Summary of Contents for First Co First-Pak FPG Series
Page 1
Installation, Operation, & Maintenance Manual IOM 8405 Rev. C 3/24 FPG SERIES Vertical Packaged Gas Heat / Electric Cooling Unit Category IV Type MSP Up to 96% AFUE ATTENTION Installer Affix these instructions on or adjacent to the furnace. Consumer Read these instructions thoroughly and retain all manuals for future reference.
Page 2
FIRST-PAK COPYRIGHT First Co. / AE-Air works to continuously improve its products and as a result, it reserves the right to change design and specifications without notice. The warranty may be void unless the Startup & Performance Checklist is completed and returned to the warrantor. If the FIRST- PAK Gas Furnace unit is not installed properly, the warranty will be void, as the manufacturer cannot be held accountable for problems that stem from improper installation.
FIRST-PAK TABLE OF CONTENTS SAFETY CONSIDERATIONS MODEL NOMENCLATURE GENERAL INFORMATION INTRODUCTION STORAGE SHIPPING & PACKAGE LIST UNIT INSPECTION CHECKLIST UNIT DIMENSIONAL DATA UNIT PHYSICAL DATA ELECTRICAL DATA INSTALLATION 13-25 REQUIREMENTS INSTALLATION PRECAUTIONS UNIT LOCATION UNIT CLEARANCE REQUIREMENTS VENT CLEARANCES REMOVAL OF A UNIT FROM A COMMON VENTING SYSTEM WALL SLEEVE INSTALLATION UNIT SUPPORT PACKAGED UNIT INSTALLATION...
1. This product should only be installed and serviced by a qualified, licensed installer or service agency. 2. Only use First Co. approved kits and accessories when modifying this product. Refer and follow instructions packaged with the kits or accessories when installing.
Page 5
FIRST-PAK SAFETY CONSIDERATIONS CONTINUED SAFETY RULES: 10. This furnace is equipped with a blocked vent shut-off system. If the furnace fails to operate, contact a qualified 1. This furnace is approved for use with Natural Gas only. service agency for repair. Refer to the FURNACE RATING PLATE.
Page 6
FIRST-PAK SAFETY CONSIDERATIONS CONTINUED 13. The following items should be inspected annually WARNING (minimum) before each heating season by a qualified service agency: a. HEAT EXCHANGER TUBES: make sure they are free HIGH VOLTAGE! from blockages, signs of carbon buildup or heavy Disconnect all power before servicing.
ELECTRIC SHOCK HAZARD INTRODUCTION Before servicing equipment, ALWAYS turn off all power FIRST-PAK FPG series are packaged gas heat / electric to the unit. There may be more than one disconnect cooling units. The unit design has been certified by Intertek switch.
FIRST-PAK STORAGE Equipment should be stored in a clean dry, conditioned area with maximum temperatures up to 120°F [48.89°C] and minimum temperatures to 32°F [0°C]. Units should be stored upright and in an indoor environment. It is recommended to leave packaging on the unit until the installation is to begin.
FIRST-PAK UNIT INSPECTION CHECKLIST Complete the inspection procedures below before preparing unit for installation: NOTE 1) Visually inspect unit for any shipping damage. Damage Check the unit nameplate for correct voltage with the must be reported immediately to the shipping plans before installing the equipment.
FIRST-PAK ELECTRICAL DATA ELECTRICAL DATA CONDENSOR INDOOR MIN. MAX. VOLTAGE-PH- COMPRESSOR MIN. MAX. MODEL NUMBER MOTOR MOTOR CIRCUIT CIRCUIT VOLTAGE VOLTAGE AMPACITY PROTECTION FPG22N9012C* 208/230-1-60 FPG33N9012C* 208/230-1-60 FPG44N9012C* 208/230-1-60 FPG22N9018C* 208/230-1-60 FPG33N9018C* 208/230-1-60 FPG44N9018C* 208/230-1-60 FPG55N9018C* 208/230-1-60 FPG33N9024C* 208/230-1-60 10.7 FPG44N9024C* 208/230-1-60 10.7...
