Panasonic S-15MM1E5B Installation Instructions Manual
Panasonic S-15MM1E5B Installation Instructions Manual

Panasonic S-15MM1E5B Installation Instructions Manual

Slim low static ducted
Hide thumbs Also See for S-15MM1E5B:

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
Air Conditioner
This air conditioner uses the refrigerant R32 or R410A.
Model No.
Indoor Units
Rated Capacity
Type
Indoor Units Type
15
22
28
36
45
56
M1
Slim Low Static Ducted S-15MM1E5B S-22MM1E5B S-28MM1E5B S-36MM1E5B S-45MM1E5B S-56MM1E5B
ENGLISH
Read through the Installation Instructions before you proceed with the installation.
In particular, you will need to read under the "IMPORTANT!" section at the top of the page.
WEB-ACXF60-41580-EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S-15MM1E5B and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Panasonic S-15MM1E5B

  • Page 1 Rated Capacity Type Indoor Units Type Slim Low Static Ducted S-15MM1E5B S-22MM1E5B S-28MM1E5B S-36MM1E5B S-45MM1E5B S-56MM1E5B ENGLISH Read through the Installation Instructions before you proceed with the installation. In particular, you will need to read under the “IMPORTANT!” section at the top of the page.
  • Page 2: Important

    IMPORTANT! This symbol refers to a hazard or WARNING Please Read Before Starting unsafe practice which can result in severe personal injury or death. This air conditioner must be installed by the sales dealer This symbol refers to a hazard or or installer.
  • Page 3 • Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death. • Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
  • Page 4 …In a Room Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors. CAUTION Keep the fire alarm and the air outlet at least 1.5 m away from the unit. …In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit.
  • Page 5 • Electronic leak detectors may be used to detect refrigerant leaks but, the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) • Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
  • Page 6 CAUTION • Ventilate any enclosed areas when installing or testing the refrigeration system. Leaked refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas. • Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation toxic gas and fire.
  • Page 7 SERVICING CAUTION • Any qualified person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification. •...
  • Page 8 Marking to the equipment continues to be visible and legible. Markings and signs • that are illegible shall be corrected. Refrigerating pipe or components are installed in a position where they are • unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
  • Page 9 REMOVAL AND EVACUATION CAUTION • When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: Remove refrigerant.
  • Page 10 Recovery equipment and cylinders conform to the appropriate standards. • d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with instructions.
  • Page 11: Check Of Density Limit

