Model GMOUT - Graphite
Installation Guide
U L
FOR USE IN HAZARDOUS LOCATIONS:
C C
US
US
R
Class I, Division 2, Groups A, B, C, and D
LISTED
T4
IND.CONT. EQ.
E317425
GENERAL DESCRIPTION
The model GMOUT is an analog output module designed for
use with the Graphite products. The module provides four
isolated outputs that are independently programmable for output
ranges of 0-5V, 0-10 V, +/-10 V, 0-20 mA, or 4-20 mA. Internal
scaling is provided to accommodate virtually any application.
The modules connect and communicate via proprietary USB
connection to the various Graphite devices. The Graphite devices,
equipped with serial ports as well as an Ethernet port(s), allows
the system to share data with PCs, PLCs, and SCADA systems.
The maximum number of modules various for each Graphite
device, see specific models for details.
Once programmed, the module will continue to operate/
control independent of the Graphite device as long as power is
applied. Remove power from the host device before installing or
replacing any modules.
CONFIGURATION
The Graphite is configured with Windows
software. The software is an easy to use, graphical interface which
DIMENSIONS In inches (mm)
2.97 (76)
4.65
(118)
®
Output Module
®
®
compatible Crimson
1.25 (32)
1
4-Channel Analog
z High density analog output module for the Graphite
products
z Available outputs include 0 to 5 VDC, 0 to 10 VDC, ±10
VDC, and 0/4-20 mA DC
z Outputs are isolated from each other and from the
backplane
z Outputs are software configured and fully scalable
U L
C C
US LISTED
US LISTED
R
IND. CONT. EQ.
E302106
provides a means of configuration and commissioning of new
systems, as well as routine module re-calibration.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that
appear in this document or on equipment must be observed to
ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not specified.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
WARNING - EXPLOSION HAZARD - Do not disconnect
equipment unless power has been switched off or area is
known to be non-hazardous.
WARNING - EXPLOSION HAZARD - Substitution of
components may impair suitability for Class I, Division 2
ORDERING INFORMATION
DESCRIPTION
Graphite Module, 4 Analog Outputs
A listing of the entire Graphite family of products and accessories
can be found at www.redlion.net.
Install - GMOUT- J
Drawing No. LP0920
Revised 04/2023
II 3 G Ex nA IIC T4 Gc
-40°C ≤ T
≤ 75°C
AMB
DEMKO 14 ATEX 1387X
IECEx UL 15.0035X
UL22UKEX2574X
PART NUMBER
GMOUT400
Need help?
Do you have a question about the GMOUT and is the answer not in the manual?
Questions and answers