Emicon RAC Series Use And Maintenance Manual

Emicon RAC Series Use And Maintenance Manual

Air cooled water chillers with turbocor compressors (oil free)
Table of Contents

Advertisement

Quick Links

R A C
AIR COOLED WATER CHILLERS
WITH
TURBOCOR COMPRESSORS
(OIL FREE)
USE AND MAINTENANCE MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Emicon RAC Series

  • Page 1 R A C AIR COOLED WATER CHILLERS WITH TURBOCOR COMPRESSORS (OIL FREE) USE AND MAINTENANCE MANUAL...
  • Page 2 RAC – Use and Maintenance Manual ev. 4 10/18) Emicon A.C. S.p.A. reserves the right to modify at any time this manual without any prior notice. EMICON A.C. S.P.A. Pag. 2 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 3: Table Of Contents

    Evaporator ..................... 21 2.2.3. Evaporator’s liquid level ................. 21 2.2.4. Condenser coil ....................22 2.2.5. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 3 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 4 Electric connections ..................38 Power supply connection ................39 3.6.1. User’s terminal board connection ..............40 3.6.2. EMICON A.C. S.P.A. Pag. 4 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 5 Checking the safety devices to avoid electric overcharges ......56 5.2.5. Checking the switches ................... 56 5.2.6. 5.3. Troubleshooting ....................56 EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 5 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 6 Alarm table ..................... 85 7.6.3. Main alarms description ................. 86 7.6.4. 7.7. Parameters ......................93 EMICON A.C. S.P.A. Pag. 6 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 7 RAC – Use and Maintenance Manual ev. 4 10/18) Refrigerant safety data sheet ............95 EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 7 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 8 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. Pag. 8 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 9: Introduction

    • 97/23/CE (PED), • 2004/108/CE (Electromagnetic Compatibility), • 2006/42/CE (Machinery Directive), • 2006/95/CE (Low Voltage Directive). EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 9 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 10: Identification Tag

    Max design temperature Design pressure Min. design temperature Max. deign temperature Setting of safety device Pag. 10 EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 11: Warranty

    On the first start-up, it is necessary duly fill in the relevant report attached to this manual and send a copy to Emicon A.C. (Customer Service), in order to make the warranty valid. 1.6.
  • Page 12: Dangerous Areas

    Service personnel must use a commercially available service kit for handling static-sensitive devices. The kit typically includes: Ground cord Assembly • Alligator clip • Grounding wrist strap • EMICON A.C. S.P.A. Pag. 12 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 13: Electrical Isolation Of The Compressor

    In particular, be careful with the CE type covers because they are coated on the outside for the purpose of being conductive. The painted covers only apply to TT300P and TT300C. 3) Remove the Mains Input cover. See Figure 1. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 13 tel.
  • Page 14: Esd Protection / Grounding Instructions

    All parts that are susceptible to damage by Electrostatic Discharge (ESD) will be marked using the following label. Please follow the instructions below to ensure safety and to protect the parts from ESD damage. EMICON A.C. S.P.A. Pag. 14 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 15 4) If you only need to remove the Service Side cover, clip the ESD strap ground to the cover screw hole that is part of the compressor housing. See yellow arrows in Figure 3. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 16: Use

    In particular, the unit’s refrigerating capacity may be lower and its current draw may be higher than specified. However, operating limits must be abided by during unit operation, as indicated in table 1.1. EMICON A.C. S.P.A. Pag. 16 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 17 It is forbidden to exceed the limits set out in this paragraph while the unit is in operation without the manufacturer’s prior explicit authorisation. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 17 tel.
  • Page 18: Prohibited Use

    • agreed upon by contract. Please contact the manufacturer for clarifications on the use of the cooler EMICON A.C. S.P.A. Pag. 18 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 19: Description

    In the next paragraph will show the main characteristic components. The figure 2.1 shows the main parts of the unit. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 19 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 20: Structural Frame

    The motor is compatible with high-speed variable-frequency operation that affords high-speed efficiency, compactness and soft start capability. Compressors is designed for use with HFC-134a. Pag. 20 EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 21: Evaporator

    When the superheat gas temperatures are too low, they suggest to adjust the liquid flow by the Electronic Expansion Valve. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 22: Condenser Coil

    • High and low pressure guages, • high and low pressure switches, • evaporator temperature probes (inlet and outlet). EMICON A.C. S.P.A. Pag. 22 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 23: Electric Board

