DA70 8 Analog Output Module
Installation Guide
z High density analog output module for the DA70
z Available outputs include: 0 to 5 VDC, 0 to 10 VDC, ±5 VDC,
±10 VDC, and 0/4 to 20 mA DC
z Outputs are isolated from each other and from the backplane
z Outputs are software configured and fully scalable
U L
FOR USE IN HAZARDOUS LOCATIONS:
C C
US
US
R
Class I, Division 2, Groups A, B, C, and D
LISTED
T4
IND.CONT. EQ.
E317425
MODULE PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- DIN rail mount DA 8AO Module
- Installation Guide
GENERAL DESCRIPTION
The DA 8AO is an analog output module designed for use with
the DA70 products. The module provides eight isolated outputs
that are independently programmable for output ranges of 0-5 V,
0-10 V, ±5 VDC, ±10 V, 0/4-20 mA DC. Internal scaling is
provided to accommodate virtually any application.
The modules connect and communicate via a proprietary
connection to the DA70 host device. The DA70 equipped with
serial ports as well as an Ethernet port(s), allows the system to
share data with PCs, PLCs, and SCADA systems. The maximum
number of modules for each DA70 device is 10.
Internal power management circuits allow the module to be
replaced while power is applied, which reduces downtime in the
event of a module failure. All configuration information is stored
locally within the module, as well as in the Host, so replacement
modules do not need to be configured.
CONFIGURATION
The DA8A0 module is configured with Windows
Crimson
®
software. The software is an easy to use, graphical
DIMENSIONS In Inches [mm]
0.49
4.53 [114.97]
[12.51]
32
31
30
29
28
27
26
25
24
23
22
21
20
6.00
19
18
17
16
[152.40]
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
0.45 [11.50]
®
compatible
1.91
[48.51]
1.35
[34.32]
6.22
[157.91]
interface which provides a means of configuration and
commissioning of new systems, as well as routine module
re-calibration.
SAFETY SUMMARY
All safety related regulations, local codes as well as instructions
that appear in this document or on equipment must be observed
to ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not consistent with these specifications.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l'installation et
l'utilisation de l'appareil.
WARNING - Explosion Hazard - Substitution of
components may impair suitability for Class I, Division 2
AVERTISSEMENT - Danger d'explosion - Le
remplacement de composants peut nuire à l'aptitude à la
classe I, division 2
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des
endroits de classe I, Division 2, Groupes A, B, C, D, ou
dans des endroits non dangereux seulement.
WARNING - Explosion Hazard - Not hot swappable. Do
not remove or replace while circuit is live unless the area
is free of ignitible concentrations.
AVERTISSEMENT - Danger d'explosion - Non échangeable
à chaud. Ne pas retirer ou remplacer sous tension sauf si la
zone est exempte de concentrations inflammables.
1
DA8AO- D
Drawing No. LP1121
Revised 05/2024
II 3 G Ex ec IIC T4 Gc
DEMKO 20 ATEX 2268X
IECEx UL 20.0007X
UL22UKEX2576X

Advertisement

loading
Need help?

Need help?

Do you have a question about the DA70 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Redlion DA70

  • Page 1 The modules connect and communicate via a proprietary safeguards. Red Lion disclaims any responsibility for damages, connection to the DA70 host device. The DA70 equipped with either direct or consequential, that result from the use of this serial ports as well as an Ethernet port(s), allows the system to equipment in a manner not consistent with these specifications.
  • Page 2 Isolation Level: The outputs are isolated from each other, and are isolated from the power supply. 500 Vrms @ 50/60 Hz for 1 minute between any of the outputs and the Host power supply input. 5. COMMUNICATIONS: Provided by the DA70 Controller MODULE CRADLE 6. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: -40 to 75 °C T...
  • Page 3 Revised 05 2024 Drawing No. LP1121 Installing Module into Cradle MODULE HOT SWAPPING Push module into cradle until you hear an audible click If the area is known to be non-hazardous (free of ignitable indicating it is properly latched. concentrations), then a module can be removed and/or installed into a cradle attached to the controller while power is applied.
  • Page 4 “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY;...