WT01 Instruction English FIG. 1 - CONTENT • Thermostat • Sensor The thermostat is an electronic PWM/PI thermostat for temperature control by means of an NTC sensor located either externally or internally within the thermostat. The thermostat is for flush mounting in a wall socket. A baseplate for wall mounting is also available.
Page 8
WT01 English rectly in the floor. The sensor cable must be led through a separate conduit or segregated from power cables. The floor sensor must be centred between loops of heating cable. The sensor cable may be extended up to 100 m by means of a separate two-core cable.
Page 9
WT01 English the cover. Ensure that both the power slide button on the cover and the power switch pin in the thermostat are down. 3. Click the cover into place by applying light, even pressure. Warning! Do not apply pressure to the corners of the display cover or to the display itself.
Page 10
WT01 English Error codes E0: Internal fault. The thermostat must be replaced. E1: Built-in sensor defective or short-circuited. Replace the ther- mostat, or use the floor sensor only. E2: External sensor disconnected, defective or short-circuited. Reconnect the sensor if disconnected, or replace the sensor.
WT01 English TECHNICAL DATA Voltage ................ 100-240 VAC Max. pre-fuse ................16 A Built-in circuit breaker ..........2-pole, 16 A Output relay ........... make contact - SPST - NO Output ................max. 16 A Terminal wire size ............1.5-2.5 mm2 Control principle ..............PWM/PI Standby power ................