Phase-sequence phase-loss relay

Advertisement

■ Specifications
Ambient operating temperature
Storage temperature
Ambient operating humidity
Storage humidity
Altitude
Voltage fluctuation range
Input frequency
Output relays
Resistive load
Inductive load
Minimum load
Maximum contact voltage 250 VAC
Maximum contact current 6 A AC
Maximum switching
capacity
Mechanical life
Electrical life
Terminal screw tightening torque
Crimp terminals
Insulation resistance
Degree of protection
Case color
Case material
Weight
Mounting
Dimensions
Installation environment
Application standards
Safety standards
EMC
Cat. No. N145-E1-01
−20 to 60°C (with no condensation or icing)
−40 to 70°C (with no condensation or icing)
25% to 85%
25% to 85%
2,000 m max.
85% to 110% of rated input voltage
50/60 Hz ±5 Hz (AC power supply)
6 A at 250 VAC (cos φ = 1)
6 A at 30 VDC (L/R = 0 ms)
1 A at 250 VAC (cos φ = 0.4)
1 A at 30 VDC (L/R = 7 ms)
10 mA at 5 VDC
1,500 VA
10,000,000 operations
Make: 50,000 times, Break: 30,000 times
1.2 N·m
2
Two solid wires of 2.5 mm
, two crimp terminals of 1.5 mm
tightened together
20 MΩ (at 500 V) between charged terminals and exposed uncharged parts
20 MΩ (at 500 V) between any charged terminals (i.e., between input, output, and power
supply terminals)
Terminal section: IP20, Rear case: IP40
Munsell 5Y8/1 (ivory)
ABS resin (self-extinguishing resin) UL94-V0
200 g
Mounted to DIN Track or via M4 screws
22.5 (W) x 90 (H) x 100 (D) mm
Overvoltage Category III, Pollution Degree 2
EN60255-5/-6
EN60664-1
EMI: EN61326 Industrial applications
Electromagnetic interference wave
CISPR11 Group 1, Class A: CISPR16-1/-2
Terminal interference wave voltage
CISPR11 Group 1, Class A: CISPR16-1/-2
EMS: EN61326 Industrial applications
Electrostatic discharge EN61000-4-2: 8 kV (in air)
Radiating radio-frequency electromagnetic field EN61000-4-3:
10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz)
Burst EN61000-4-4:
Surge EN61000-4-5:
Conducted RF EN61000-4-6:
Power frequency magnetic field immunity
EN61000-4-8: 30 A/m
Voltage dip/short interruptions
EN61000-4-11: 0.5 cycle, 0.180° each, polarity 100% (rated voltage)
Phase-sequence Phase-loss Relay
2
with insulation sleeves, can be
1 kV (I/O signal line), 2 kV (power line)
1 kV with line (power line),
2 kV with ground (power line)
3 V (0.15 to 80 MHz)
K8AB-PH
3

Advertisement