Summary of Contents for Hawle HAWIDO 1500 Series
Page 2
HAWIDO - REGULATING VALVES Instruction for Pressure Reducing Valve Type 1500 ND40 - ND200 Keep this instruction manual at the location of the valve...
Page 3
Example of a nameplate Once the commissioning work has been completed, enter the following data and always specify this additional information concerning the valve type, pressure and flow ratios, whenever you consult or have reason to question the manufacture or supplier: Year of manufacture: ...........
ONTROL VALVE PRESSURE REDUCING STAINLESS STEEL DESIGN 3.4 C ONTROL VALVE PRESSURE REDUCING STAINLESS STEEL PARTS LIST 3.5 C ONTROL LINE AND ACCESSORIES 3.6 P OSITION INDICATOR DRAWING 3.7 P OSITION INDICATOR ARTS LIST ANNEX 1. T ORQUE TABLE HAWLE IN EUROPE...
2 to 40º C General safety guidelines The Hawle HAWIDO regulating valve is designed for use on drinking water supply systems. Please consult the manufacturer before using it with other media. Material damage or injury to persons can occur if it is not installed, commissioned, operated or maintained according to these instructions or to codes of practice.
Recommended installation Before the installation, all pipe work must be blown or flushed through to prevent any foreign material such as pieces of wood, stone etc. from entering the valve. Legend: Gate valve input side Strainer Pressure reducing valve, e.g. type 1500 Dual-chamber flange Mounting piece, welding part Gate valve output side...
B. Commissioning Operation diagram (1500) Components: Main valve 1200 Ball valves (A, B, C) Filter Orifice One-way flow restrictor Control valve Pressure gauge (A, B) Optical Position indicator Electrical position indicator (optional) Valve opening limiter (optional) Preparation Before commissioning the valve, check that the gate valves on the inlet and outlet sides of the valve are closed and that the flange connections are correctly tightened and sealed.
Venting Proceed as follows: Slowly open the inlet gate valve until water flows into the valve. The valve fills with water and the air escapes via the vent holes. When the valve venting procedure has caused all the air to be expelled from the control lines, retighten the headless screws.
Setting the reaction speed) Original pressure value is not Pressure gauge faulty Check or replace pressure reached gauge Changed operating conditions Reset accordingly (see Chapter: Recommended installation) Epoxy-coating damaged Transportation damage, Repair with Hawle two- installation damage component repair set for coatings...
D. Putting out of service and Maintenance Putting out of service The operating pressure reducing valve must first be hydraulically shut off as follows: Slowly close the gate valves after and before the valve Slowly close ball valve (2A, 2B, 2C) The valve is taken out of operation and the maintenance can be accomplished.
Checking the valve Remove the optical position indicator. Check that the valve spindle moves easily by raising and lowering it with the threaded rod. Install the optical position indicator. Putting the valve back into service see chapter Commissioning Checking the operation of the valve Note: In order to avoid pressure surges, large flow rates have to be throttled by closing slowly the gate valve before the Hawido - Valve.
Checking the operation of the one-way flow restrictor Undo the locknut Screw in the set screw and then unscrew it as far as it goes Screw in again a few turns. This process must be easy and with little resistance Putting the valve back into service see chapter Commissioning Checking the operation of the valve...
Page 21
-18- 0620 Coil AC voltage Indicate the voltage 0620 xxx xxx Coil Coil DC voltage Indicate the voltage 0621 xxx xxx 0630 Appliance socket for electric coil 0630 000 000 Appliance socket for electric coil 0652, 0653 Plug module for solenoid valves Type 0653 024 008 LBV 24 DC = 8-14S incl.
Page 22
1199 Ratchet with attachment for the one 1199 000 040 way flow restrictor Ratchet with attachment. 5292 Hawle Typ: VR 69-252 5292 000 000 Tube à 90 g Grease AG: Outside thread IG:Inside thread AD: Outside diameter ID: Inside diameter...
-22- E. Annex Torque table When assembling the main valve and the pilot valve, all bolts are checked with a torque wrench according to the following list. Grease the bolts before mounting ! Strenght class Diameter Hexagon bolt Tightening torque Reference Max.
Need help?
Do you have a question about the HAWIDO 1500 Series and is the answer not in the manual?
Questions and answers