    Check of Density Limit Check the amount of refrigerant in the system and floor space of the room according to the legislation on refrigerant drainage. If there is no applicable legislation, follow the standards described below. The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for the maximum refrigerant charge amount [m ] used in the appliance are determined according to installation space of the appliance.
  • Page 12 < Whether or not to use R32 refrigerant leakage detection sensor > • According to the type of diagrams shown in Fig. 2, it is necessary to install R32 refrigerant leakage detection sensor if the installation space is within the range of using R32 refrigerant leakage detection sensor.
  • Page 13 Fig. 2 Slim Low Static Ducted When connecting the duct to either inlet side or outlet side Installed on top of drop ceiling Installed on top of drop ceiling Inside of a room Inside of a room inst inst inst inst : Floor area of the room (m When not partitioning : Calculate from A...
  • Page 14 Type 15, 22, 28, 36, 45, 56 ≥ 2.2 inst 20.0 U-8LZ2E8, U-10LZ2E8 15.0 Nonuse of R32 refrigerant leakage detection sensor 10.0 U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Floor area of the room (m 1.8 ≤ h < 2.2 inst 20.0 15.0 Nonuse of R32 refrigerant leakage detection sensor...
  • Page 15 Slim Low Static Ducted Concealed Ceiling When connecting the duct to either inlet side or outlet side ≥ 2.2 1.8 ≤ h < 2.2 inst inst Use or nonuse of R32 refrigerant leakage Nonuse Nonuse detection sensor 15~56 15~56 Capacity of indoor unit Refrigerant charge amount (kg) 10.0 10.2...
  • Page 16 Slim Low Static Ducted Concealed Ceiling When connecting the duct to either inlet side or outlet side ≥ 2.2 1.8 ≤ h < 2.2 inst inst Use or nonuse of R32 refrigerant leakage Nonuse Nonuse detection sensor 15~56 15~56 Capacity of indoor unit Refrigerant charge amount (kg) 10.6 10.8...
  • Page 17 Fig. 2 Slim Low Static Ducted When not connecting the duct to either the inlet side or outlet side Inside of a room Installed on top of drop ceiling Inside of a room inst inst inst inst : Floor area of the room (m When not partitioning : Calculate from A and h inst...
  • Page 18 Type 15, 22 ≥ 2.2 inst 20.0 U-8LZ2E8, U-10LZ2E8 15.0 Use of R32 refrigerant leakage detection sensor 10.0 U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32 refrigerant leakage detection sensor Floor area of the room (m 1.8 ≤ h <...
  • Page 19 Type 28 ≥ 2.2 inst 20.0 U-8LZ2E8, U-10LZ2E8 15.0 Use of R32 refrigerant leakage detection sensor 10.0 U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32 refrigerant leakage detection sensor Floor area of the room (m 1.8 ≤ h < 2.2 inst 20.0 15.0...
  • Page 20 Type 36 ≥ 2.2 inst 20.0 U-8LZ2E8, U-10LZ2E8 15.0 Use of R32 refrigerant leakage detection sensor 10.0 U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32 refrigerant leakage detection sensor Floor area of the room (m 1.8 ≤ h < 2.2 inst 20.0 15.0...
  • Page 21 Type 45 ≥ 2.2 inst 20.0 U-8LZ2E8, U-10LZ2E8 15.0 Use of R32 refrigerant leakage detection sensor 10.0 U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32 refrigerant leakage detection sensor Floor area of the room (m 1.8 ≤ h < 2.2 inst 20.0 15.0...
  • Page 22 Type 56 ≥ 2.2 inst 20.0 U-8LZ2E8, U-10LZ2E8 15.0 Use of R32 refrigerant leakage detection sensor 10.0 U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32 refrigerant leakage detection sensor Floor area of the room (m 1.8 ≤ h < 2.2 inst 20.0 15.0...
  • Page 23 Slim Low Static Ducted Concealed Ceiling When not connecting the duct to either the inlet side or outlet side ≥ 2.2 1.8 ≤ h < 2.2 inst inst Use or nonuse of R32 refrigerant leakage Nonuse Nonuse detection sensor 15~ 56 15, 22 15~56 15, 22...
  • Page 24 Slim Low Static Ducted Concealed Ceiling When not connecting the duct to either the inlet side or outlet side ≥ 2.2 1.8 ≤ h < 2.2 inst inst Use or nonuse of R32 refrigerant leakage Nonuse Nonuse detection sensor 15~ 56 15, 22 15~56 15, 22...
  • Page 25: Table Of Contents

    CONTENTS Page Page IMPORTANT ......2 7. HOW TO INSTALL WIRELESS REMOTE CONTROLLER ....48 Please Read Before Starting Check of Density Limit NOT E...
  • Page 26: General

    1. GENERAL This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. The installation of pipe-work shall be kept to a minimum.
  • Page 27: Type Of Copper Tube And Insulation Material

    1-3. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source, you will need: Deoxidized annealed copper tube for refrigerant tubing. Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm.
  • Page 28: Site

    2. SELECTING THE INSTALLATION SITE 2-1. Indoor Unit AVOID: ● areas where leakage of flammable gas may be expected. ● places where large amounts of oil mist exist. ● direct sunlight. ● locations near heat sources which may affect the performance of the unit. ●...
  • Page 29 Installation location of R32 refrigerant leakage detection sensor When installing R32 refrigerant leakage detection sensor away from the indoor unit, place it at 300 mm or less from a floor surface and satisfy the condition either (1) or (2) below. (1) If no obstacles exist in a straight line from R32 refrigerant leakage detection sensor to the indoor unit, wall distance should be within 10 m in horizontal straight line.
  • Page 30: How To Install The Indoor Unit

