Summary of Contents for First Co COOL-PAK ECO Series
Page 1
Installation, Operation, & Maintenance IOM 7202 Rev. A 12/23 COOL PAK AC (ECE) SPACE CONSTRAINED AIR CONDITIONERS WITH ELECTRIC HEAT ATTENTION Read all instructions thoroughly and retain all manuals for future reference.
Page 2
COOL-PAK AC IOM COPYRIGHT The Manufacturer works to continually improve its products and as a result, it reserves the right to change design and specifications without notice. The warranty may be void unless the Startup & Performance Checklist is completed and returned to the warrantor. If the COOL-PAK AC unit is not installed properly the warranty will be void as the manufacturer cannot be held accountable for problems that stem from improper installation.
COOL-PAK IOM TABLE OF CONTENTS SAFETY CONSIDERATIONS MODEL NOMENCLATURE GENERAL INFORMATION UNIT OPERATION STORAGE UNIT INSPECTION CHECKLIST ECE UNIT DIMENSIONAL DATA UNIT PHYSICAL DATA ELECTRICAL DATA 11-16 INSTALLATION INSTALLATION PRECAUTIONS UNIT LOCATION UNIT CLEARANCE REQUIREMENTS WALL SLEEVE INSTALLATION PACKAGED UNIT INSTALLATION DUCTWORK FRESH AIR VENT CONDENSATE DRAIN...
COOL-PAK AC IOM SAFETY CONSIDERATIONS 1. READ THE ENTIRE MANUAL BEFORE STARTING THE INSTALLATION. 2. These instructions are intended as a general guide and do not supersede national, state, or local codes in any way. 3. Altering the product, improper installation, or the use of unauthorized factory parts voids all warranty or implied warranty and may result in adverse operation and/or performance or may result in hazardous conditions to service personnel and occupants.
COOL-PAK AC IOM GENERAL INFORMATION UNIT OPERATION The Eco-series COOL-PAK AC models are a space constrained package air-conditioning unit with Unit Operating Range °F [°C] integrated electric heat or hot water. The unit is tested Cooling Condition to AHRI 210/240 2023 and is in compliance with UL 1995 Rev 5.
COOL-PAK IOM UNIT INSPECTION CHECKLIST Before preparing unit for installation, complete the NOTE inspection procedures below. Check the unit nameplate for correct voltage with the plans 1) Visually inspect unit for any shipping damage. before installing the equipment. Damage must be reported immediately to the Ensure that all electrical ground, connections are made in shipping company to make a claim.
COOL-PAK IOM UNIT PHYSICAL DATA PHYSICAL DATA COOL-PAK Model ECE092**B ECE122**B ECE182**B ECE242**B ECE302**B Compressor (Quantity) Rotary (1) Scroll (1) Factory Charge (R410A) lb. [kg] [1.53] [1.85] [2.36] [2.39] [2.48] ID MOTOR Motor (Quantity) Fan Motor Type Motor HP OD MOTOR Motor (Quantity) Fan Motor Type Motor HP...
COOL-PAK AC IOM ELECTRICAL DATA ECE ELECTRICAL DATA (208/230-1PH-60HZ) MIN. CIRCUIT MAX. OVERCURRENT COMPRESSOR OUTDOOR MOTOR INDOOR MOTOR AMPACITY (MCA) PROTECTION (MOP) Model CIRCUIT 1 (L1-L2) CIRCUIT 1 (L1-L2) Number 240V 208V 240V 208V 16.4 18.5 ECE09203B 11.6 11.6 ECE12200B 17.0 19.1 ECE12203B...
COOL-PAK IOM INSTALLATION INSTALLATION PRECAUTIONS WARNING CAUTION When soldering and brazing, it is recommended that fire extinguishers be available. When soldering and brazing close Always wear all appropriate personal protection Equipment to valves or sensitive components, heat shields or wet rags when installing and servicing units.
COOL-PAK AC IOM INSTALLATION (continued) UNIT LOCATION UNIT CLEARANCE REQUIREMENTS The COOL-PAK AC is designed for through-the-wall Service clearance must be provided for future installation. The interior portion of the unit is maintenance and service. A minimum of 29 in. [73.66 surrounded by a closet with a rear access Figure 5.
