Global Fire Equipment JNR-V4-2 Installation & Commissioning Manual

Fire alarm control panel
Table of Contents

Advertisement

Quick Links

www.acornfiresecurity.com
Manufacturers of Fire Detection Equipment
JUNIOR V4 - FIRE ALARM CONTROL PANEL
INSTALLATION & COMMISSIONING MANUAL - 06/2016
JUNIOR V4
FIRE ALARM CONTROL PANEL
INSTALLATION & COMMISSIONING MANUAL
VERSION 1.0 - 06/2016
www.globalfire.pt
www.acornfiresecurity.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the JNR-V4-2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Global Fire Equipment JNR-V4-2

  • Page 1 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 JUNIOR V4 FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL VERSION 1.0 - 06/2016 www.globalfire.pt www.acornfiresecurity.com...
  • Page 2: Table Of Contents

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 OVERVIEW Introduction................................... Key Features................................... Access Levels..................................Typical System Schematic..............................Power Requirements................................Battery Requirements................................. ABS box information................................Identifying Components..............................EN54 Information................................. Recommended Cables...............................
  • Page 3 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Sounder Audibility Check..............................Panel....................................Analogue Loop Monitoring.............................. Open Circuit Test................................. Conventional Sounder Monitoring..........................Detector Tests..................................Detector Tests By Zone.............................. Unassigned Detector Test............................Wrapping Up Installation And Commissioning......................
  • Page 4 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 5 Input/Output - Disable & Assign ..........................5-1 Configure I/O Groups..............................5-2 Select Fault I/O Group..............................5-3 Assign I/O Group to Device............................5-4 Inhibit I/O for Device..............................
  • Page 5 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 7 Monitor Device Counts & Test ..........................7-1 Device Count, Type & Value............................7-2 Test Sounders................................. 7-3 Sounders on Test Activation............................. 7-4 Test Zones..................................
  • Page 6: Introduction

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 OVERVIEW INTRODUCTION This document covers the installation and commissioning of a JUNIOR fire alarm panel. This document is intended for use by a competent, qualified, fire alarm installation engineer. The JUNIOR fire alarm system should be tailored to the building requirements.
  • Page 7: Access Levels

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 ACCESS LEVEL 1 - General User Unless otherwise indicated, in order to enable the operation of a particular switch, either a valid User or Programming Access Code is required to be entered.
  • Page 8: Typical System Schematic

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 TYPICAL SYSTEM SCHEMATIC 24 V VOLTAGE FREE NORMALLY OPEN CONTACTS NON-LATCHING ACTION REMOTE DISABLEMENT OF SELECTED DETECTORS CLASS CHANGE REMOTE EVAC. Loop 2 ALL AUX RELAYS RATED AT PC Loader...
  • Page 9: Power Requirements

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 POWER REQUIREMENTS LIVE NEUTRAL EARTH MEANWELL MODEL: PS-45-27 DANGER 220 VOLTS POWER SUPPLY SPECIFICATION - MEANWELL Model: PS-45-27 MAINS SUPPLY VOLTAGE 85-264 V 50/60 Hz INTERNAL POWER SUPPLY Min.
  • Page 10: Battery Requirements

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 BATTERY REQUIREMENTS The battery AH required are calculated from the following formula: Quiescent current in mA of Standby time required in the panel with everything hours divided by 1000.
  • Page 11: Abs Box Information

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 ABS BOX INFORMATION 273 mm 106 mm VIEW FROM FRONT VIEW FROM SIDE VIEW FROM REAR VIEW FROM TOP DIMENSIONS SIZE 273 (W) x 403 (L) x 106 (H) mm WEIGHT WITHOUT BATTERIES 1,6 Kgs...
  • Page 12: Identifying Components

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 IDENTIFYING COMPONENTS INSIDE JUNIOR www.globalfire.pt www.acornfiresecurity.com...
  • Page 13 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 JUNIOR MAIN BOARD FRONT VIEW REAR VIEW Junior Expansion Junior Expansion Loop Card Loop Card www.globalfire.pt www.acornfiresecurity.com...
  • Page 14 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 NOTE: Junior can only be networked with repeater panels. J-NET-INT-485-NEW INTERFACE FOR RS485 COMMUNICATION J-NET-INT-FO FIBRE OPTIC INTERFACE J-NET-INT-TCP/IP INTERFACE FOR TCP/IP COMMUNICATION UNIOR -SIM...
  • Page 15: En54 Information

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 EN54 INFORMATION In accordance with EN54pt.2 1997/AC:1999 clause 13.7, the maximum number of sensors and/or manual call points in this panel, will not exceed 512 units. The Fire Detection Control Panel complies with the requirements of EN54 pt.
  • Page 16: Recommended Cables

