Micropilot FMR43 HART About this document About this document Document function These Operating Instructions contain all the information required in the various life cycle phases of the device: from product identification, incoming acceptance and storage, to installation, connection, operation and commissioning, through to troubleshooting, maintenance and disposal.
For an overview of the scope of the associated Technical Documentation, refer to the following: • Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the nameplate • Endress+Hauser Operations app: Enter serial number from nameplate or scan matrix code on nameplate. Endress+Hauser...
Android, Google Play and the Google Play logo are trademarks of Google Inc. Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. HART®...
The device fulfills general safety requirements and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this fact by affixing the CE marking. IT security Our warranty is valid only if the product is installed and used as described in the Operating Instructions.
Micropilot FMR43 HART Basic safety instructions Device-specific IT security The device offers specific functions to support protective measures by the operator. These functions can be configured by the user and guarantee greater in-operation safety if used correctly. The user role can be changed with an access code (applies to operation via the onsite display, Bluetooth or FieldCare, DeviceCare, asset management tools e.g.
Product description Micropilot FMR43 HART Product description Product design A0053675 1 Product design Micropilot FMR43 with sample process connections Electronics housing Process connection ½ thread Process connection NA Connect Tri-Clamp ISO2852 Process connection M24 Process connection NEUMO BioControl Incoming acceptance and product...
Micropilot FMR43 HART Incoming acceptance and product identification Check the following during incoming acceptance: • Is the order code on the delivery note (1) identical to the order code on the product sticker (2)? • Are the goods undamaged? • Do the data on the nameplate correspond to the order specifications and the delivery note? •...
Page 12
Incoming acceptance and product identification Micropilot FMR43 HART 4.3.2 Transporting the product to the measuring point WARNING Incorrect transport! The housing or sensor can be damaged or pull off. Risk of injury! ‣ Transport the device to the measuring point in its original packaging or by the process connection.
Micropilot FMR43 HART Mounting Mounting Mounting requirements 5.1.1 Mounting instructions During installation, it is important to ensure that the sealing element used has an operating temperature that corresponds to the maximum temperature of the process. • Devices with CSA approval are intended for indoor use •...
Mounting Micropilot FMR43 HART Mounting the device 5.2.1 Screwing in the device • Turn by the hex bolt only; max. torque 50 Nm (37 lbf ft) • M24 sensors: Mount with tool only on the parallel spanner flat, max. torque 30 Nm (22 lbf ft) •...
Page 15
Micropilot FMR43 HART Mounting 5.2.4 Process connections: MNPT/G 1½, NEUMO BioControl D50 PN16, 80 GHz; PEEK Information about the mounting nozzle The maximum nozzle length H depends on the nozzle diameter D. The maximum length of the nozzle H depends on the nozzle diameter D.
Mounting Micropilot FMR43 HART 5.2.7 Process connections: MNPT/G ½, 180 GHz; PTFE Information about the mounting nozzle The maximum nozzle length H depends on the nozzle diameter D. The maximum length of the nozzle H depends on the nozzle diameter D.
Micropilot FMR43 HART Electrical connection Electrical connection Connecting the device 6.1.1 Potential equalization If necessary, establish potential equalization using the process connection or the grounding clamp supplied by the customer. 6.1.2 Supply voltage 12 to 30 V on a direct current power unit The power unit must be safety-approved (e.g.
Page 18
Electrical connection Micropilot FMR43 HART to IEC/DIN EN 61326-1: Test level on DC power ports and input/output ports is 1 000 V line to earth. Overvoltage protection category According to IEC/DIN EN 61010-1, the device is intended for use in overvoltage protection category II networks.
The differences between the structure of the operating menus of the onsite display and the Endress+Hauser FieldCare or DeviceCare operating tools can be summarized as follows: The onsite display has a reduced menu to configure basic settings on the device.