    3. HOW TO INSTALL THE INDOOR UNIT 3-1. Required Minimum Space for Installation and Maintenance Services ● This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below. ●...
  • Page 31 ● The diagram shows the detailed dimensions of the indoor unit. a) Refrigerant tubing joint (liquid tube) b) Refrigerant tubing joint (gas tube) c) Upper and bottom drain port (O.D.26 mm) d) Suspension lug e) Power supply outlet (ø17 mm) f ) Flange for air outlet duct g) Cover plate h) Electrical component box...
  • Page 32: Preparations Before Installation

    3-2. Preparation Before Installation (1) Confirm the positional relationship between the unit and suspension bolts. ● Install the inspection opening on the Air discharge Air intake control box side where maintenance and inspection of the control box and drain pump are easy. Install the inspection Drop ceiling opening also in the lower part of the unit.
  • Page 33: For Bottom Intake

    3-3. For Bottom Intake For bottom intake, replace the cover plate and frame filter assy net in the procedure shown in the diagram. (1) Remove the frame filter assy. Remove the cover plate. Air intake Frame filter assy Cover plate Air discharge Dummy hole (2) Refer to the diagram to attach the cover plate and frame filter assy in the direction of the...
  • Page 34: Installing The Duct

    3-4. Installing the Duct Connecting to the duct in case of connecting to the indoor unit using R32 refrigerant. Connect the duct supplied in the field as shown in the diagram. Flange (field supply) Flange Connection screw (× 10) Insulation material (field supply) Main unit Rectangular solid duct (field supply)
  • Page 35: Suspending The Indoor Unit

    3-5. Suspending the Indoor Unit Depending on the ceiling type: a) Insert suspension bolts. b) Use existing ceiling supports or construct a suitable support. Hole-in-anchor Concrete Insert Hole-in-plug Ceiling tiles Ceiling support Suspension bolt (M10 or 3/8”) (field supply) WARNING It is important that you use extreme care in supporting the indoor unit inside the ceiling.
  • Page 36: Installing The Drain Pipe

    Level Vinyl hose (6) Tighten the upper nut. 3-6. Installing the Drain Pipe (1) Prepare standard hard PVC pipe (O.D. 26 mm) for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage.
  • Page 37 CAUTION ● Do not install an air bleeder as this may cause water to spray from the drain pipe outlet. Air bleeder Prohibited ● Make sure that the drain port is not a downward gradient from the joint section (may lead to abnormal noise).
  • Page 38: Checking The Drainage

    3-7. Checking the Drainage After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water. (1) Connect power to the power terminal board (L, N terminals) inside the electrical component box.
  • Page 39: Electrical Wiring

    4. ELECTRICAL WIRING 4-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram under Section 4-3. WARNING (2) This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
  • Page 40: Wire Length And Wire Diameter For Power Supply System

    4-2. Wire Length and Wire Diameter for Power Supply System Indoor unit (B) Power supply cable Type Time delay fuse or circuit capacity Min. 2.5 mm Max. 130 m * 15 A Control wiring (C) Inter-unit (between outdoor and (E) Remote control wiring for group (D) Remote control wiring indoor units) control wiring control...
  • Page 41: Wiring System Diagrams

    4-3. Wiring System Diagrams ex.) Indoor unit Outdoor unit : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 (No. 1) Power supply Power supply 220-230-240V~ 50Hz 220-230-240V~ 50-60Hz Ground Ground Remote controller ex.) Indoor unit Outdoor unit : U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 (No. 2) Power supply Power supply 220-230-240V~ 50-60Hz 380-400-415V 3N~ 50Hz...
  • Page 42 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug.
  • Page 43 WARNING Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also occur. Therefore, ensure that all wiring is tightly connected. When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal”...
  • Page 44 ■ Wiring samples Clamper inside the box for remote control wiring and inter-unit control wiring R32 refrigerant leakage Inter-unit control wiring detection sensor wiring Power cable Earth wiring: Make the earth wiring Remote control wiring 25 - 30 mm longer than power cable. Clamping clip Use this screw when connecting the shield for the inter-unit control wiring to ground.
  • Page 45: How To Process Tubing

    5. HOW TO PROCESS TUBING Must ensure mechanical connections be accessible for maintenance purposes. 5-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes that run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
  • Page 46: Connecting Tubing Between Indoor And Outdoor Units