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 RECOMMENDED CABLES Analogue Loops, Conventional Sounders and Data Loops Fire rated Cables for Loops and Sounder Circuits AEI type Firetec Multicore Ref. F1C1 (1 mm ) to F1C2.5 (2.5 mm ) in 2 core AEI type Firetec Armoured Ref.
  • Page 17: Definitions

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 DEFINITIONS Analogue Loop The physical link, usually fireproof 2 conductor shielded wiring cable, forming a ring of interconnection between sensors and the detection panel. Cable form A connecting lead.
  • Page 18: Installation

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 INSTALLATION INTRODUCTION This section covers the physical installation of the system. It primarily focuses on the parts that are required and how they should be connected together.
  • Page 19: Panel Main Board - Connection Definitions

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 PANEL MAIN BOARD - CONNECTION DEFINITIONS JUNIOR MAIN BOARD Loop connections. A1 corresponds to Loop 1 and A2 to Loop 2 Conventional sounder circuit 1 Conventional sounder circuit 2 5 pin connector for RS485, Fibre-optic or TCP/IP (LAN) connection with repeater panel...
  • Page 20: Fitting Junior Expansion Loop Card

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 FITTING JUNIOR EXPANSION LOOP CARD 1 - This operation should only be performed by qualified personnel. 2 - Power to the panel should be completely removed, both primary and secondary (batteries) supplies, before the installation process of the card is initiated.
  • Page 21: Data Loops

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 DATA LOOPS If the system includes mini-repeaters to allow remote viewing and control of the system, an RS422/485, Fibre Optic or TCP/IP connection may be used. For redundancy in the case of RS422/485 and Fibre Optic this can be wired in the form of a Loop, thus protecting the Data Loop from interruptions or short circuits by creating a bi-directional communications flow.
  • Page 22: Panel Rs485

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 PANEL RS485 NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards. If a repeater panell is required, the appropriate interface board for the desired communications media must be installed in both the panel and repeater.
  • Page 23: Repeater Rs485

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 REPEATER RS485 NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards. The repeater connections to the RS485 Interface are basically the same as for the Panel.
  • Page 24: Panel Fibre Optic

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 PANEL FIBER-OPTIC NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards. Connection is made using fibre optic cable instead of copper cable.
  • Page 25: Repeater Fibre Optic

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 REPEATER FIBER-OPTIC NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards. The repeater connections to the Fibre-Optic Interface are basically the same as for the Panel.
  • Page 26: Analogue Loop

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 TCP/IP Connection The use of a TCP/IP network may require the support and co-operation of the end users IT department. Be sure that this support is available before deciding on this communications method.
  • Page 27: Conventional Sounders

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 CONVENTIONAL SOUNDERS Conventional Sounders is the term used to describe conventional alarm sounders (or bells) connected directly to a Panel. Loop-powered Sounders are different and are connected to the Analogue Loop. Two Conventional Sounder circuits are provided on the Panel.
  • Page 28: Panel Batteries

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 PANEL BATTERIES It is recommended that the batteries are fitted at the end of commissioning the system otherwise it can be difficult to remove the power quickly if there is a problem.
  • Page 29: Commissioning

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 COMMISSIONING INTRODUCTION Commissioning involves checking that all connections have been made properly and that all hardware is functioning correctly. This means the system must first be installed in accordance with the previous section of this manual.
  • Page 30 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 CONTROLS BUZZER SILENCE The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this switch, the operation of the buzzer will be stopped until a new fire or fault appears on the system.
  • Page 31 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 QUEUE REVIEW FIRE - General User Access (no code entry required) If more than one fire has been detected then the LED next to this button will flash. Press the button to step through all detected fires.
  • Page 32: Getting The Panel Running

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 GETTING THE PANEL RUNNING Apply AC power to the Panel. The LCD should display the software version and the message ‘INITIALIZING’ . This will be followed by the date and time (and the company name if it has been set).
  • Page 33: Getting Into Programming Mode

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 GETTING INTO PROGRAMMING MODE (ACCESS LEVEL 3) When the Panel is powered up it will be necessary to enter the panel programming mode. Familiarize yourself with this section before proceeding to the next section in the manual and powering up the panel.
  • Page 34 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Logging In To enter programming mode you need to log in. The Panel must be powered up and must have initialized itself i.e. NOT be showing the ‘INITIALIZING’ message. Press ENTER on the Keypad.
  • Page 35: Getting The System Running