Operation options Micropilot FMR43 HART "Diagnostics" menu Diagnostic information and settings as well as help for troubleshooting. "Application" menu Functions for detailed adjustment of the process for optimum integration of the device into the application. "System" menu System settings for device management, user administration or safety.
Page 21
Micropilot FMR43 HART Operation options Operating status LED (1) See diagnostic events section. Bluetooth LED (3) • LED lit: Bluetooth enabled • LED not lit: Bluetooth disabled or Bluetooth option not ordered • LED flashing: Bluetooth connection established Keypad lock LED (5) •...
Operation options Micropilot FMR43 HART Access to operating menu via onsite display Functions: • Display measured values and fault and notice messages • Display a symbol in the event of an error • Electronically adjustable onsite display (automatic and manual adjustment of measured value display in 90°...
Micropilot FMR43 HART Operation options 7.4.1 Operation Navigation Navigation by swiping with finger. Operation via the LED indicator is not possible if the Bluetooth connection is enabled. Selecting option and confirming Select the required option and confirm using the checkmark at the top right (see screens below).
Page 24
FieldCare Function range FDT-based plant asset management tool from Endress+Hauser. FieldCare can configure all smart field devices in a system and helps you manage them. By using the status information, FieldCare is also a simple but effective way of checking their status and condition.
Micropilot FMR43 HART System integration A0033202 4 QR code for free Endress+Hauser SmartBlue App Download and installation: 1. Scan the QR code or enter SmartBlue in the search field of the Apple App Store (iOS) or Google Play Store (Android).
Commissioning Micropilot FMR43 HART Device variable Measured value Tertiary variable (TV) Absolute echo amplitude Quaternary variable (QV) Relative echo amplitude Primary variable (PV) is always applied to the current output. The assignment of the measured values to the device variables can be changed in the following submenu: Application →...
Micropilot FMR43 HART Commissioning A0053357 Operating status LED Operating key "E" One-key commissioning LED Keypad lock LED 1. If necessary, disable keypad lock (see "Access to operating menu via LED indicator" > "Operation"). 2. Repeatedly press the "E" key briefly until the one-key commissioning LED flashes.
Commissioning Micropilot FMR43 HART 3. Once all the pages have been completed, click > to close the Commissioning wizard. If the Commissioning wizard is cancelled before all necessary parameters have been configured, the device may be in an undefined state. In such situations, it is advisable to reset the device to the factory default settings.
Micropilot FMR43 HART Commissioning Commissioning via additional operating tools (AMS, PDM, etc.) Download the device-specific drivers: https://www.endress.com/en/downloads For more details, see the help for the relevant operating tool. Configuring the device address via software See "HART address" parameter Enter the address to exchange data via the HART protocol.
Page 30
Commissioning Micropilot FMR43 HART 9.10.1 Level measurement in liquids 100% A0016933 6 Configuration parameters for level measurement in liquids Reference point of measurement Length of antenna + 10 mm (0.4 in) 50 to 80 mm (1.97 to 3.15 in); medium εr < 2...
Page 31
Micropilot FMR43 HART Commissioning 9.10.2 Level measurement in bulk solids 100% A0016934 7 Configuration parameters for level measurement in bulk solids Reference point of measurement Length of antenna + 10 mm (0.4 in) Distance Level "Empty calibration" parameter (= 0 %) "Full calibration" parameter (= 100 %) 9.10.3...
Operation Micropilot FMR43 HART During simulation of the switch output or current output, the device issues a warning message for the duration of the simulation. 9.11 Protecting settings from unauthorized access 9.11.1 Software locking or unlocking Locking via password in FieldCare/DeviceCare/SmartBlue app Access to parameter configuration of the device can be locked by assigning a password.
The Heartbeat submenu is only available during operation via FieldCare, DeviceCare or the SmartBlue app. The submenu contains the wizards that are available with the Heartbeat Verification and Heartbeat Monitoring application packages. Documentation on the Heartbeat Technology: Endress+Hauser website: www.endress.com → Downloads.