COOL-PAK IOM INSTALLATION (continued) 3" Min. WALL SLEEVE INSTALLATION Refer to installation instruction packed with the wall sleeve to assemble and mount into the wall. Before unit installation, verify that sleeve components are not 3" Min. Installed Wall Sleeve damaged and that the drain line is unobstructed free of NOTE: Sleeve dimensions vary Min.
COOL-PAK AC IOM INSTALLATION (continued) PACKAGED UNIT INSTALLATION 1) Before installing the unit in the sleeve be sure to go through the unit inspection check-list 2) Open the rear access door to grab loose items such as a electrical disconnect. Architectural Louver 3) Ensure that properly sized ductwork is in place...
COOL-PAK IOM INSTALLATION (continued) AIR FILTER DUCTWORK All indoor return air must be filtered. The preferred Discharge ductwork is normally used with these units. methods are listed below. When return air ductwork is required, the unit is supplied with 1 in. [5.08 cm] thick filter rack/duct collar 1.
COOL-PAK AC IOM CONDENSATE DRAIN The COOL-PAK is designed so that the wall sleeve is the principle drain pan. Drain tubing is factory installed which drains evaporator condensate though the bottom of the unit which then is allowed to drain into the wall sleeve pan.
COOL-PAK IOM ELECTRICAL THERMOSTAT REQUIREMENTS HIGH VOLTAGE A minimum of a 1C/1H thermostat is required to operate All wiring must comply with local and national code the COOL-PAK AC. Thermostat connections are as requirements. Units are provided with wiring diagrams follows: and nameplate data to provide information required for THERMOSTAT CONNECTIONS KEY...
COOL-PAK AC IOM CONTROLS ECO SERIES CONTROL MODULE Figure 12 - ECO Series Control Module POWER-UP ANTI-SHORT CYCLE DELAY When power is first applied to the control, all timers are After the compressor output has been energized the reset. The control will execute a random start delay control will execute a 6-minute anti short cycle delay before allowing normal operation of outputs, and a from the time the compressor is de-energized, before...
COOL-PAK IOM output will be energized. When the “W2” input is CONTROLS (continued) removed, all of the outputs will be turned off COOLING OPERATION immediately. STEADY STATE COOLING If the “W2” thermostat input is present with a “W1/Y” When the “W1/Y” input is present, and and the input, the control will switch the system to auxiliary heat compressor is not being held off by the anti-short cycle mode and will de-energize the compressor and...
COOL-PAK IOM 4. Set system switch to “Cool” and lower the STARTUP INSTRUCTIONS thermostat set point to coldest setting. The PRE-STARTUP CHECKS compressor should energize as well as the outdoor Before start-up, thoroughly check all the components. fan and indoor blower. Optimal operation of equipment requires cleanliness.
COOL-PAK AC IOM TROUBLESHOOTING PROBLEM POSSIBLE CAUSE CHECKS & CORRECTIONS Power supply off Apply power; close disconnect. Blown Fuse Replace fuse or reset circuit breaker. Check for correct fuses. If voltage is below minimum voltage specified on unit data plate, contact lower Voltage supply low power company.
Page 27
COOL-PAK IOM TROUBLESHOOTING (continued) PROBLEM POSSIBLE CAUSE CHECKS & CORRECTIONS Recalculate heating and cooling loads. If not excessive, possibly adding Unit undersized insulation will rectify the situation. Loss of conditioned air by Check for leaks in ductwork or introduction of ambient air through doors or leaks windows.
COOL-PAK AC IOM MAINTENANCE & SERVICE PREVENTIVE MAINTENANCE WARNING To ensure maximum performance and service life of equipment, a formal schedule of regular preventative ELECTRIC SHOCK HAZARD maintenance must be established and adhered to. Check motor connections to ensure they are secure and in Failure to do establish and perform preventative accordance with the unit wiring diagram.
Need help?
Do you have a question about the COOL-PAK ECO Series and is the answer not in the manual?
Questions and answers