Current Draw and Audibility ratings
Figure 4 Light Output – Vertical Dispersion, Wall to Floor
Degrees*
5-30
35
40
45
50
55
60
65
70
75
80
85
90
*Tolerance of ±1 degree is permitted.
2.3 Current Draw and Audibility ratings
For the strobe, the current draw for each setting is listed in Table 2. For the horn strobe, the current draw and audibility settings are listed in
Table 3. Reference binational harmonized standard UL 464/ULC 525 for minimum sound level requirements.
Table 2 UL/ULC Maximum Strobe Current Draw (mA)
Candela
Rating
15
30
75
95
110
115
135
150
177
185
FCP*
*FCP Fire Control panel, future use
LED L-series Outdoor Horn Strobes and Strobes — P/N I56-0040-000 5/6/2024
Percent of Rating
0
100
90
65
46
34
27
22
18
16
15
13
12
12
12
16-33 VDC
Wall
Ceiling
18
22
70
75
85
—
105
—
—
120
(future)
(future)
Figure 5 Light Output – Vertical Dispersion,
*Tolerance of ±1 degree is permitted.
A0469-00
18
22
70
75
—
90
—
110
115
—
Configurations for Notification Appliances
Ceiling to Walls to Floor
Degrees*
Percent of Rating
0
5-25
30-45
50
60
65
70
75
80
85
90
100
90
75
55
45
35
35
30
30
25
25
A0468-00