Remedial action: The standard user name is "admin" and the password is the device serial number indicated on the device nameplate (only if the password was not changed by the user beforehand) If the password has been forgotten, contact Endress+Hauser Service (www.addresses.endress.com) Endress+Hauser...
Page 35
For information on measures in the case of an error message: See "Pending diagnostic messages" section. If the measures do not rectify the problem, contact your Endress+Hauser office. 11.1.4 Additional tests If no clear cause of the error can be identified or the source of the problem can be both the device and the application, the following additional tests can be performed: 1.
Diagnostics and troubleshooting Micropilot FMR43 HART Parameter overview with brief description Parameter Description Selection / User entry Failure behavior current output Defines which current the output assumes in the case of an • Min. error. • Max. Min: < 3.6 mA Max: >21.5 mA Note: The hardware DIP Switch for alarm current has priority over software setting.
Micropilot FMR43 HART Diagnostics and troubleshooting "Out of specification (S)" option The device is operated: • Outside of its technical specifications (e.g. during startup or a cleaning) • Outside of the configuration performed by the user (e.g. level outside configured span) "Maintenance required (M)"...
Diagnostics and troubleshooting Micropilot FMR43 HART 11.6 Pending diagnostic messages Pending diagnostic messages are displayed in alternating sequence with the measured value display in the onsite display. Pending diagnostic messages can be displayed in the Active diagnostics parameter. Navigation: Diagnostics → Active diagnostics 11.7...
Page 39
Micropilot FMR43 HART Diagnostics and troubleshooting Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] Diagnostic of configuration Data transfer failed 1. Retry data transfer Alarm 2. Check connection Processing download Download active, please wait...
Diagnostics and troubleshooting Micropilot FMR43 HART Diagnostic Short text Remedy instructions Status Diagnostic number signal behavior [from the [from the factory] factory] HART Device Variable Check device specific diagnosis. Warning Alert Echo lost Check parameter "DC value" Warning In safety distance 1.
Micropilot FMR43 HART Diagnostics and troubleshooting 11.8.3 Overview of information events Info number Info name I1000 --------(Device ok) I1079 Sensor changed I1089 Power on I1090 Configuration reset I1091 Configuration changed I11074 Device verification active I1110 Write protection switch changed I11104...
Maintenance Micropilot FMR43 HART 11.9.2 Resetting the password via the operating tool Enter a code to reset the current "Maintenance" password. The code is delivered by your local support. Navigation: System → User management → Reset password → Reset password For details see the "Description of device parameters"...
13.1 General information 13.1.1 Repair concept The Endress+Hauser repair concept is devised in such a way that repairs can only be carried out through device replacement. 13.1.2 Replacing a device After the device is replaced, previously saved parameters can be copied to the newly installed device.
14.2 DeviceCare SFE100 Configuration tool for IO-Link, HART, PROFIBUS and FOUNDATION Fieldbusfield devices DeviceCare is available for download free of charge at www.software-products.endress.com. You need to register in the Endress+Hauser software portal to download the application. Technical Information TI01134S 14.3...
Micropilot FMR43 HART Accessories 14.5 Field Xpert SMT70 Universal, high-performance tablet PC for device configuration in Ex Zone 2 and non-Ex areas For details, see "Technical Information" TI01342S 14.6 Field Xpert SMT77 Universal, high-performance tablet PC for device configuration in Ex Zone 1 areas For details, see "Technical Information"...
Technical data Micropilot FMR43 HART Technical data 15.1 Input 15.1.1 Measured variable The measured variable is the distance between the reference point and the product surface. The level is calculated based on "E", the empty distance entered. 15.1.2 Measuring range The measuring range starts at the point where the beam hits the tank floor.
