PLC extension module User manual Wuxi XINJE Electric Co., Ltd. Data No. PF 02 20230906 1.0...
Page 3
Basic description Thank you for purchasing the XINJE XF series programmable controller and extension module. This manual mainly introduces the hardware features of XF series extension module. Before using the product, please read this manual carefully and conduct wiring on the premise of fully understanding the contents of the manual.
Safety precautions The problems that may arise during the use of the product are basically included in the safety precautions, which are indicated in two levels of attention and danger. For other unfinished matters, please follow the basic electrical operation procedures. When used incorrectly, it may cause danger, moderate injury or minor Attension injury, and property damage.
Page 5
2. Do not directly touch the conductive part of the product. It may cause malfunction and fault. 3. Please use DIN46277 guide rail, M3 screw or Xinje XG-EB to fix the product and install it on a flat surface. Incorrect installation may cause malfunction and product damage.
Page 6
3. Do not make external wiring to the empty terminal. It may cause malfunction and product damage. 4. When processing the screw hole, please do not let the cutting powder and wire debris fall into the product cover. May cause malfunction, fault, etc. 5.
Page 7
9. Do not use ink to write on the device in the area shown in the picture. This may cause a malfunction.
Page 8
Preface Sincerely thank you for purchasing the XINJE Programmable Controller XF-IO series products. This manual is convenient for users to understand and use the necessary precautions, specifications, functions, and other contents of XF-IO units. Before use, one should thoroughly read this manual and related manuals, and correctly use this product based on a thorough understanding of the functions/performance of the XF-IO series extension module.
XS series PLCopen controller It mainly records XS series instruction section. instruction manual (XS Studio) (2) I/O unit Manual name Main content XF Series expansion module user It mainly records the product specifications and maintenance manual information of the XF series IO unit.
CPU unit General term for XF/XSF series CPU units Power module unit General term for XF series power modules Protection level according to DIN 40050: protection against finger contact IP20 and intrusion of particles with a diameter greater than 12mm The backplane bus is a serial data bus used by various modules to communicate with each other.
3. Product System Configuration In this chapter, the overall configuration, precautions during configuration, and peripheral device related content are explained. 3-1. Overall configuration 3-2. Major event Different CPU units are used, and the corresponding expandable IO units are also different. ...
Module version: Hardware version Function Basic functions first official H2.0 production 4-2. Naming rules Series Name XF series extension module ① Extension module Right extension module ② Module Type Power module ③ Output power Output power 35W ④ AC Input Input Type ⑤...
(2) System indicator light System indicator light Meaning Extinguish No input power supply Normally ON The input power of the power module is normal and (green) provides power to the CPU unit normally Normally ON The input power of the power module is normal, but (red) the power supply to the CPU unit is abnormal 4-4.
Project Specification Type XF-P35-E Power Input power Input AC100~240V 50/60Hz Protective grounding for equipment and operators (in LG - Protective grounding accordance with the functional protection part of IEC 61131-2 and GB/T 15969.2 standards) Functional grounding terminals, i.e. grounding functions used safety purposes, such...
4-6-2. Installation method The module is installed using DIN rails, which must comply with the IEC 60715 standard (35mm wide and 1mm thick). The size information is shown in the following figure, in millimeters (mm). When the module is installed on a non recommended Attention DIN rail as mentioned above, the DIN rail latch may not lock properly.
5. Digital quantity module unit 5-1. Naming convention ① Series Name XF: XF series extension module ② Extension module E: Right extension module 4: 4 channels 8: 8 channels ③ Input channel 16: 16 channels 32: 32 channels 64: 64 channels Empty: Digital input PNP and NPN type ④...
Module version: Hardware version Software version Function H2.0 V2.0 Basic functions for the first official production 5-2-2. Module view (1) Description of each section Number Name System LED indicator light ① Channel LED indicator light ② Detachable terminal block ③ Clasp ④...
(3) Channel indicator light Model Channel indicator light Corresponding input channel has input Normally ON(green) ON signal XF-E16X X0~X17 Corresponding input channel has no Extinguish input ON signal (4) Color identification Number Color Module Type White Digital input Gray Digital output and digital mixing module Light blue Analog input Dark Blue...