    • Fan control (step or variable speed); Auto/Manual control modes; • historical alarm list. • EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 23 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 24: Manufacturer Test

    The use of wrong values of nominal voltage and / or frequency outside the permitted range can cause malfunctions and / or faults and implies the expiry of the warranty terms offered by Emicon AC. In particular, this applies in any case where is used a nominal voltage of 400 V AC with 380 V AC power supplies.
  • Page 25: Motor Drive System

    The soft-start function and the variable-speed drive combined, limit the inrush current at start-up. Figure 2.2: Compressor component identification EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 25 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 26 Service-side access cover Capacitor side access cover Compressor I/O board Figure 2.2: Compressor component location EMICON A.C. S.P.A. Pag. 26 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 27 Inverter sends current, temperature, error, and DC bus voltage information to the BMCC via the Backplane. With the input gating signals, the IGBT Inverter controls the motor at a variable frequency of 0-750Hz. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 28: Compressor Controller

    Stop/start short cycle Motor cooling circuit failure (over temperature) • Refrigerant loss • Power supply • EMICON A.C. S.P.A. Pag. 28 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 29: Unit Technical Data

    Sight glass Temperature probe Non-Return valve Flooded evaporator PDSW Differential pressure switch Electronic expansion valve EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 29 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 30: Wiring Diagram

    Economizer: to increase the chiller Energy efficiency, growing the liquid sub-cooling in the thermal expansion valve inlet, tank to a refrigerant quantity took immediately after the filter and put in the 2 compressor stage inlet. EMICON A.C. S.P.A. Pag. 30 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 31: Refrigerant

    The evaporator is insulated externally with thermal insulation and anti condensation cladding, which has 19 mm thick instead 9 mm on the standard model. RAC series are available in various versions with different pressure sound. 2.9. Refrigerant The unit is designed to work with gas R134A. It contains no chlorine and it is considered ozone-safe and environment friendly.
  • Page 32: Installation

    The weight of some models could be unbalanced, it’s necessary check the unit stability before starting to handle it. For any unit handling, please follow the instructions shown in figure 3.1 , considering it as indicative. EMICON A.C. S.P.A. Pag. 32 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 33: Placing

    Manufacturer, in order to develop of common agreements on necessary measures. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 34 Figure 3.2: Service area It is recommended to verify the congruence between the tecnical data of the Manual’s unit and the project data. EMICON A.C. S.P.A. Pag. 34 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 35: Hydraulic Circuit

    Washing the hydraulic circuit once the pipes are placed by appropriate substances. So avoiding dirt • and solid particles remain in the tubes and to cause any damage. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 35 tel.
  • Page 36: Hydraulic Circuit Connections

    EMICON A.C. S.P.A. Pag. 36 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 37: Hydraulic Circuit Filling

    To use aggressive anti-freeze mixtures or not compatible with copper, carbon steel, aluminum and other materials which are used in its construction, it is forbidden. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 37 tel.
  • Page 38: Electric Connections

    The electrical system of the unit must to be projected by qualified draftsman and only expert electrical technicians appointed by the Client(Unit’s Owner) are allowed to perfom the electrical connections and in conformity with local regulations. EMICON A.C. S.P.A. Pag. 38 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 39: Power Supply Connection

    The power cable conductors must be connected to the free terminals upstream the main disconnecting switch, while the grounding conductor must be connected to the appropriate terminal PE or to the ground bar. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 39 tel.
  • Page 40: User's Terminal Board Connection

    When connecting the unit to the power supply, it is necessary to check that the phases are connected in the correct sequence. On this purpose, make sure that all electric motors rotation is right. EMICON A.C. S.P.A. Pag. 40 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 41: Safety Valve

    In any case, any pipes on the safety valves discharge must be manufactured according to laws and regulations in force. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 41 tel.
  • Page 42: Operation

    Initial survey Before starting-up, the unit must undergo a visual inspection by a technician with suitable expertise, including the following checks: EMICON A.C. S.P.A. Pag. 42 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 43 • the value of adjustment temperature and of the anti-freeze warning on the microprocessor must be set correctly. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 43 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 44: First Startup

    If the machine is expected to stay in this mode for more than 24 hours, the master switch must be turned to the OFF position in order to cut the power supply. EMICON A.C. S.P.A. Pag. 44 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 45: Winter Break