    5-2. Connecting Tubing Between Indoor and Outdoor Units N OTE When connecting to the mini VRF 8HP, 10HP (outdoor units type LE1 only), select the main tube by using the following values. For details, refer to the installation instructions of the outdoor unit. Indoor unit Type M1 0.098...
  • Page 47: Insulating The Refrigerant Tubing

    5-3. Insulating the Refrigerant Tubing Tubing Insulation Must ensure that pipe-work shall be protected from physical damage. ● Thermal insulation must be applied to all units tubing, Two tubes arranged together including distribution joint (field supply). * For gas tubing, the insulation material must be heat Liquid tube Gas tube resistant to 120°C or above.
  • Page 48: Taping The Tubes

    N OTE If noise bothers you from the area between indoor and outdoor units’ connection pipes, it is effective to wind the soundproofing materials (field supply) to reduce noise. CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
  • Page 49: Checklist After Installation

    8. CHECKLIST AFTER INSTALLATION WORK □ Work List Content Check Possibility of Failure & Checkpoint Are the indoor units installed following the □ There is a possibility of light injure or loss of Installation content of Section “2. SELECTING THE property.
  • Page 50: External Static Pressure

    9. EXTERNAL STATIC PRESSURE SETTING Choose one of the following methods from “a”, “b”, “c” as shown in the flow chart (within the dotted lines) and then make the setting accordingly. a. No setting modification: When using as it is factory preset at shipment. (If resetting after external static pressure setting once, it might be different from factory preset.) b.
  • Page 51: How To Set On Indoor Unit Control Pcb

    CAUTION ● Make sure the external static pressure is in a range of specifications. Then proceed the external static pressure setting. Improper settings can cause noise, a shortage of airflow volume and water leakage. See Fig. 9-2 for the external static pressure setting range.
  • Page 52: Operating The High-Spec Wired Remote Controller (Cz-Rtc5B)

    9-2. Operating the High-spec Wired Remote Controller (CZ-RTC5B) How to set the external static pressure 1. Keep pressing the buttons 20:30 (THU) simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the LCD display. START Maintenance func 20:30 (THU) 1.
  • Page 53: Operating The Timer Remote Controller (Cz-Rtc4)

    9-3. Operating the Timer Remote Controller (CZ-RTC4) How to set the external static pressure 1. Press and hold down the buttons simultaneously for 4 or more seconds. ° , the unit no., item code and detailed data ° will blink on the LCD display.) 2.
  • Page 54 9-4. Operating the Wired Remote Controller (CZ-RTC6 series) Stop the system before performing these steps. How to set the external static pressure 1. Keep pressing the buttons simultaneously for 4 or more seconds. The “Main tenance func” screen appears on the LCD display.
  • Page 55 External static pressure’s upper limit in high static pressure mode Standard external static pressure’s upper limit Rated external static pressure in high static pressure mode Lower static pressure in high static pressure mode Rated external static pressure at shipment Lower limit airflow Upper limit airflow Airflow (m³/min.) Type 15...
  • Page 56: Operating The Wired Remote Controller (Cz-Rtc6 Series)

    10. APPENDIX ■ Care and Cleaning WARNING ● For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning. ● Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
  • Page 57 N OT E The frequency with which the filter should be cleaned depends on the environment in which the unit is used. Clean the filter frequently for best performance in the area of dusty or oil spots regardless of filter status. <How to clean the filter>...
  • Page 58 ■ Troubleshooting If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. ● Indoor unit Symptom Cause Noise Sound like streaming water during ●...
  • Page 59 ● Check Before Requiring Services Symptom Cause Remedy Air conditioner does not run Power failure or after power failure Press ON/OFF operation button on remote at all although power is turned controller again. Operation button is turned off. ● Switch on power if breaker is turned off. ●...
  • Page 60 ■ Tips for Energy Saving Avoid ● Do not block the air intake and outlet of the unit. If either is obstructed, the unit will not work well, and may be damaged. ● Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls and ceiling of the room are warmed by the sun, it will take longer to cool the room.
  • Page 61 WEB-ACXF60-41580-EN DC0121-0...

This manual is also suitable for:

S-22mm1e5bS-28mm1e5bS-36mm1e5bS-45mm1e5bS-56mm1e5b

Table of Contents