This appliance is not CAUTION design certified for installation in mobile homes, recreational vehicles, or outdoors. A First Co. approved wall When the unit is in operation components are rotating sleeve must be used to install the FPG unit.
FIRST-PAK INSTALLATION CONTINUED UNIT CLEARANCE REQUIREMENTS The unit may be installed with zero clearances to adjacent combustible surfaces. This furnace shall not be installed directly on carpeting, tile, or other combustible material, other than wood flooring. Service clearance must be provided for future maintenance and service.
FIRST-PAK INSTALLATION CONTINUED VENT CLEARANCES FIGURE 9 - Location of Vent Termination Clearances VENT TERMINATION CLEARANCES CLEARANCE CANADIAN INSTALLATIONS¹ US INSTALLATIONS² A = Clearance above grade, veranda, porch, deck, or 12 in (30 cm) 12 in (30 cm) balcony (see 1.23.5-i(9)b.) B = Clearance to window or door that may be opened 6 in (15 cm) for appliances 10,000 Btuh (3 kW) 12 in (30cm) for appliances >10,000 Btuh(3 kW)
FIRST-PAK INSTALLATION CONTINUED REMOVAL OF A UNIT FROM A COMMON VENTING SYSTEM WARNING When an existing furnace is removed from a common venting system serving other appliances, the venting ELECTRIC SHOCK HAZARD system is likely to be too large to properly vent the Disconnect all power supplies before servicing.
FIRST-PAK INSTALLATION CONTINUED WALL SLEEVE INSTALLATION Refer to installation instruction packed with the wall sleeve REAR INSTALLATION & DIMENSIONS to assemble and mount into the wall. Before unit installation, make sure sleeve components are not damaged; drain line is not obstructed and is leak free. Check all seals to ensure that they are in position and un- damaged.
INSTALLATION CONTINUED UNIT SUPPORT The FIRST-PAK wall sleeve is not intended or designed to Things to consider prior to build the support structure: provide complete support for the FIRST-PAK unit. Additional support is required. A field constructed platform 1. Accurately measure the unit and choose a strong may be used for this purpose and may also be constructed building material for the support structure.
FIRST-PAK INSTALLATION CONTINUED PACKAGED UNIT INSTALLATION Insulation is used in indoor equipment to provide a barrier NOTE between outside air conditions surrounding the unit and the varying conditions inside the unit. If the insulating Locate the unit in an area that meets minimum barrier is damaged, the surrounding ambient air will affect clearance requirements for all service access panels the inside surface temperature of the cabinet;...
Page 21
FIRST-PAK INSTALLATION CONTINUED PACKAGED UNIT INSTALLATION 6. Ensure that the wall sleeve is installed squarely and is secured before installing the unit. NOTE 7. Inspect the sleeve seal, which is supplied with the sleeve, to ensure that it is properly secured and Check nameplate voltage, amperage and fuse size for aligned (see FIGURE 13 –...
FIRST-PAK INSTALLATION CONTINUED DUCTWORK AND DUCT CONNECTIONS IMPORTANT Both supply and return air ducts must be attached to the unit. IMPORTANT The supply duct connection must be sized to a minimum of the same size as the unit discharge air opening.
FIRST-PAK INSTALLATION CONTINUED GAS HEAT CONDENSATE DRAINAGE AIR FILTER In addition to air conditioning condensation, the FPG**N9 The FIRST-PAK unit must not be operated without an air unit will produce condensation during the combustion filter in place. The unit is equipped with a factory installed process.
FIRST-PAK INSTALLATION CONTINUED COMBUSTION AIR GAS PIPING & CONNECTION This is a direct vent furnace, which receives its combustion All gas piping and connections to this furnace must be air from outside and discharges the products of performed by a qualified installer. Installation methods and combustion outside.
FIRST-PAK INSTALLATION CONTINUED GAS PIPING & CONNECTION CONTINUED WARNING FIRE OR EXPLOSION HAZARD WARNING Failure to follow the safety warnings exactly could In the State of Massachusetts: result in serious injury, death or property damage. This product must be installed by a licensed Plumber or Never test for leaks with an open flame.