5-2-4. Technical specification Project Specification Input points Rated input voltage DC24V Rated input current Input ON voltage Input ON current 2.5mA Input OFF voltage Input OFF current Input resistance ON → OFF 20us response time (hardware) Input resistance OFF → ON 100us response time (hardware) Derate by 75% when operating at 60 ℃...
Page 22
5-2-5-2 Terminal Definition&Wiring Terminal Definition XF-E16X Meaning A-list terminal Terminal layout B-list terminal Meaning CH10 CH11 CH12 CH13 CH14 CH15 External wiring Number Name System indicator light ① Channel indicator light ② Backplane bus ③ Input Channel&Wiring ④...
Page 23
5-2-5-3 Installation method (1) Installation demand The module is installed using DIN rails, which must comply with the IEC 60715 standard (35mm wide and 1mm thick). The size information is shown in the following figure, in millimeters (mm). When the module is installed on a non recommended Attention DIN rail as mentioned above, the DIN rail latch may not lock properly.
Page 24
(3) Disassemble steps Use a slotted screwdriver or similar tool to pry the rail Slotted screwdriver 一字螺丝刀 latch upwards. DIN guideway As shown in the left figure: DIN轨道锁扣 lock catch Buckle position 扣手位置 Pull the module straight forward at the buckle position (raised part), and press down on the top of the latch after completion.
5-2-5-5 Installation environment When wiring a module, its terminal must meet the following requirements: Suitable cable diameter Chinese standard/mm American Standard/AWG 0.75 If using other tube type wire lugs, please crimp them to the stranded wire, and the shape and size requirements are shown in the following figure: 5-2-6.
Channel logic level The "Logic Level Configuration" corresponds to a separate logic level configuration for each channel. The setting method is to select parameters from the drop-down menu. The program execution logic after external signal input. External Logic level Run program Operation result input signal...
5-3-1. Product overview XF-E16YT series digital output expansion module, which has 16 channels of digital output and supports NPN output, and is suitable for XF, XSF series CPU unit products and XF series communication coupler units. 16 channels digital output;...
5-3-2. Module view (1) Description of each section Number Name System LED indicator light ① Channel LED indicator light ② Detachable terminal block ③ Clasp ④ Signal indication ⑤ Color identification indicating ⑥ module type Module hardware and software ⑦ versions Wiring diagram ⑧...
(3) Channel indicator light Model Channel indicator light Corresponding input channel has Normally ON(green) input ON signal XF-E16YT Y0~Y17 Corresponding input channel has Extinguish no input ON signal (4) Color identification Number Color Module Type White Digital input Gray Digital output and digital mixing module Light blue Analog input Dark Blue...
5-3-4. Technical specification Project Specification Output points Rated load voltage DC24V(DC10.2V~28.8V) Maximum load current 0.5A/1 port, 4A/module Surge current protection support Leakage current at OFF Below 0.1mA Maximum voltage drop at ON 0.5V~1V Output ON → OFF response 0.1ms time (hardware) Output OFF →...
Page 32
5-3-5-2 Terminal Definition&Wiring Terminal Definition XF-E16YT Meaning A-list terminal Terminal layout B-list terminal Meaning CH10 CH11 CH12 CH13 CH14 CH15 24V+ External wiring Number Name System indicator light ① Channel indicator light ② Backplane bus ③ Input Channel&Wiring ④...
Page 33
5-2-5-3 Installation method (1) Installation demand The module is installed using DIN rails, which must comply with the IEC 60715 standard (35mm wide and 1mm thick). The size information is shown in the following figure, in millimeters (mm). When the module is installed on a non recommended Attention DIN rail as mentioned above, the DIN rail latch may not lock properly.
Page 34
(3) Disassemble steps Use a slotted screwdriver or similar tool to pry the rail Slotted screwdriver 一字螺丝刀 latch upwards. DIN guideway As shown in the left figure: DIN轨道锁扣 lock catch Buckle position 扣手位置 Pull the module straight forward at the buckle position (raised part), and press down on the top of the latch after completion.
