Instructions for Use
Key to symbols
Symbols on the machine
This product complies with applicable EU directives
Symbols in this user manual
Warning/Caution!
Risk of crushing
Application area
The product is a variable flow damper or constant flow damper
designed for comfort ventilation indoors. The product is used to
regulate the supply air or extract air flow in ventilation ducts.
The product may not be used for anything other than its
intended use.
General
Read through the entire Instructions for Use before you
install/use the product and save the instructions for
future reference. It's not permissible to make changes
or modify this product other than those specified in this
document.
The packaging contains the following items
1 x REACT V GMB
1 x Instructions for Use
Protective equipment
Always use appropriate personal protective equipment
for the work in question, in the form of gloves, respirators
and protective glasses during handling, installation,
cleaning and service/maintenance.
Electrical safety
Permitted voltage, see "Electrical data". It is not permissible
to insert foreign objects into the product's contactor
connections or the electronics' ventilation openings; risk for
short circuiting.
24 V isolation transformer to be connected should comply with
the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product
and the power supply source.
Disconnect the power supply when working on the product and
it is not required to be running.
Always follow the local/national rules for who shall be permitted
to carry out this type of electrical installation.
The document was originally written in Swedish
Other risk
When the product is voltage fed, the damper will either
open or close. This can entail a certain risk of pinch
injuries, for example, on the fingers if these are placed
between the damper blade and ventilation duct when
the damper blade rotates. The product's actuator is
equipped with a release button that permits manual
control of the damper blade, always ensure this is
activated before working on the internal parts of the
damper.
Handling
• Always use appropriate transport and lifting devices when the
product is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring tubes.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry
regulations.
• Install the product so that it is not accessible by unauthorized
persons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the
vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection
hatch must be located so that the product is accessible for
inspection.
• If the product is mounted so that it is possible to gain access
to the inside of the product, it must be supplemented with
appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product
must be insulated on the outside against condensation.
• For installation, the accessory FSR is recommended.
• The product can be installed position-independent.
• It is recommended to mount the product so that the product's
display is visible.
• The product must be laid down prior to installation so that it
cannot fall over.
• Check to make sure that the product doesn't have any visible
defects.
• Check that the product is properly secured after it has been
installed.
• Use the product's eyes to secure the cables with cable ties.
• Check that all cables are properly secured in place after
installation.
• Check that the actuator/controller is properly mounted.
02/09/2024
Art. 1546152

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the REACT V GMBa and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Swegon REACT V GMBa

  • Page 1 REACT V GMBa Instructions for Use 02/09/2024 Art. 1546152 Key to symbols Other risk When the product is voltage fed, the damper will either Symbols on the machine open or close. This can entail a certain risk of pinch injuries, for example, on the fingers if these are placed...
  • Page 2 10908 Vnom at 120 Pa in pressure reading. Installed according to the instructions. Ø d Ø d Figure 1. Dimensions (mm), REACT V GMB circular. The damper can be installed at an optional angle. Swegon reserves the right to alter specifications. 02/09/2024...
  • Page 3: Installation

    Images 1-5 require no straight duct section (image 3 illustrates a T piece with a cleaning hatch). Image 6 requires a straight duct section before the damper equivalent to 4 x the diameter of the duct. 02/09/2024 Swegon reserves the right to alter specifications.
  • Page 4 28.4 1205 4338 6602 23767 1200 x 700 32.0 1446 5206 7923 28523 1400 x 700 35.8 1688 6077 9243 33275 Vnom at 120 Pa in pressure reading. Installed according to the instructions. Swegon reserves the right to alter specifications. 02/09/2024...
  • Page 5 Straight duct section requirements in case of sound attenuator with baffle Figure 7. Straight duct section requirements 3 x B in case of sound attenuator with baffle. Applies to both supply and extract air. 02/09/2024 Swegon reserves the right to alter specifications.
  • Page 6 Control signal 0-10 V DC / 2-10 V DC Positive half-wave, AC only Negative half-wave, AC only Mode 2-10 V: Damper closed < 0.8 V b c d e f WH OG PK GY CA C B Figure 8. Wiring diagram. Swegon reserves the right to alter specifications. 02/09/2024...
  • Page 7 Pressing button: Select between the menus Service port For connection of the hand-held terminal GUIV3-M Release button Pressed button: Actuator disconnected, the motor stops, manual overriding possible Released button: Returns to standard mode 02/09/2024 Swegon reserves the right to alter specifications.
  • Page 8 Modbus address 1…247 Communication settings b1…b32 Shows the nominal air flow Nom. The display only shows three figures; in the case of larger values, apostrophes are shown and the remaining figures are hidden Swegon reserves the right to alter specifications. 02/09/2024...
  • Page 9 4 8 0 0 - N one -1 9 6 0 0 - N one -1 19200-None-1 38400-None-1 76800-None-1 115200-None-1 76800-None-2 76800 -Even-1 76 8 0 0 - O dd -1 115200-None-2 115200-Even-1 115200-Odd-1 Standard setting 02/09/2024 Swegon reserves the right to alter specifications.
  • Page 10: Troubleshooting

    “Y” signal and the polarity on “G” and “G0”. See or change has been approved by Swegon AB; or (2) the “Connection”. serial number on the product has been made illegible or •...
  • Page 11: Performance Checks

    = set max. flow in [l/s, m /h, cfm] max. = nominal flow in [l/s, m /h, cfm], see tables pages 2 & 4. Note: Does not indicate damper position. Figure 13. Damper open. Jumper to the left. 02/09/2024 Swegon reserves the right to alter specifications.
  • Page 12: Technical Data

    IP class: IP42 (Cable installed downwards) Swegon AB hereby affirms that: Corrosivity class: REACT V GMBa complies with the essential characteristic Pressure class: demands and relevant regulations specified in the directives, 2006/42/EC (MD), 2014/30/EU (EMC) and 2011/65/EU Leakage classes according to SS-EN 1751...