    Manufacturer. Inputting incorrect values may allow unit operation in out-of-specification conditions and, consequently, damage the machine and the whole system. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 45 tel.
  • Page 46: Maintenance

    Inside the unit there can be areas with high voltage. Works requiring access to such areas may be carried out only by qualified and trained personnel, authorised as provided by local laws and regulations in force. EMICON A.C. S.P.A. Pag. 46 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 47: Scheduled Maintenance

    Servicing during the unit’s operating lifetime and, in particular, scheduled leak detection, on-site inspections and check-ups of safety equipment, must be carried out as provided by local laws and regulations in force. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 48: Leak Detection

    ) For units installed on the European Union’s territory, leakage management must be carried out according to indications laid out in the (CE) Regulation 1516/2007. EMICON A.C. S.P.A. Pag. 48 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 49: Noise And Vibration Check

    The required personal protective equipment must be used at all times when working on the unit. In particular, it is necessary to at least wear protective spectacles, gloves, safety helmet and shoes. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 50 Check functioning of the coolant level sensor in the evaporator Check calibration of the coolant level sensor in the evaporator EMICON A.C. S.P.A. Pag. 50 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 51 Clean finned coils Check noise and vibration level of the fans Check the supply voltage of the fans EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 51 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 52 Carry out leak detection on the cooling line Check calibration and functioning of the safety high pressure switch EMICON A.C. S.P.A. Pag. 52 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 53: Routine Maintenance

    If the installation environment does not allow to preserve operating conditions similar to the nominal ones during a suitable period of time, contact the manufacturer to identify which procedures must be carried out. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 53 tel.
  • Page 54: Checking The Refrigerant Moisture Indicator

    Checking the guide it is also possible to see whether the level of coolant in the circuit is suitable or not. As a EMICON A.C. S.P.A. Pag. 54 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 55: Checking The Refrigerant Superheat

    The liquid coolant subcooling is the difference between the saturation temperature (bubble point in zeotropic blends, that is to say blends characterized by temperature glide) which conforms to the condensing pressure EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 56: Checking The Safety Devices To Avoid Electric Overcharges

    Table 5.3 indicates the most common types of device crashes that can occur, as well as the most probable causes and possible solutions according to each type. EMICON A.C. S.P.A. Pag. 56 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 57 3. The cooled water correct temperature is lower See trouble 2.d The microprocessor does not work EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 57 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 58 If all these controls give a positive result. EMICON A.C. S.P.A. Pag. 58 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 59 If all these controls give a positive result. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 59 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 60 Recharge the cooling system The operations described must to be to carried out from qualified and trained personnel EMICON A.C. S.P.A. Pag. 60 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 61 Check electric connections thermostatic expansion valve operation EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 61 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 62 Change the probe parameter in the The probe corresponding to the microprocessor; otherwise replace the alarm code is defective probe. EMICON A.C. S.P.A. Pag. 62 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 63: Extraordinary Maintenance

    When needed, comply with the national law and regulation on the transport of coolant fluid. Do not modify the unit or replace its components without the manufacturer's explicit approval. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 64: Opening The Cooling Circuit

    It is advisable to make sure it can work up to a pressure equal to 0.3 bar absolute. After performing maintenance on the refrigeration circuit, carry out the following activities: EMICON A.C. S.P.A. Pag. 64 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 65: Leak Test

    Do not use the compressor to create the vacuum. Do not use a megaohmeter to check the engine or feed the compressor when the vacuum has been created. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 65 tel.
  • Page 66: Refrigerant Charge

    Do not use a different coolant than the one indicated on the Data Plate. Use only new or recycled coolants with known composition and suitable features for use in refrigeration EMICON A.C. S.P.A. Pag. 66 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 67: Coolant Handling

    Clearly indicate the coolant quality (new, recycled, reused) on the containers to avoid mixing different kinds of fluid. Do not connect coolant containers to one another using a collector. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 67 tel.
  • Page 68: Procedures After Maintenance

    Record on the Register the quantity and type of coolant employed. Verify the unit tightness within one month from the leak repair to make sure the intervention was successful. EMICON A.C. S.P.A. Pag. 68 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 69 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 69 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 70: Dismantling And Disposal

    After draining the coolant, reduce the machine to single components. Dispose of them according to their features in accordance with existing local law and regulation. EMICON A.C. S.P.A. Pag. 70 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 71 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 71 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 72: T3C Chiller