5-3-5-5 Installation environment When wiring a module, its terminal must meet the following requirements: Suitable cable diameter Chinese standard/mm2 American Standard/AWG 0.75 If using other tube type wire lugs, please crimp them to the stranded wire, and the shape and size requirements are shown in the following figure: 5-3-6.
Channel logic level The "Logic Level Configuration" corresponds to a separate logic level configuration for each channel. The setting method is to select parameters from the drop-down menu. The following table pulling method reflects the parameters Settable parameters that can be set: positive logic, negative logic The program execution logic after external signal input.
XF-E8NX8YT series digital input output hybrid expansion module, which has 8 channels of digital input, 8 channels of digital output and supports NPN input and output, and is suitable for XF, XSF series CPU unit products and XF series communication coupler units. 8 channels digital input;...
5-4-2. Module view (1) Description of each section Number Name System LED indicator light ① Channel LED indicator light ② Detachable terminal block ③ Clasp ④ Signal indication ⑤ Color identification indicating ⑥ module type Module hardware and software ⑦ versions Wiring diagram ⑧...
(3) Channel indicator light Model Channel indicator light Corresponding input channel has Normally ON(green) input ON signal X0-X7 XF-E8NX8YT Y0-Y7 Corresponding input channel has Extinguish no input ON signal (4) Color identification Number Color Module Type White Digital input Gray Digital output and digital mixing module Light blue Analog input...
5-4-4. Technical specification Project Specification Input channel Input type Rated input voltage DC24V Rated input current Input ON voltage Input ON current Input OFF voltage Input Input OFF current specifications Derate by 50% when operating at 55 ℃ Input derating (with no more than 4 ON input points), or by 10 ℃...
Page 43
External wiring Number Name System indicator light ① Channel indicator light ② Backplane bus ③ Input Channel&Wiring ④ Output Channel&Wiring ⑤ 5-4-5-3 Installation method (1) Installation demand The module is installed using DIN rails, which must comply with the IEC 60715 standard (35mm wide and 1mm thick).
Page 44
The module is installed on the guide rail. When installing, align the module with the DIN guide rail and press the module in the direction indicated by the arrow. After installation, there is a noticeable clicking sound As shown in the left figure: Explanation: After module installation...
Page 45
5-4-5-4 Installation environment This product can be installed in four positions (installation direction): horizontal direction, vertical direction, top of the cabinet, and bottom of the cabinet. It is recommended to install in the horizontal direction. The heat dissipation design is through natural convection, to ensure normal ventilation and heat dissipation, and to reserve sufficient wiring space, the minimum gap must be left around this product, as shown in the following figure: If there are high-temperature heat source equipment (heaters, transformers,...
5-4-6. Parameters and mapping addresses Name Type Description 8 channels input and 8 channels XF_E8X8Y Stuct output module BOOL Channel 0 input value BOOL Channel 1 input value BOOL Channel 2 input value BOOL Channel 3 input value BOOL Channel 4 input value BOOL Channel 5 input value BOOL...
Error code parameters: Module level error codes(ErrCode_module) Meaning Error level Internal module error occurred and cannot be repaired by the user layer. Important 5-4-7. Functions and Settings Channel input filtering time Each channel of "filtering time" corresponds to a separate filtering parameter, and the setting method is to select the parameter from the drop-down menu.
Channel logic level The "Logic Level Configuration" corresponds to a separate logic level configuration for each channel. The setting method is to select parameters from the drop-down menu. The following table pulling method reflects the parameters Settable parameters that can be set: positive logic, negative logic The program execution logic after external signal input.
6. Analog module unit 6-1. Naming rules ① Series Name XF series extension module ② Extension module E: Right extension module 1 channel 2 channels ③ Input channel 4 channels 6 channels 8 channels ④ Type Analog voltage and current input...
12mm width design Module version: Hardware version Software version Function H2.0 V2.0 Basic functions for the first official production 6-2-2. Module view (1) Description of each section Number Name System LED indicator light ① Channel LED indicator light ② Detachable terminal block ③...