FIRST-PAK ELECTRICAL HIGH VOLTAGE LOW VOLTAGE THERMOSTAT WARNING A standard 24 VAC single stage heating and cooling thermostat is required to control this unit. For ELECTRIC SHOCK HAZARD FPG**N9030C units, a dual stage thermostat must be used Disconnect all power supplies before servicing. Lock in order to reach rated system performance.
FIRST-PAK CONTROLS CONTROL BOARD SIGNAL PROBLEM POSSIBLE CAUSE CHECKS & CORRECTIONS SLOW FLASH Stand-by mode, awaiting call from room Status = Stand-by mode; does not Status of stand-by mode displayed no thermostat indicate fault condition fault indicated RAPID FLASH Room thermostat is requesting heat Status = Thermostat requesting heat;...
Page 28
FIRST-PAK FIGURE 23 - Control Board COOLING OPERATION When the unit is given a "Y" input the unit will operate in steady state cooling mode. The compressor will FIGURE 24 – Electrical Component immediately come on after a "Y" input. After a 5s time delay the indoor fan will be energized.
Page 29
FIRST-PAK CONTROLS CONTINUED BLOWER CONTROL FPG gas heat units are equipped with a direct drive indoor blower motor. All models have 5 fan speeds: T1 is the constant fan speed. T2 is used for freeze protection. T3 may be used for heating mode providing the speed selection allows the unit to operate within specified temperature rise range.
FIRST-PAK HEATING OPERATIONS FIGURE 26 - Heating Sequence of Operations FPG SERIES – IOM (REV. C 3/24)
Page 33
FIRST-PAK HEATING OPERATIONS CONTINUED TO LIGHT BURNERS 1. Turn off electrical power to the unit. 2. Turn the room thermostat to the lowest setting. Check that the position of the gas valve switch is in the “on” position (see FIGURE 28 – Gas Valve Check that the position of the manual gas shut-off valve is in the “on”...
Page 34
FIRST-PAK HEATING OPERATIONS CONTINUED GAS SUPPLY PRESSURE 4. Connect tubing and a manometer to the 1/4” hose barb connector. 1. Turn “off” the gas supply to the furnace using the manual gas valve. 2. Remove the inlet pressure port plug using a 3/16” hex wrench.
FIRST-PAK HEATING OPERATIONS CONTINUED TEMPERATURE RISE This gas furnace is designed to operate within a specific range of temperatures while in heating mode. The “Temperature Rise” range is shown on the rating plate. MEASURE Temperature rise is defined as the temperature difference SUPPLY TEMP between the air entering the furnace and the air leaving SUPPLY...
FIRST-PAK CIRCUIT SCHEMATIC FIGURE 39 - Circuit Diagram STARTUP INSTRUCTIONS PRE-STARTUP CHECKS: PRIOR TO THE STARTUP OF THE UNIT: 1. Ensure supply voltage matches nameplate data. 2. Ensure the unit is properly grounded. WARNING 3. With the power off, check blower wheel set screws for proper tightness and that the blower wheel Electrically ground the unit.
Page 43
FIRST-PAK STARTUP INSTRUCTIONS CONTINUED UNIT STARTUP: Example of input rate calculation using the typical heating 1. Ensure that power is connected to the unit and the valve of Natural Gas of 1,000 BTU cu/ft, and 90 seconds local disconnect is switched to ON position. time to complete one revolution of the 1 cu/ft dial on the 2.
FIRST-PAK TROUBLESHOOTING HEATING PROBLEM POSSIBLE CAUSE CHECKS & CORRECTIONS Open Circuit Fuse (Electrical Panel) Replace fuse Open Circuit Breaker (Electrical Panel) Re-set circuit breaker / fuse OPERATION Open Unit Power Switch Check position / electrical state of switch (External disconnect, adjacent to unit) Refer to LED &...
FIRST-PAK TROUBLESHOOTING CONTINUED HEATING Step 1 Thermostat calls for heat by energizing “W” terminal with 24 volts a/c Expected The room thermostat R terminal is constantly powered with 24 volts a/c by its connection to the control board R Operation terminal and the unit transformer.