    Fan control (step or variable speed); • • Auto/Manual control modes; historical alarm list. • EMICON A.C. S.P.A. Pag. 72 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 73: Compressor Control

    At that point, the state is changed into the operational state. Operational State: EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 73 tel.
  • Page 74: Individual Compressor States

    The shutdown state therefore switches into the idle stage when this compressor reaches full stop. Individual compressor states 7.2.2. Absent State: EMICON A.C. S.P.A. Pag. 74 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 75 (ie. when it has reached its operational state). Fault State: EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 75 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 76: Alarm Handling

    Correct baud rate for MCX master and all Danfoss Turbocor compressors (RS485-2); Correct address setup for individual Danfoss Turbocor compressors. • EMICON A.C. S.P.A. Pag. 76 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 77: User Interface

    7.4.2. Pressing the key when the unit is ON, you go to the menu described in the following table. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 77 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 78 Display input and output values Alarms Access to alarm menu Active Alarms List of the active alarms Alarm Log EMICON A.C. S.P.A. Pag. 78 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 79 The screen shows some data on specific compressors. If you press the or buttons, the screen changes to display additional data for that compressor. If you press LEFT or RIGHT, the screen switches to the next/previous compressor. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 79 tel.
  • Page 80 Input and output display 7.4.2.4. Menu I/O – Input/Output Sub-menu: IOd – I/O Display LCD display EMICON A.C. S.P.A. Pag. 80 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 81 • time since its activation in the format hours:minutes:seconds (seconds for LCD display • only). EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 81 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 82 EMICON A.C. S.P.A. Pag. 82 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 83: Keyboard

    Access to menus Alarms Admission to the list of active alarms Menu Backward scroll of menu EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 83 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 84: Alarms

    7.6. Alarms Group1: ALA – Alarms Group2: CFG – Configuration EMICON A.C. S.P.A. Pag. 84 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 85: Alarm Actions

    OFF; • action on the alarm relay, warning relay and buzzer. • EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 85 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail...
  • Page 86: Main Alarms Description

    Warning Code Alarm description type period delay (s) delay (s) unit OFF relay relay (min) EMICON A.C. S.P.A. Pag. 86 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 87 Warning Code Alarm description automatic type delay (s) delay (s) unit OFF relay relay period EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 87 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 88 General AI alarm 5 Semi Code Alarm description Reset Startup Steady Activi with Alarm Warning automatic EMICON A.C. S.P.A. Pag. 88 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 89 TC1 AC-Inverter temp TC1 AC-discharge temp TC1 AC-suction pressure TC1 AC-discharge pressure TC1 AC-3 phase current trip EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 89 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 90 TC2 AC-discharge temp TC2 AC-suction pressure TC2 AC-discharge pressure TC2 AC-discharge pressure TC2 AC-shaft cavity temp EMICON A.C. S.P.A. Pag. 90 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 91 TC3 AC-suction pressure TC3 AC-discharge pressure TC3 AC-3 phase current trip TC3 AC-shaft cavity temp EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 91 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 92 TC4 AC-discharge pressure TC4 AC-3 phase current trip TC4 AC-shaft cavity temp TC4 AC-leaving Air/Water EMICON A.C. S.P.A. Pag. 92 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 93: Parameters

    Code: acronym to identify the parameter. It clearly identifies the parameter and it is showed on the display. Description: parameter description to display on a LCD display. EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag.
  • Page 94 Text Values: list of mnemonic values that parameters can assume. The entering to the parameters visualization and modification mode is possible from menu. For a complete user interface description, please (see “7.4 User Interface”). EMICON A.C. S.P.A. Pag. 94 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel.
  • Page 95: Emicon A.c. S.p.a. Via A. Volta, 49 - 47014 Meldola (Fc) - Italy

    RAC – Use and Maintenance Manual ev. 4 10/18) Refrigerant safety data sheet EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 95 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 96 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. Pag. 96 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 97 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 97 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 98 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. Pag. 98 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 99 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 99 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 100 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. Pag. 100 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 101 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 101 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 102 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. Pag. 102 via A. Volta, 49 – 47014 Meldola (FC) – Italy tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...
  • Page 103 RAC – Use and Maintenance Manual ev. 4 10/18) EMICON A.C. S.P.A. via A. Volta, 49 – 47014 Meldola (FC) – Italy pag. 103 tel. (+39) 0543/495611 – fax. (+39) 0543/495612 – e-mail emicon@emiconac.it...