GENERAL DESCRIPTION
The model GMOUT is an analog output module designed for
use with the Graphite products. The module provides four
isolated outputs that are independently programmable for output
ranges of 0-5V, 0-10 V, +/-10 V, 0-20 mA, or 4-20 mA. Internal
scaling is provided to accommodate virtually any application.
The modules connect and communicate via proprietary USB
connection to the various Graphite devices. The Graphite devices,
equipped with serial ports as well as an Ethernet port(s), allows
the system to share data with PCs, PLCs, and SCADA systems.
The maximum number of modules various for each Graphite
device, see specific models for details.
Once programmed, the module will continue to operate/
control independent of the Graphite device as long as power is
applied. Remove power from the host device before installing or
replacing any modules.
DIMENSIONS In inches [mm]
2.97 [76]
4.65
[118]
®
4-Channel Analog
Output Module
z High density analog output module for the Graphite
z Available outputs include 0 to 5 VDC, 0 to 10 VDC, ±10
z Outputs are isolated from each other and from the
z Outputs are software configured and fully scalable
C C
CONFIGURATION
software. The software is an easy to use, graphical interface which
provides a means of configuration and commissioning of new
systems, as well as routine module re-calibration.
SAFETY SUMMARY
that appear in this document or on equipment must be observed
to ensure personal safety and to prevent damage to either the
device or equipment connected to it.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not consistent with these specifications.
1.25 [32]
ORDERING INFORMATION
DESCRIPTION
Graphite Module, 4 Analog Outputs
A listing of the entire Graphite family of products and accessories
1
products
VDC, and 0/4-20 mA DC
backplane
U L
US LISTED
US LISTED
R
IND. CONT. EQ.
E302106
The Graphite is configured with Windows
All safety related regulations, local codes as well as instructions
Do not use these products to replace proper safety interlocking.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
WARNING - EXPLOSION HAZARD - Do not disconnect
equipment unless power has been switched off or area is
known to be non-hazardous.
WARNING - EXPLOSION HAZARD - Substitution of
components may impair suitability for Class I, Division 2
can be found at www.redlion.net.
Install - GMOUT- K
Drawing No. LP0920
Revised 11/2023
II 3 G Ex nA IIC T4 Gc
-40°C ≤ T
≤ 75°C
AMB
DEMKO 14 ATEX 1387X
IECEx UL 15.0035X
UL23UKEX2879X
®
compatible Crimson
PART NUMBER
GMOUT400
®

Advertisement

loading
Need help?

Need help?

Do you have a question about the Graphite GMOUT and is the answer not in the manual?

Questions and answers

Summary of Contents for Redlion Graphite GMOUT

  • Page 1 WARNING - EXPLOSION HAZARD - Substitution of [118] components may impair suitability for Class I, Division 2 ORDERING INFORMATION DESCRIPTION PART NUMBER Graphite Module, 4 Analog Outputs GMOUT400 A listing of the entire Graphite family of products and accessories can be found at www.redlion.net.
  • Page 2 Graphite system. Some modules, depending on usage may consume high levels Consult the user manual or www.redlion.net/OpTemp of power. This may limit the total number of modules that can further details. be installed on a single Graphite host. Check the Graphite Storage Temperature Range: -40 to +85 °C T...
  • Page 3 Drawing No. LP0920 LEDs EMC INSTALLATION GUIDELINES Visit http:/ /www.redlion.net/emi for more information on EMI STS - STATUS LED guidelines, Safety and CE issues as they relate to Red Lion The Status LED is a green LED that provides information products.
  • Page 4 “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY;...

This manual is also suitable for:

Graphite gmout400