Page 46
FIRST-PAK TROUBLESHOOTING CONTINUED HEATING Step 6 Control board energizes the spark ignitor & the gas valve (trial for ignition) Expected During trial for ignition, the draft inducer, & gas valve are energized. After 10 seconds, the spark ignitor is de- Operation energized &...
FIRST-PAK TROUBLESHOOTING CONTINUED COOLING PROBLEM POSSIBLE CAUSE CHECKS & CORRECTIONS Power supply off Apply power; close disconnect. Blown Fuse Replace fuse or reset circuit breaker. Check for correct fuses. If voltage is below minimum voltage specified on unit data plate, Voltage supply low ENTIRE UNIT contact power company.
Page 48
FIRST-PAK MAINTENANCE & SERVICE - HEATING AIR FILTER(S) COMBUSTION AIR PROVING SWITCH Furnace filters should be checked monthly and replaced as necessary. Do not operate the furnace without filters in The combustion air-proving switch is a safety device which place. The Interval of filter replacement will vary with verifies operation of the combustion blower and that the environmental factors and the size and type of filters used.
Page 49
FIRST-PAK GAS HEAT CONDENSATE DRAIN &TRAP The heating condensate drain trap receives the water created by the combustion process. Water is carried to the trap by a drain tube which runs from the heat exchanger collector box to the drain trap located in the cooling chassis behind the evaporator coil.
Page 50
FIRST-PAK MAINTENANCE & SERVICE – HEATING CONTINUED INDOOR BLOWER MOTOR PERIODIC INSPECTIONS Check the openings on the end of the indoor blower motor The following items should be inspected annually to make sure they are not blocked and free from debris. (minimum) before each heating season by a qualified The indoor blower motor contains permanently sealed ball service agency:...
Page 51
FIRST-PAK MAINTENANCE & SERVICE – HEATING CONTINUED HEATING MODULE REMOVAL The entire gas heat section may be removed as a unit for service if required. 1) Turn off electrical power to furnace and disconnect low and high voltage field wiring at unit.
Page 52
FIRST-PAK FIGURE 43 – Heating Access Panel Removal FPG SERIES – IOM (REV. C 3/24)
Page 53
FIRST-PAK MAINTENANCE & SERVICE – COOLING AIR CONDITIONER MODULE REMOVAL FIGURE 49 – Drain Tube Disconnection The air-conditioning chassis may be removed as a unit for service if required. Turn off electrical power to refrigeration chassis. 1) Remove screws (2) from controls cover and remove panel.
Page 54
FIRST-PAK MAINTENANCE & SERVICE – COOLING CONTINUED 6) Slide-out refrigeration chassis FIGURE 48 – Slide AIR CONDITIONER MODULE REASSEMBLY Out Chassis 1) To put-back the chassis, make sure all the 7) Side panel can be removed from the evaporator refrigerant lines are in place and there are no section to service the TXV.
Page 55
FIRST-PAK PREVENTIVE MAINTENANCE To achieve maximum performance and service life of WARNING equipment, a formal schedule of regular maintenance should be established and followed. ELECTRIC SHOCK HAZARD Check motor connections to ensure they are secure WARNING and in accordance with the unit wiring diagram. It is illegal to discharge refrigerant into the ECM motors have line voltage power applied at all atmosphere.
FIRST-PAK REPLACEMENT PARTS Table 15 – Replacement Part For service part inquiries, please contact 8273 Moberly Lane Dallas, TX 75227 214-388-5751 FPG SERIES – IOM (REV. C 3/24)
FIRST-PAK STARTUP & PERFORMANCE CHECKLIST FIGURE 49 - Startup and Performance Checklist (1 of 2) FPG SERIES – IOM (REV. C 3/24)
Page 58
FIRST-PAK STARTUP & PERFORMANCE CHECKLIST CONTINUED FIGURE 50 - Startup and Performance Checklist (2 of 2) NOTES FPG SERIES – IOM (REV. C 3/24)
Need help?
Do you have a question about the First-Pak FPG Series and is the answer not in the manual?
Questions and answers