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 GETTING THE SYSTEM RUNNING Ensure all connectors are firmly in place. Ensure that all connections are tight, with no stray strands of wire. Ensure that the SIM CARD is securely fitted in the Panel and Repeaters.
  • Page 36: Learning Which Devices Are Fitted

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Learning Which Devices Are Fitted Enter programming mode. (See page 6 Access Levels, Installer Access Code) If site specific data has NOT been pre-programmed then select function 8-3-1 Clear Customer Flash Memory and clear the customer flash.
  • Page 37: Panel

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Analogue Loop Monitoring Check that a short circuit or open circuit is detected on any of the Analogue Loops. Open Circuit Test Disconnect either the + or the - OUT connection for the Loop.
  • Page 38: Detector Tests

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Detector Tests If the devices have been assigned to Zones (on a pre-programmed SIM CARD or via the programming menus) then it is possible to test the detectors with limited or no sounder operation.
  • Page 39: Battery Fault Message Test

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Battery Fault Message Test This test should be performed for each set of batteries. Test only the actual battery connections. Panel Main Board STATUS ZONES QUEUE REVIEW...
  • Page 40: Advanced Functionality

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 ADVANCED FUNCTIONALITY PROGRAMMING FUNCTIONS GENERAL 1 Review Historic Log 6-3 Discovery Specific - Functions only available for 1-1 Display Historic Log panels programmed to use Apollo Discovery Protocol 1-3 Clear Historic Log 6-3-1 Select Device Sensitivity Mode...
  • Page 41: Keys To Use Within Functions

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Keys To Use Within Functions Most functions use some or all of the following keys: are used to browse through items is often used to change fields (move the cursor).
  • Page 42: Specific Functions

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 SPECIFIC FUNCTIONS Review Historic Log All the functions associated with reviewing or printing events and settings. 1-1 Display Historic Log The panel logs all events in an internal event log. It can store a rolling 2000 entries. When it is full the latest entry is added and the oldest entry discarded.
  • Page 43: Zones - Disable & Assign

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Zones - Disable & Assign All the functions associated with managing Zones 3-1 Disable Zones Allows you to disable or enable Zones. All devices in disabled Zones will cease to operate with the exception of the (audible) output from loop sounders.
  • Page 44: Sounders - Disable & Assign

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Sounders - Disable & Assign 4-1 Sounder Configuration Allows selection of PRESET or PROGRAMMED sounder operation. Selecting PRESET (the default) will result in all sounders being operated; any Sounder Group settings will be ignored.
  • Page 45: Disable Sounders

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 4-3 Disable Sounders Allows specific sounders to be disabled or Enabled. Disabled sounders will not be operated regardless of Sounder Configuration, Sounder Groups and evacuate requests.
  • Page 46: Sounder Delay Set-Up

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 4-6 Sounder Delay Set-up Allows the sounder delay to be set-up: The sounder delay can be set to GLOBAL MODE, ZONAL MODE or DISABLED. The sounder delay period is defined (to a maximum of 10 minutes).
  • Page 47: Input/Output - Disable & Assign

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Input/Output - Disable & Assign Input/Output Analogue Loop device management. 5-1 Configure I/O Groups Allows an I/O Group to be established. The I/O Group can then be used for fire or fault reporting. 512 I/O Groups can be defined.
  • Page 48: Assign I/O Group To Device

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 5-4 Inhibit I/O for Device Allows a device to be set so that it does not operate certain I/O Groups. The options are: COMMON The Common I/O Group (512) is not activated when the device detects fire ZONAL...
  • Page 49: Device Set-Up

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Device Set-up Allows specific settings to be selected for individual Analogue Loop devices. 6-1 General Settings common to all types of Analogue Loop devices. 6-1-1 Disable Loops Allows a specific Analogue Loop to be disabled or enabled.
  • Page 50: Set Device Reporting Details

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 6-1-4 Set Device Reporting Details Each device can be set to: FIRE FAULT PRE-ALARM TRANSPARENT The default is FIRE reporting. When the device is activated or reaches its alarm threshold then the event is reported in accordance with this setting.
  • Page 51: Global Sensitivity Set-Up

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 6-1-8 Global Sensitivity Set-up This function selects the sensitivity of all the detectors that have been set to GLOBAL SENSITIVITY. Different settings can be entered for weekdays and for Saturday and Sunday. Settings are : HIGH (alarm threshold of 45)
  • Page 52: Other Device Options

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 6-2 Other Device Options 6-2-1 Select Device Heat Grade This function is only applicable to Heat Detectors. It has no effect on other devices. It allows the alarm threshold for the heat detector to be set.
  • Page 53: Discovery Specific