Page 47
Micropilot FMR43 HART Technical data 100% A0051658 Antenna tip + 10 mm (0.4 in) Usable measuring range 50 to 80 mm (1.97 to 3.15 in); Medium ε ≤2 Vessel height Reference point of the measurement, varies depending on the antenna system (see section on Mechanical...
Page 48
For the dielectric constants (DC values) of many media commonly used in industry, please refer to: • Dielectric constant (DC value) Compendium CP01076F • The Endress+Hauser "DC Values app" (available for Android and iOS) Measurement in storage vessel Storage vessel - measuring conditions Calm medium surface (e.g.
Page 49
Micropilot FMR43 HART Technical data Measurement in buffer vessel Buffer vessel - measuring conditions Moving medium surface (e.g. permanent free filling from above, mixing jets) Process connections MNPT/G ¾, G 1, M24, 80 GHz in buffer vessel Media group Measuring range A (ε...
Page 50
Technical data Micropilot FMR43 HART Process connection MNPT/G 1½, NEUMO BioControl D50 in buffer vessel Media group Measuring range A (ε 1.4 to 1.9) 3 m (10 ft) B (ε 1.9 to 4) 6 m (20 ft) C (ε 4 to 10) 13 m (43 ft) D (ε...
Micropilot FMR43 HART Technical data Process connections ½ and M24, 180 GHz in vessel with agitator Media group Measuring range A (ε 1.4 to 1.9) 4 m (13 ft) B (ε 1.9 to 4) 7 m (23 ft) C (ε...
Page 52
Technical data Micropilot FMR43 HART 15.2.2 Signal on alarm for devices with current output Current output Signal on alarm in accordance with NAMUR recommendation NE 43. • Max. alarm: can be set from 21.5 to 23 mA • Min. alarm: < 3.6 mA (factory setting)
Page 53
Micropilot FMR43 HART Technical data Pre-programmed linearization curves Linearization tables for calculating the volume in the following vessels are preprogrammed into the device: • Pyramid bottom • Conical bottom • Angled bottom • Horizontal cylinder • Sphere Other linearization tables of up to 32 value pairs can be entered manually.
Technical data Micropilot FMR43 HART • Loop current • Terminal current* • Not used Visible depending on the order options or device settings 15.3 Environment 15.3.1 Ambient temperature range Process connections MNPT/G ½, M24, Tri-Clamp, Neumo BioControl –40 to +80 °C (–40 to +176 °F) The permitted ambient temperature is reduced at higher process temperatures.
Page 55
Micropilot FMR43 HART Technical data °F °C °C °F A0054839 9 Ambient temperature T depending on the process temperature T –40 °C (–40 °F) +80 °C (+176 °F) +80 °C (+176 °F) +80 °C (+176 °F) +130 °C (+266 °F) +40 °C (+77 °F)
Technical data Micropilot FMR43 HART 15.3.7 Vibration resistance • Stochastic noise (random sweep) as per DIN EN 60068-2-64 Case 2/ IEC 60068-2-64 Case 2 • Guaranteed for 5 to 2 000 Hz: 1.25 (m/s /Hz, ~ 5 g 15.3.8 Shock resistance • Test standard: DIN EN 60068-2-27 Case 2 •...
Page 57
Micropilot FMR43 HART Technical data Process connections MNPT/G ¾, MNPT/G 1½, G1, 316 L Antenna 80 GHz, PEEK Seal Process pressure range –10 to +130 °C (+14 to +266 °F) –1 to 20 bar (–14.5 to 290 psi) 150 ° (302 °F) For max. 20 min EPDM –40 to +130 °C (–40 to +266 °F)
The pressure range may be further restricted in the event of a CRN approval. 15.4.2 Dielectric constant For liquids ε ≥ 1.2 For bulk solids ε ≥ 1.6 For applications with lower dielectric constants than indicated, contact Endress+Hauser. 15.5 Additional technical data Current Technical Information: Endress+Hauser website: www.endress.com → Downloads. Endress+Hauser...