Section 2 NS Series Functions
NS Series Programming Manual
Operations When Communications Errors Occur
A communications error will occur if an attempt is made to read or write to a communications address
in an unconnected host. This function is used to set whether or not to continue with subsequent set
operations or to interrupt the operations when such a communications error occurs.
Interruption of operations can only be selected for synchronous communications. Operations will con-
tinue for asynchronous communications.
Continue operations
Example
Write Bit
Write Word
Write String
N
o
t
e
N
o
t
e
N
o
t
e
Whether or not to continue operation after a communications error is set on the Expansion Set-
ting Tab Page in the Property Settings Dialog Box for Multifunction Objects.
If a communications error caused by something other than communications with an unconnected
host occurs, the error message display will be followed by the System Menu. For this reason,
Multifunction Object processing will be canceled.

2-11-5 Canceling Multifunction Object Processing

More than one function can be executed using a Multifunction Object, but if an error occurs during
execution or if the execution of the operation is cancelled, Multifunction Object processing is stopped.
In such cases, the functions set for execution after the cancelled function will not be executed.
Write Bit
Write Word
Write String
N
o
t
e
N
o
t
e
N
o
t
e
Refer to the previous section Operations When Communications Errors Occur for information on
operations when a communications error occurs.
Refer to the description of each function if Multifunction Object processing is stopped.
Communications
error
The next function is
executed when the error
message is closed.
Executed
This function is not executed because
processing of the Multifunction Object
has been stopped.
Interrupt operations
Example
Write Bit
Write Word
Write String
Click the No
Button in the Write
Confirmation
Dialog Box.
2-168
2-11 Multifunction Objects
Communications
error
All operations will be
interrupted after a
communication error occurs.
The Multifunction
Object processing
will be stopped.