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 6-3 Discovery™ Specific Analogue Loop device settings that are specific to devices that support the Discovery™ communication protocol. These functions will only act on Sub-panels that are set to Discovery™ protocol. 6-3-1 Select Device Sensitivity Mode Allows a specific operating mode to be selected for a specific device.
  • Page 54 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 6-3-5 Check for Devices Needing Service When activated this function reads the drift compensation value of every Discovery™ device connected to the system.
  • Page 55: Automatic Address Setting (Sam)

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 6-4 Automatic Address Setting (ASET) - Wizmart Protocol only Introduction Automatic Address Setting (ASET) is a special install and commissioning mode that can be activated on a per loop basis whilst in INSTALLATION mode.
  • Page 56: Activate Aset Mode (Sam)

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 In order to initiate the programming procedure of the SAM’s the Panel has to be in INSTALLATION MODE. See function 8.4.1. 6-4-1 Activate ASET Mode (SAM) The enabling of this mode is done on a per loop basis.
  • Page 57: Clear Loop

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 NOTE: A programmed SAM that has been RESET and re-enters the fire condition will force the panel to activate the sounders without a new address being programmed. The panel will activate the bells/sounders every time there is a new fire condition, regardless of it being caused by a new address being attributed or not.
  • Page 58: Troubleshooting Sam

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 TROUBLESHOOTING a) SAM does not program If during the course of programming a SAM, the new address is not programmed in the module, verify that the connections to both the loop and the conventional device are correctly made.
  • Page 59: Monitor Device Counts & Test

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Monitor Device Counts & Test 7-1 Device Count, Type & Value Use this function to check that all loop devices are present. to select the device address on that loop.
  • Page 60: General

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 General 8-1 Time/Date & Timers 8-1-1 Set Date & Time Allows the date and time for the system to be set. The date and time is displayed on the LCD whilst the system is not in fault or fire.
  • Page 61: Configure Evacuate Timer

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 8-1-4 Configure Evacuate Timer Allows the evacuate timer to be enabled and the duration of the timer to be set. The evacuate timer runs in parallel to all other events. Once triggered it starts counting down, when it expires all sounders are activated.
  • Page 62: Two Devices To Evacuate

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 8-2-2 Call Points to Evacuate Enables or disables a system wide setting that a report of fire from a call-point automatically starts evacuation.
  • Page 63: Clear Non-Volatile Ram

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 8-3-2 Clear Non-Volatile RAM Clearing the NVRAM clears all the installation settings and the system is automatically put into Installation Mode. On the Panel this will result in: The Analogue Loop will be enabled All disabled Zones will be enabled...
  • Page 64: Other Features

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 8-4 Other Features These are programming functions that do not fall into any other category. 8-4-1 Active/Installation Mode An essential function. The system should always be left in ACTIVE mode, unless the system is being installed and debugged.
  • Page 65: The Pc Loader Software

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 The PC Loader Software ® The PC Loader software is runs under Windows (98, 98SE, Me, 2000 and XP). Communications to the panel is through one of the serial communication ports (COMM PORT) and in order to install it, the only requirement is to double click on the installer package supplied and follow the supplied instructions.
  • Page 66: Set User Access Code

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 8-4-4 Set User Access Code This function allows the installer to change the customer Access Code. Use pq to change code sequence. 8-4-5 Set User Functions Allows the user access level to be set for every programming function.
  • Page 67: Technical Specifications

    www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 TECHNICAL SPECIFICATIONS Please note that these specifications apply to the Junior Analogue Addressable panel, 1 or 2 loop models, equipped with a 2.4 Amp power supply @ 28.5V DC nominal. Weight Empty: 1.6 Kg Including sealed lead acid batteries:...
  • Page 68 www.acornfiresecurity.com Manufacturers of Fire Detection Equipment JUNIOR V4 - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - 06/2016 Maximum Continuous Primary Power Supply Rating 2.4 Amps @ 28,5 V DC nominal, comprising: 1 Amp max. temperature compensated, short circuit protected, battery charger.
  • Page 69 EN55022 class B, EN61000-4-22,3,4,5,6,8,11 EN61000-3-2,3 EN54-2 and EN54-4 We, Global Fire Equipment S.A. hereby declare, for the effects of the requirements laid down with EN54-4 paragraph 6.1, that the power supply equipment included in our analogue addressable fire alarm panel named JUNIOR, has been designed in accordance with a quality management system which incorporates a set of rules for the design of all elements of the p.s.e., and that its components have been selected for the intended purpose , and expected to...

This manual is also suitable for:

Junior v4Jnr-v4-1

Table of Contents