1RU form factor that helps reduce infrastructure and administrative costs. The S9301-32D is the epitome of future networking with a powerful 8-core processor and 32 high-speed 400GE interfaces. It comes with redundant, hot swappable components for convenience, increased availability, reliability and lower costs of maintenance.
Space Clearance: The S9301-32D width is 17.17 inches (43.6cm) and shipped with a rack mount brackets suitable for 19 inch (48.3cm) wide racks. The depth of the S9301-32D chassis is 25.4 inches (64.5cm) without the field replaceable units (FRUs) and comes with adjustable mounting rails suitable for rack depths of 20 inches (50.8cm) to 35 inches (88.9cm).
• Cooling: The S9301-32D has two options for airflow direction. There is a back-to-front option (Figure 3. Left) and a front-to-back option (Figure 3. Right). Make sure the equipment on the same rack have the same airflow direction. Back-to-Front Airflow Front-to-Back Airflow Figure 3.
AC power cord (AC version only) 0.77lbs (350g) RJ45 to DB9 female cable 0.23lbs (105g) S9301-32D (W x D x H) 17.17” x 25.4” x 1.72” (436 x 645 x 43.8mm) Dimension PSU (W x D x H) 1.99” x 12.64” x 1.57” (50.5 x 321 x 40mm) Fan module(W x D x H) 1.71”...
The DC power supply units are the same size for both back-to-front airflow and front-to-back airflow. Therefore, only the dimensions for front-to-back airflow PSU will be provided in the figure below. (Front-to-Back Airflow PSU) Figure 7. S9301-32D Hardware Installation Guide | 8...
The AC power supply units are the same size for both back-to-front airflow and front-to-back airflow. Therefore, only the dimensions for front-to-back airflow PSU will be provided in the figure below. (Front-to-Back Airflow PSU) Figure 9. S9301-32D Hardware Installation Guide | 9...
The picture on the bottom is for the fans with front-to-back airflow, identified with a red handle. (Back-to-Front Airflow Fans) (Front-to-Back Airflow Fans) Figure 10. Port Overview Port ID Form Factor Maximum Support Distance Support Speed 0 ~ 31 QSFP-DD 49.7mi (80km) 400G SFP+ 6.21mi (10km) 1/10G Figure 11. S9301-32D Hardware Installation Guide | 10...
Page 14
In a front-to-back or back-to-front airflow setup, you can mix and match ZR and OpenZR+ transceivers. Please noted if any OpenZR+ transceiver is used, you can only install up to 6 ZR/OpenZR+ transceivers to the S9301-32D. (See the figure below for the port configuration) Figure 13.
Page 15
Make sure the captive screw of the inner rail is positioned at the front of the chassis. 2.2 After the attachment pins are secured to the inner rail, lock the inner rail to the chassis using two M4 screws (one on each chassis side). See the figure below. S9301-32D Hardware Installation Guide | 12...
Page 16
3.2 Once the rear bracket is secured, pull back the clip of the front bracket attach it to the rack. An audible click can be heard when the bracket is secured onto the rack. Figure 18. S9301-32D Hardware Installation Guide | 13...
Page 17
4.4 Push the blue release tab on each rail to unlock the rails and slide the chassis all the way into the rack. 4.5 Lock the chassis into place by using the captive screw on the front of the inner rail. Figure 19. S9301-32D Hardware Installation Guide | 14...
4. Carefully slide the new fan module into the fan bay and gently push until it is flush with the case. 5. Secure the captive screw on the fan module to lock the fan in place. Figure 22. S9301-32D Hardware Installation Guide | 15...
1. Locate the release tab on the PSU. Then press and hold down the release tab to unlock the PSU from the power bay. 2. While holding down the release tab, grip the PSU's handle and firmly pull it out of the power bay. DC Version: AC Version: Figure 24. S9301-32D Hardware Installation Guide | 16...
Page 20
5. An audible click will be heard when the PSU is installed correctly. The PSU will not go in all the way if it is in the wrong direction. Illustrations are for reference purposes only. Actual PSU position may differ. DC Version: AC Version: Figure 25. S9301-32D Hardware Installation Guide | 17...
4. Using a crimping tool, firmly secure the grounding wire to the grounding lug. Figure 26. 5. Locate the designated location for securing the grounding lug, which is located on the side of S9301-32D Hardware Installation Guide | 18...
Page 22
Figure 27. 6. Using 2 M4 screws and 2 washers (provided with the package contents), firmly lock the grounding lug to either of the designated grounding locations on the router. Figure 28. S9301-32D Hardware Installation Guide | 19...
Also, please ensure that both PSUs have been properly installed before powering up the equipment, as the S9301-32D is designed to support 1 + 1 power redundancy. 2. Attach the DC power cables to the lugs.
Page 24
3. Attach the power cable. Locate the DC power screw-type terminal block located on the PSU. Remove the plastic cover that is protecting the terminal block by pushing from the top or bottom of the cover and S9301-32D Hardware Installation Guide | 21...
Page 25
6. Verify that the power supply is operating. If connected correctly, when turned on, the LED on the PSU will light up with a Green color designating normal operation. S9301-32D Hardware Installation Guide | 22...
If connected correctly, when turned on, the LED on the PSU will light up with a solid Green color designating normal operation. If only a 110V AC power source is available, the S9301-32D can still be powered with both PSUs providing 1000 watts each for a total output of 2000 watts.
PSU0 working normal Blinking Amber PSU0 fail (PSU0 needs service) PSU1 No power Solid Green PSU1 working normal Blinking Amber PSU1 fail (PSU1 needs service) No Power Blinking Blue Beacon feature is enabled on the switch S9301-32D Hardware Installation Guide | 24...
Fan is abnormal, service is required Management Port LED LED Condition Equipment Status Left LED No power Solid Green 1G link-up Blinking Green 1G TX/RX activity Right LED No power Solid Amber 10M/100M link-up Blinking Amber 10M/100M TX/RX activity S9301-32D Hardware Installation Guide | 25...
After the connection is established, a prompt for the username and password displays. Enter the username and password to access the CLI. The username and password should be provided by the Network Operating System (NOS) vendor. S9301-32D Hardware Installation Guide | 26...
There are two types of OOB management ports that can both access the x86 for management purposes. 1. The first port type is the RJ45 OOB port marked a symbol. 2. The second port type is the two 10G SFP+ ports also marked with a symbol. Figure 37. S9301-32D Hardware Installation Guide | 27...
3. Place the bail (wire handle) in the unlocked position and align the transceiver with the port. 4. Slide the transceiver into the port and use gentle pressure to secure it in place. An audible click can be heard when the transceiver is secured in the port. S9301-32D Hardware Installation Guide | 28...
Page 32
The equipment and its modules should only be repaired, maintained or replaced by skilled personnel. Instructed person is a term applied to persons who have been instructed and trained by a skilled person, or who is supervised by a skilled person. <電源コードセットに関する使用上の注意事項> 付属の「AC電源コードセット」は、本製品専用のものです。他の電気機器には絶 対に使用しないでください。 S9301-32D Hardware Installation Guide | 29...
Page 33
VCCI Notice This is Class A equipment. Operation of this equipment in a residential environment could cause radio interference. In such a case, the user may be required to take corrective actions. S9301-32D Hardware Installation Guide | 30...