(3) Channel indicator light Model Channel indicator light Corresponding input channel has Normally ON(green) input ON signal XF-E4AD CH0~CH3 Corresponding input channel has Extinguish no input ON signal (4) Color identification Number Color Module Type White Digital input Gray Digital output and digital mixing module Light blue Analog input Dark Blue...
6-2-4. Technical specification 6-2-4-1. Module performance Project Specification Input channel 0V~5V (0~64000) 0V~10V (0~64000) Voltage Input range -5V~5V (-32000~32000) -10V~10V (-32000~32000) Analog input 1V~5V (12800~64000) range (rated) 0mA~20mA (0~64000) Current Input range 4mA~20mA (12800~64000) -20mA~20mA (-32000~32000) Maximum Voltage input DC±15V input range Current input -40~40mA...
1V~5V analog input Current 0mA~20mA analog input -20mA~20mA analog input 4mA~20mA analog input 6-2-5. Installation&Wiring 6-2-5-1 Apparent dimension 80.1 87.84...
Page 54
6-2-5-2 Terminal Definition&Wiring Terminal Definition XF-E4AD A-list Terminal B-list Meaning Meaning terminal layout terminal Input grounding Input grounding Analog voltage Analog voltage input terminal input terminal Analog current Analog current input terminal input terminal Input grounding Input grounding Analog voltage Analog voltage input terminal input terminal...
Page 55
6-2-5-3 Installation method (1) Installation demand The module is installed using DIN rails, which must comply with the IEC 60715 standard (35mm wide and 1mm thick). The size information is shown in the following figure, in millimeters (mm). When the module is installed on a non recommended Attention DIN rail as mentioned above, the DIN rail latch may 35±0.3...
Page 56
(3) Disassemble steps Use a slotted screwdriver or similar tool to pry the rail Slotted screwdriver 一字螺丝刀 latch upwards. DIN guideway As shown in the left figure: DIN轨道锁扣 lock catch Buckle position 扣手位置 Pull the module straight forward at the buckle position (raised part), and press down on the top of the latch after completion.
6-2-5-5 Installation environment When wiring a module, its terminal must meet the following requirements: Suitable cable diameter Chinese standard/mm2 American Standard/AWG 0.75 If using other tube type wire lugs, please crimp them to the stranded wire, and the shape and size requirements are shown in the following figure: 6-2-6.
Module level error codes(ErrCode_module) Meaning Error level Channel 1 upper limit overflow. Normal Channel 1 low limit overflow. Normal Channel 1 disconnected. Important Reserve Channel 2 upper limit overflow. Normal Channel 2 low limit overflow. Normal Channel 2 disconnected. Important Reserve Channel 3 upper limit overflow.
Page 59
The following table pulling method reflects the parameters that Settable parameters can be set: voltage, current Default parameters Voltage 0V~5V, 0V~10V, -5V~5V, -10V~10V, 1V~5V Voltage measurement range Default: 0V~10V Current measurement range 0mA~20mA, 4mA~20mA, -20mA~20mA Module power detection Check whether the external power supply 24V of the module is normal: ...
Page 60
Calibration function Due to the possibility of drift between the analog output converted from DA and the set digital output after the product leaves the factory or has been in use for a period of time, customers can immediately reflect it to the proportional scaling value (digital operation value) by setting the DA offset calibration function, and can easily complete the calibration at system startup on their own.
Unit display conversion This function can directly display the output analog data as the actual output unit required by the customer. Due to the customer's use of analog expansion module DA, the basic output is to provide analog quantities corresponding to the outputs of some instruments or sensors; For example, controlling a frequency output range of 0~50Hz for a frequency converter and controlling an analog signal of 4~20mA for frequency control.
Page 62
Input filtering time setting 5ms Select the filtering time for channel 0; Select 5ms.
Page 63
WUXI XINJE ELECTRIC CO., LTD. No.816, Jianzhu West Road, Binhu District, Wuxi City, Jiangsu Province, China 214072 Tel: 400-885-0136 Fax: (510) 85111290 www.xinje.com...