in zunanja enota, ki so pravilno izbrani in, ki so glede na model in moč kompatibilni. V primeru okvare Vivax klimatske naprave se obvezujemo, da bomo napravo v najkrajšem možnem času popravili, zagotovo pa v roku 45 dni. Če se Vivax Cool klimatska naprava ne more popraviti ali se ne popravi v roku 45 dni od ...
Page 134
Naziv podjetja, ki je izdalo garancijo: SCArA‐Tec d.o.o., Gozdna ulica 2C, Spodnje Hoče, 2311 Hoče Tel.: +386 2 618 52 08 Centralni servis: SCArA‐Tec d.o.o., Gozdna ulica 2C, Spodnje Hoče, 2311 Hoče Ime, priimek Telefonska št.: Naslov: E‐mail: Datum vgradnje: Serviser/monter: Žig in podpis DATUM SPREJEMA NAPRAVE V SERVIS DATUM POPRAVILA ...
Page 135
MONTAŽERJEV IN SERVISERJEV Mesto ‐ regija Podjetje‐montažer E‐mail Telefon: Ljubljana z okolico Tomaž Oman TO s.p. 031/ 359 921 to@siol.com Ljubljana z okolico Klima Blatnik, Jože Blatnik s.p. 031/ 394 694 klima.blatnik@yahoo.com aleksander.ponikvar@siol.ne Ljubljana z okolico Elsan, Aleksander Ponikvar s.p. 041/ 683 121 t Ljubljana z okolico Kniss d.o.o. 031/ 406 704 luka.bizjak@gmail.com 01/ 600 32 91 Ljubljana z okolico Klima ELEKTRO d.o.o. info@klimaelektro.si 080/ 33‐38 Ljubljana z okolico Elektro Čepon d.o.o. 031/ 427 446 info@elektro‐cepon.si Ljubljana z okolico VENALIA d.o.o. 0590 51 840 info@venalia.si Ljubljana z okolico PERAL, Alojz Perme s.p. info@mojaklima.si 031/ 669 888 Ljubljana z okolico Kapitan d.o.o. kapitan@telemach.net ...